ST AN576 Application note

AN576
APPLICATION NOTE
PCB LAYOUT OPTIMISATION
INTRODUCTION
Protection requirements are becoming more and more well known and are often defined by rules or stan­dards. To satisfy these requirements, there is, in the majority of cases, a standard solution or a dedicated product.
However, knowledge of the disturbances and the use of suitable protection devices are not sufficient in themselves to solve the problem. In many applications, the correct design of the PCB layout is essential for success.
Figure 1. Classical protection circuit
Track B
Track A
I
DEVICE
DISTURBANCE
SOURCE
INFLUENCE OF THE PROTECTION LOCATION
The circuit presented in Figure 1 shows the classical approach for the protection location. Here the pro­tection device (see Note 1) is located close to the module to be protected. When a disturbance occurs on the track A the TRANSIL P clamps the surge at a maximum voltage V part.
During this clamping action there is a current through P and also in the track A. This phenomenon induces a voltage on track B, where it is close to A. To avoid this undesirable parasitic overvoltage on track B, the circuit of Figure 2 is recommended.
Note: 1. TRANSIL devices are used as examples throughout this document, but the same arguments are valid for TRISILS.
V
CL
P
TO BE
PROTECTED
and thus protects the sensitive
CL
REV. 2A - 3588
1/6May 2004
AN576
Figure 2. Recommended protection location
Track B
P
Track A
V
CL
DEVICE
TO BE
PROTECTED
I
DISTURBANCE
SOURCE
In this case the current due to the clamping phase of P remains located in the disturbance area and the track B is not affected.
To summarize, it is recommended that the protection device is located as close as possible the distur­bance source. For example, all the lines coming into the board ought to be protected close to the connec­tor.
INFLUENCE OF THE PCB LAYOUT ON THE ESD PROTECTION
These days, printed circuit boards are often auto-routed by computer aided design and the track lengths are not optimized.
Figure 3. Non-optimized LAYOUT for ESD
A
P
U
DISTURBANCE
SOURCE
B
DEVICE
TO BE
PROTECTED
Figure 3 shows the classical non-optimized layout. When a surge occurs the protection device P acts and there is a clamping voltage V
across it. Due to the fast rise time of the ESD overvoltage there is a high
CL
di/dt between the points A and B. This di/dt generates, in the parasitic inductances located between A and P and between B and P, overvoltages up to several hundred volts. So the applied voltage V across the device to be protected is the sum of the clamping voltage and the voltage across the parasitic inductance: thus the sensitive module is not protected.
2/6
Loading...
+ 4 hidden pages