S+S Regeltechnik HYGRASGARD KFTM-LQ-CO2-Modbus, HYGRASGARD AFTM-LQ-CO2-Modbus, AERASGARD ALQ-CO2-Modbus, AERASGARD AFTM-LQ-CO2-Modbus, AERASGARD ACO2-Modbus User Manual

...
HYGRASGARD® AFTM- ⁄ KF TM - LQ - CO2 - Modbus
G
The maintenance-free microprocessor-controlled on-wall or duct sensor with Modbus connection with/without optional display is an all-in- one device used for det ecting all rele vant measured values, such as humidity, temperature, CO and control of the ent ire room climate. It measures C O / HIGH, temperatures in the range from –35...+80 °C as well as relative air humidity of 0...100 % r.H. Relative humidit y (% r.H.) is the quotient of water vapour partial pressure divided by the sat uration vapour pressure a t the respective gas t emper atur e. A digital, long-term stable sensor as a measuring element for relative humidity and temperature guarantees exact measurement results. T he CO sensor (non-dispersive inf ra-red technology). The detection range of the sensors is calibr ated f or sta ndard applica tions such as monitoring residential rooms and conf erence rooms. Room ventilation on an as-needed basis, improved well-being and cust omer benefit, increased co mfor t as well as reduced operating costs through energy c onser vation are just some of the benefits of employing the AERASGARD there are applications for C O crucial fact or in this respect is that both of these measurands are not convertible into each ot her and derivations An NDI R - CO
measuring instrument measures selectively and cannot det ect any VOCs; a VOC mixed gas sensor cannot detec t CO2 molecules.
2
measu rements, for VOC measurements, bu t from our perspective, above all, for a
2
in the range from 0...5000 ppm, VOC in one of three select able sensitiv ity levels LOW / MEDIUM
2
concentration and air quality (VOC), thus enabling effective monitoring
2
content of the air is measured using an opt ical NDIR
2
®
CO2. The abo ve explanations demo nstrate that
combination of both measurands. The
to or fr om one another canno t be made.
TECHNICAL DATA
Power supply: 24 V AC ⁄ D C (± 10 %) Power c onsumption: < 4.8 W ⁄ 24 V DC typical; < 6.8 VA ⁄ 24 V AC typical; peak current 200 mA Data points: temperature, rela tive humidit y, air quality (VOC), carbon dioxide (CO
HUMIDITY
Sensors: digital humidity sensor with integrated temperature sensor, low hysteresis, high long-term stability
plastic
Sensor protection:
sinter filter, Ø 16 mm, L = 35 mm, exchangeable (optional Measur ing range, humidity: 0...100 % r. H. Opera ting range, humidity: 0...95 % r. H. (non- precipitating air)
± 2.0 %
Devia tion hu midity: typic ally
(20...80 % r. H.) at +25 °C, otherw ise ± 3.0 %
TEMPERATURE
Measur ing ran ge, temp eratu re: –35...+80 °C Operating range, temperature: –10...+60 °C Deviation, temperature: ± 0.2 K at + 25 °C
AIR QUALITY (VOC)
VOC sensor: VOC measuring range: 0...100 % air quality; with r efer ence to calibration gas;
VOC sensor (metal oxide)
with automatic calibration
(VOC = volatile organic compounds)
multi-range switching
VOC measuring accura cy: ± 20 % final value (with reference to the calibration gas) Service life: > 60 months (under normal load conditions)
CARBON DIOXIDE (CO2)
CO2 sensor:
Optical NDIR sensor (no n-dispersive infr a-red technology) incl. atmospheric air pr essur e compensation (up to 1100 mbar)
with automatic and manual calibration
CO2 measuring range: 0...5000 ppm
measur ing accuracy: ± 30 ppm ± 3 % of measur ed value
CO
2
temperature dependence:
CO
2
Press ure dep endenc e: ± 0.13 % ⁄ m m Hg
± 5 ppm ⁄ °C o r ± 0.5 % of me asured value ⁄ ° C (whi chever is the g reate r)
Long-term stability: < 2 % in 15 years Gas exchange: by diffusion Bus parameters: Bus inte rfa ce: RS 485,
In the absence of current delivery
galvanically isolated,
In case of a g reat er numb er of dev ices, RS 4 85 transceivers mu st be used.
