ST AN303 Application note

ST AN303 Application note

AN303

Application note

Thyristors and TRIACs: latching current

Introduction

The purpose of this note is to familiarize TRIAC or thyristor (SCR) users with the latching current IL.

The importance of this parameter is illustrated with some typical examples. Procedures are given for measurement of IL. The variation of IL with operating conditions and device sensitivity are described.

This application note presents only the TRIAC case. However, the concepts are valid for SCRs (except for the various conduction modes).

Definition

The latching current (IL) of a TRIAC is the minimum value of the load current (current flowing between electrodes A2 and A1) that keeps the device conducting when the gate signal is removed (see Figure 1).

Figure 1 below shows the latching current and the gate current pulse. After the TRIAC triggering, a current (IT) flows through the TRIAC. If the gate current (IG) is removed while the current IT is lower than the latching current IL, the TRIAC switches off.

Figure 1. Blocked TRIAC

IG

 

 

 

 

IG > IGT

 

 

 

RL

 

 

 

 

IT

Gate current

t

A2

IT

IG

 

 

IL

 

 

A1

 

 

 

G

 

 

 

 

 

 

Main current

 

 

 

 

 

t

 

 

April 2009

Doc ID 3654 Rev 3

1/13

www.st.com

Application examples

AN303

 

 

1 Application examples

The importance of the latching current is highlighted by the following application examples.

1.1Example 1: low power lamp control

In the application circuit shown in Figure 2 a TRIAC is used to control a 10 W signaling light.

For the European mains (Vrms = 230 V), the peak load current is about 61 mA. A Z01 device could be used to control this load current, but the maximum latching current is specified as

50 mA if a Z0110 device is used in quadrant II. The peak load current is then very close to the maximum latching current given in the datasheet. The device will turn off if the gate current pulse is too short.

Figure 2. Control of a low-power lamp

 

 

IT

 

 

IL

 

Lamp (10 W)

Main

 

 

current

 

 

t

230 V

IT

A2

 

IG

 

 

A1

 

 

G

 

 

IG

 

 

Gate

 

 

current

 

 

t

 

 

tp

Thus, a TRIAC could not remain on if its latching current is higher than the load current at the moment the gate current is removed (refer to Figure 2). For correct operation, a continuous gate current should be applied or a longer gate current pulse should be applied.

For example, for a sinusoidal load current (I(t) = Ipeak x sin(ωt)), the pulse width is given by the following equation (refer to AN302 for a complete definition of IH(a)):

tp > 1ω · arcsin(IHMAXIpeak ) + 1ω · arcsin (IILMAXpeak )

To reduce the pulse width duration, a more sensitive TRIAC could be used (for example, for the Z0103 IL max is 15 mA in QII).

a. The minimum current that keeps a TRIAC conducting is called the hypostatic or holding current IH.

2/13

Doc ID 3654 Rev 3

AN303

Application examples

 

 

1.2Example 2: inductive load control

When a TRIAC controls an inductive load (L), the rise of the load current IT is slowed down. The approximate load current slope dIT/dt is given by:

dIT ~ VA dt = L

where VA is the mains voltage when the gate signal is applied.

In Figure 3 the impact of the gate pulse width on the TRIAC conduction is shown.

In continuous lines: A short gate signal (T1) is applied. The TRIAC doesn’t remain in

the on state because the load current IT doesn’t reach the TRIAC latching current level before the gate current removal.

In dotted lines: A longer gate signal (T2) is applied. In this case, the TRIAC turns on and remains in the on state. The TRIAC turns off when the load current reaches zero after the gate current removal.

Figure 3. Control of an alternating current (AC) motor

M

 

 

I

A2

IG

T VT

A1 G

 

 

IG

T1

t

 

 

T2

 

 

VT

VA

t

IG

IL

t

For correct operation a gate current has to be applied until the load current reaches the TRIAC latching current. The control mode shown in Figure 3 is a square pulse.

Another TRIAC control mode is to apply a gate pulse train. Application note AN308 offers some TRIAC control circuits specially designed to work with inductive loads.

Doc ID 3654 Rev 3

3/13

Application examples

AN303

 

 

1.3Example 3: varying power load control

For most applications, the load power is controlled by the TRIAC conduction time. For arc welding (see Figure 4), the controlled power can be subjected to considerable variations. The device current rating is chosen and validated for full-wave and full load operation. The application operation is then ensured in the worst case but, for low power loads, a TRIAC triggering issue could occur.

In the case of an open load operation, the load current equals the transformer magnetizing current, which is much lower than full load current. The load current could even be below the TRIAC latching current in one triggering quadrant. Thus, the TRIAC could turn on properly in one quadrant but could not turn on in another quadrant, for which the latching current is higher. An unbalance then occurs and induces a direct current (DC) through the transformer, which heats its coils and can cause transformer failure.

For correct circuit design, the TRIAC operation should be validated in full load and also in open load. (See AN308 for a schematic circuit diagram dedicated to this welding application.)

Figure 4. Arc welding control

G

A2

A1

4/13

Doc ID 3654 Rev 3

Loading...
+ 9 hidden pages