AN1296
Application note
Ring wave tests with ACS108 driving valves and pumps
Introduction
In this application note, test results obtained using ACS108 AC switch devices are
presented in order to analyze their behavior when subjected to standard ring wave surges.
The behavior of these devices subjected to a 1.2/50 µs impulse wave is specified in the
datasheets.
The test procedure is described in the UL858A standard. The only difference with the tests
below is that the normalized waveform is applied directly to the semiconductor and the load
(refer to Figure 1).
No coupling network is used to apply the surges while the system is connected to the mains
terminals. The only stress is due to the breakover turn-on current. The current conduction
during half mains cycle is not an issue.
The ACSs are not triggered by their gate - they turn on by over voltage when the generator
voltage exceeds their clamping level. The surge is then applied across the load and the load
current flows through the ACS™ which is in the on state.
Figure 1. Test diagram
Load
Over voltage
protection
(Trisil™-like)
TM: Trisil is a trademark of STMicroelectronics
Ringwave
generator
AC power
switch
Integrated
driver
IOUT
OUT
G
COM
RG = 150W
All the following oscillograms have been produced using the equipment listed below:
● Tektronix TDS754A scope
● Tektronix voltage P6013A probe (1/1000 ratio)
● Eurocraft pulse current transformer (1 V /10 A ratio)Tektronix TCP202 current probe
TM: ACS is a trademark of STMicroelectronics
June 2010 Doc ID 8159 Rev 3 1/8
www.st.com
Results AN1296
1 Results
Three kinds of loads have been used during the tests.
● Val ve
● Pump
● Resistor rated at 5 W, 150 Ω
1.1 Valve
The valves used were rated for 120 V, 50 mA, 60 Hz operation. Two different types of
behavior can appear during ring wave test when using such valves.
● The valve insulation is sufficient: when the ACS turns on, the current is limited by the
load inductor. Only a capacitive current (approximately 250 mA peak, see Figure 2) can
be seen during the rise of voltage across the switch. Such a turn on is not stressful for
the device.
Figure 2. 3 kV surge with a well insulated valve
V
(200 V/div)
out
I
(0.5 A/div)
out
2/8 Doc ID 8159 Rev 3
AN1296 Results
● The valve insulation is not sufficient: in this case, the valve oil winding insulation breaks
down when the switch turns on, i.e. when the whole surge voltage is applied across the
valve. The load then behaves like a short-circuit. The ACS current is no longer limited
and could reach up to 120 A (refer to Figure 3). The conduction losses could then be so
high that the die silicon could melt or its bonding wires could fuse and cause the
destruction of the device package. In practice, as the test is done with the complete
equipment including clamping devices or filters, this behavior does not occur.
Figure 3. 3 kV surge with an insufficiently insulated valve
V
(200 V/div)
out
I
(50 A/div)
out
Doc ID 8159 Rev 3 3/8