Bus pr oto col: Modbus (RTU-Mode), address range 0...
(under currentless conditions) can be
bus ter mination can be activated v ia DIP switch. Up to 32 dev ices possible in one segment.
247
selectable Baud ra te: 9600, 1920 0, 38400 Baud Stat us indic ator: Green L ED = Telegram valid / red LED = Telegr am error Signal filtering: 4 s / 32 s
Ambient temperature: –10...+ 60 °C Response time: < 2 minutes Electrical connection: 0.2 - 1.5 mm Enclosure: plastic, UV-st abilised, material polyamide, 30 % glass-globe reinforced,w ith quick-locking screws (slotted ⁄
Phillips head combination), colour tra ffic white (similar t o RAL 9016),,enclosure c over for displa y is transpare nt!
2
, via push -in ter minal
Enclosure dimensions: 126 x 90 x 5 0 mm ( Tyr 2) Cable gland: 2 x M 16 x 1.5; including strain relief, exchang eable Protective tube:
KCO2 /
KLQ - CO2 /
PLEUROFORMTM, mater ial: poly amide (PA6), with torsion protection, v
with out fil ter: NL = 2 02.5 mm, wi th plast ic sinter filter: NL = 235 mm (optional with metal sinter filter: NL = 227 mm )
AFTM - C O2 / in stainless s teel,
KFTM - C O2 /
AFTM - L Q - CO2 - Modbus:
Ø 16 mm, with plastic sinter f ilter: NL = 55 mm (optional with met al sinter filter: NL = 47 m m)
KFTM - L Q - CO2 - Modbus (Paten t No. DE 10 2014 010 719.1):
Process connection: channel sensor s using a flange (in cluded in the scope of delivery), on-wall sensor s using screws Prot ection class: III (according to EN 6 0 730) Protection type: IP 65 (ac cording to EN 60 529) enclosure only! (PLEUROFORM IP 30) Standards: CE-conformity, electr omagnetic compatibility a ccording to EN 61 326, EMC directiv e 2014 ⁄ 30 ⁄ EU Optional:
three-line display with illumination,
to displa y the actual humidity, actual t emper atur e, air quality and / or the actual CO
cuto ut appr ox. 70 x 40 mm (W x H),
14
), atmospheric pressure
2
metal
sinter filter, Ø 16 mm, L = 32 mm)
VOC sensitivity low, medium, high
configured and addr essed via DIP switch!
= 30 m/s (air), Ø 20 mm,
max
content
2
HYGRASGARD® AFTM- ⁄ KF TM - LQ - CO2 - Modbus
offset
°C
r.H.
VOCCO²
mode address
12345678
ON
DIPA
123456
ON
DIPB
zero
CO²
VOC
1
2
3
4
B A
GND
U+
G
Display
standard
By default, the display indicat es the f ollowing measurements with the corresponding units
CO2 content in ppm, temperature
Backlighting is provided for impro ved legibility.
The Modbus int erface allows the display to be both in t he 7 segment range and in the do t-matrix range.
Display - individually
programmable
cyclically
in °C,
relative humidity
air quality
and consecutively:
(VOC) in %,
in % r.H.
individually
configured,
Display
alternative output variables
The Modbus int erface can be used to program an
variable
instead of the standard display.
In this case, the first line indicates the value while the second line indicates the corresponding unit The index in the thir d line indicates the display type:
Index 1
= CO2 content in
Index 2
= air quality (VOC) in
Index 3
= temperature in
Index 4
= relative humidity in
Index 5
= atmospheric pressure in
ppm
°C
statically
%
% r.H.
hPa
alternative output
.
Schematic diagram
Plug for display
B
4 3
A
2
GND
1
U+
Zero point calibration
The sensors ar e pre-set and c alibra ted at t he factory. Each measuring channel has a separate offset potentiometer for subsequent adjustment of the measurement. The adjusting range is ± 10 % of the measuring range.
offset
DIP A: Bus address DIP B: Bus parameters
(Baud rate, parity ...) Telegram indicator
Reception (LED green) Error (LED red)
Offset correction
LED (internal status)
CO²
zero
mode address
ON
123456
VOC
DIPB
r.H.
VOCCO²
ON
DIPA
12345678
B
4 3
A
2
GND
1
U+
°C
Reset button
15
AERASGARD® AFTM - LQ - CO2 - Modbus
G
WS-03
Weather and sun
protection hood
(optional)
ACO2-Modbus
ALQ - CO2-Modbus
without filter
(standard)
AERASGARD® ACO2 - Modbus AERASGARD® ALQ - C O2 - Modbus AERASGARD® AFTM - CO2 - Modbus
for humidity, temperature and CO2 content, Deluxe
AERASGARD® AFT M - LQ - CO2 - Modbus
for humidity, temperature, CO2 content and air quality (VOC), Deluxe
Type ⁄ WG02 Measuring Range
-Modbus
AC O
2
ACO2 MODBUS 5000 ppm 1501-7110-6001-200 ACO2 MODBUS D ISPL AY 5000 ppm 1501-7110-6071-200
ALQ - CO2-Modbus
ALQ-CO2 MODBUS 5000 ppm 0...100 % 1501-7111-6001-200 ALQ-CO2 MODBUS DISPLAY 5000 ppm 0...100 % 1501-7111-6071-200
AFTM - C O2-Modbus
AFTM-CO2 MODBUS 0...100 % r.H. –35...+80 °C 5000 ppm 1501-7116-6001-200 AFTM-CO2 MODBUS DI SP LAY 0...100 % r.H. –35...+80 °C 5000 ppm 1501-7116-6071-200
AFTM - LQ - CO2-Modbus
AFTM-LQ-CO2 MODBUS 0...100 % r.H. –35...+80 °C 5000 ppm 0...100 % 1501-7118-6001-200 AFTM-LQ-CO2 MODBUS DISPL AY 0...100 % r.H. –35...+80 °C 5000 ppm 0...100 % 1501-7118-6071-200 Not e: This unit
AFTM - CO2 - Modbus
AFTM - LQ - CO2 - Modbus
with plastic sinter filter
(standard)
AFTM - CO2 - Modbus
AFTM - LQ - CO2 - Modbus
with metal sinter filter
(optional)
On-wall sensor for CO2 content, Deluxe
On-wall sensor for CO2 content and air quality (VOC), Deluxe
Multifunctional on-wall sensor
Multifunctional on-wall sensor
Humidity Temperature CO
must not
be used as safet y-relevant device!
2
VOC
Display
Item No.
Accessories SF-M Metal WS-03 Weather and sun protection hood
sinter filter, Ø 16 mm, L = 3 2 mm, exchangeable stainless steel
V4A
, 200 x 180 x 150 mm, stainless steel 7100-0040-6000-000
16
(1.4 404 ) 7000-0050-2200-100
AERASGARD® KFTM - LQ - CO2 - Modbus
G
MFT - 20 - K
Mounting flange,
plastic
KCO2-Modbus
KLQ - CO2-Modbus
without filter
(standard)
AERASGARD® KCO2 - Modbus AERASGARD® KLQ - C O2 - Modbus AERASGARD® KFTM - CO2 - Modbus
for humidity, temperature and CO2 content, Delu xe
AERASGARD® KF TM - LQ - CO2 - Modbus
for humidity, temperature, air quality (VOC) and CO2 content, Delu xe
Type ⁄ WG02 Measuring Range
-Modbus
KCO
2
KCO2 MODBUS 5000 ppm 1501-8110-6001-200 KCO2 MODBUS D ISPL AY 5000 ppm 1501-8110-6071-200
KLQ - CO2-Modbus
KLQ-CO2 MODBUS 5000 ppm 0...100 % 1501-8111-6001-200 KLQ-CO2 MODBUS DISPLAY 5000 ppm 0...100 % 1501-8111-6071-200
KFTM - C O2-Modbus
KFTM-CO2 MODBUS 0...100 % r.H. –35...+80 °C 5000 ppm 1501-8116-6001-200 KFTM-CO2 MODBUS DISP L AY 0...100 % r.H. –35...+80 °C 5000 ppm 1501-8116-6071-200
KFTM - LQ - CO2-Modbus
KFTM-LQ-CO2 MODBUS 0...100 % r.H. –35...+80 °C 5000 ppm 0...100 % 1501-8118-6001-200 KFTM-LQ-CO2 MODBUS D ISPL AY 0...100 % r.H. –35...+80 °C 5000 ppm 0...10 0 % 1501-8118-6071-200 Not e: This unit
KFTM - CO2 - Modbus
KFTM - L Q - CO2 - Modbus
with plastic sinter filter
(standard)
KFTM - CO2 - Modbus
KFTM - L Q - CO2 - Modbus
with metal sinter filter
(optional)
Duct sensor for CO2 content, Delu xe
Duct sensor for air quality (VOC) and CO2 content, Delu xe
Multifunctional duct sensor
Multifunctional duct sensor
Humidity Temperature CO
must not
be used as safet y-relevant device!
2
VOC
Display
Item No.
Accessories SF-M Metal MFT-20- K Mounting flange,
sinter filter, Ø 16 mm, L = 3 2 mm, exchangeable, stainless steel
V4A
plastic (included in the scope of delivery) 7000-0031-0000-000
17
(1.4 404 ) 7000-0050-2200-100
1 2 3 4 5 6 7 8
ON DIP A
1 2 3 4 5 6
ON DIP B
HYGRASGARD® AFTM- ⁄ KF TM - LQ - CO2 - Modbus
G
| Configuration
BUS ADDRESS
Bus addr ess
(binar y coded, value selectable from 1 to 247)
DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6 DIP 7 DIP 8
128 64 32 16 8 4 2 1 O N O N
Example shows 128 + 64 + 1 = 193 as Modbus address.
The device address in the range of For switch positions 1 to 8 see the table on the back!
Address 0 is reserved for broadcast messages. Addresses greater than 247 must not be assigned and are ignored by the device. The DIP switches are binary-coded with the following values:
DIP 1 =
128
DIP 2 =
64
DIP 3 = 32 ............ DIP 3 = OFF
DIP 4 = 16 ............ DIP 4 = OFF
DIP 5 = 8 ............ DIP 5 = OFF
DIP 6 = 4 ............ DIP 6 = OFF
DIP 7 = 2 ............ DIP 7 = OFF
DIP 8 =
OFF OFF OFF OFF OFF
1 to 247
is set at DIP switch [A].
............ DIP 1 = ON
............ DIP 2 = ON
1
............ DIP 8 = ON The switch positions show n here r esults in the Modbus address
O N
MODBUS
DIP switch [A
Rev. 2017 - V14 GB intro
]
128 + 64 + 1 = 193
BUS PARAMETER
Baud rate
(selectable)
9600 baud 19200 baud 3840 0 baud Reserved
Parity
(selectable)
EVEN (numbered)
ODD (numbered)
The baud rate (speed of transmission) is set at DIP switches 1 and 2 of DIP switch block [B]. Selectable are
Parity
is set at DIP switch 3 of DIP switch block [B].
Selectable are
Parity check
Selectable are The
8N1 mode
The functionality of DIP switch 3 (parity) and DIP switch 4 (parity check) of DIP switch block [B] is therefore deactivated. Selectable are 8N1
Bus termination
Selectable are When bus parameters and bus address are changed at devices with
approx. 30 seconds.
S
DIP
DIP
1
O N O N O N
OFF OFF OFF
DIP 3Parity check
(on / of f)
Active
O N
(1 stop bit)
Inactive (no parity)
OFF
(2 stop bits)
9600 baud, 19200 baud, or
EVEN
or
ODD
– see table!
is activated via DIP switch 4 of DIP swit ch block [B].
active (1 stop bit)
is activated via DIP switch 5 of DIP swit ch block [B].
active
or
inactive (default)
is activated via DIP switch 6 of DIP swit ch block [B].
active
(bus termination resistance of 120 Ohm), or
2
OFF
O N
38400 baud
, or i
nacti ve (2 stop bits)
MODBUS
DIP switch [B
– see table!
– see table !.
DIP 48N1 mode
O N
OFF Inactive (default) OFF Inactive OFF
, i.e. no parit y check – see table!
]
(on / of f)
Active
inactive
(no bus termination) – see table!
display
, the respective settings ar e shown on the display for
DIP 5Bus termination
(on/of f)
O N
Active
DIP
O N
6
COMMUNICATION INDICATOR
Communication is indicated via two LEDs. Error-f ree received telegrams ar e signalized by the green LED lighting up, regardless of the device address. Faulty telegrams or triggered Modbus exception telegrams ar e depicted by the red LED lighting up.
DIAGNOSTICS
An error diagnostic function is integrated
18
HYGRASGARD® AFTM- ⁄ KF TM - LQ - CO2 - Modbus
G
| Configuration
READOUT IN THE DISPLAY
By default, the display indicates the following measurements with the corresponding units
CO2 content in ppm,
air quality
(VOC) in %,
temperature
in °C,
relative humidity
in % r.H.
cyclically
Rev. 2017 - V14 GB intro
and consecutively:
The Modbus interface can be used to program an
CO2 content in ppm,
In this case, the first line indicat es the value while the second line indicates the corresponding unit The index in the third line indicates the display type, e.g. atmospheric pressure (see the table "Function 06 Writ e Single Register").
The Modbus interface allows the display screen to be individually configured, both in the 7 segment range and in the dot-matrix range. This means that messages such as those f rom the PLC can be displayed.
individual display
For the The register s 4x0002 to 4x0019 contain information about the characters and segments to be displayed.
The dot-matrix area is also pr ogrammable in the default setting (regist er 4x0001 contains the value 0). In this case, the current measured value is automatically displayed in the 7-segment area.
The two left-aligned positions are represented by the regist er 4x00 03 (range -9...99). The value 0 switches off the display of both positions. The display is only active if the r egister 4x0002 has positive values.
Composition of Segment Pattern (Register 4x0005)
Bit 0 ......
Bit 1 ......
Bit 2 ......
Bit 3 ......
Bit 4 ......
Bit 5 ......
Bit 6 ......
Bit 7 ......
Bit 8 ......
Bit 9 ......
Bit 10 ....
Bit 11 ....
Bit 12 ....
Bit 13 ....
Bit 14 ....
Bit 15 ....
Dot A Dot B Dot C Dot D Dot DP1
- ­Dot E Dot DP2
- -
- -
- -
- -
- -
- -
- -
- -
air quality
(VOC) in %,
Reading: Unit: Index:
, the register 4x0001 (physical value displayed) must contain t he value 10.
Dot A Dot B Dot C Dot D Dot EDot DP1 Dot DP2
alternative output variable
temperature
1013 hPa 5
in °C,
relative humidity
instead of the standard display:
in % r.H., atmospheric pressure
statically
.
in hPa
Dot Matrix A H B I C J D K E L F M G N
19
HYGRASGARD® AFTM- ⁄ KF TM - LQ - CO2 - Modbus
G
ASCII Code Table for Dot Matrix Display Area
ASCII
Sign
32
Blank
33
!
34
35
#
36
$
37
%
38
&
40
(
41
)
42
*
43
+
44
,
45
-
46
.
47
/
48
0
49
1
50
2
51
3
52
4
ASCII characters or control characters are displayed as spaces.
ASCII
53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
Sign
5 6 7 8 9
: ;
<
=
>
? @ A B C D E
F G H
ASCII
73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 93
| Configuration
Sign
I J
K
L
M
N O P Q R S
T U V
W
X Y Z
[
]
ASCII
94 95 96 97 98
99 100 101 102 103 104 105 106 107 108 109 110 111 112 113
Sign
^ _ \ a b c d e f g h i j k l
m
n o p q
Rev. 2017 - V14 GB intro
ASCII
Sign
114
r
115
s
116
t
117
u
118
v
119
w
120
x
121
y
122
z
123
{
124
|
125
}
129
ü
132
ä
142
Ä
148
ö
153
Ö
154
Ü
223
°
20
HYGRASGARD® AFTM- ⁄ KF TM - LQ - CO2 - Modbus
G
| Telegrams
TELEGRAMS Function 04 Read Input Register
Register Parameter Data Type Value Range
3x0001 CO2 Sampling 4 s Signed 16 bit 3 50...500 0 350...5000 p pm
3x0002 CO2 Filtering 32 s Signed 16 bit 35 0...5000 350...5000 ppm
3x0003 VOC Sampling 4 s Signed 16 bit 0...1000 0.0...100.0 % VO C
3x0004 VOC Filtering 32 s Signed 16 bit 0...1000 0.0...100.0 % VO C
3x0005 Temperature Sampling 4 s Signed 16 bit – 350…800 – 35.0...+80.0 °C
3x0006 Temperature Filtering 32 s Signed 16 bit –350…800 – 35.0...+80.0 °C
3x0007 Relative humidity Sampling 4 s Signed 16 bit 0...1000 0.0...100.0 % r.H.
3x0008 Relative humidity Filtering 32 s Signed 16 bit 0...1000 0.0...10 0.0 % r.H.
3x0009 Atmospheric pressure Sampling 4 s Signed 16 bit 700…1100 70 0...1110 h Pa
3x0010 Atmospheric pressure Filtering 32 s Signed 16 bit 700…1100 7 00...1110 hP a
Function 06 Write Single Register & Function 16 Write Multiple Register
Register Parameter (display) Data Typ e Value Range
4x0001 Physical parameter displayed Index on display Unsigned 8 bit 0…10 0 …10
Standard display (cyclic):
VOC in %, CO2 in ppm, temperature in °C, relative humidity in % r.H.
alternative display (static):
CO2 in ppm 1 1
VOC in % 2 2
Temperature in °C 3 3
Relative humidity in % r.H. 4 4
Atmospheric pressure in hPa 5 5
Freely configurable display 10
4x0002 7-Segment Value Signed 16 bit -999…9999 -999…9999
4x0003 7-Segment Value Signed 8 bit - 9…99 -9…99
4x0004
4x0005 Segment Pattern Unsigned 16 bit See Binary Pattern
4x0006 Dot Matrix Character A Unsigned 8 bit 0…255 ASCII character
4x0007 Dot Matrix Character B Unsigned 8 bit 0…255 ASCII character
4x0008 Dot Matrix Character C Unsigned 8 bit 0…255 ASCII character
4x0009 Dot Matrix Character D Unsigned 8 bit 0…255 ASCII character
4x0010 Dot Matrix Character E Unsigned 8 bit 0…255 ASCII character
4x 0011 Dot Matrix Character F Unsigned 8 bit 0…255 ASCII character
4x00 12 Dot Matrix Character G Unsigned 8 bit 0…255 ASCII character
4x0013 Dot Matrix Character H Unsigned 8 bit 0…255 ASCII character
4x0 014 Dot Matrix Character I Unsigned 8 bit 0…255 ASCII character
4x00 15 Dot Matrix Character J Unsigned 8 bit 0…255 ASCII character
4x0016 Dot Matrix Character K Unsigned 8 bit 0…255 ASCII character
4x0017 Dot Matrix Character L Unsigned 8 bit 0…255 ASCII character
4x0018 Dot Matrix Character M Unsigned 8 bit 0…255 ASCII character
4x0019 Dot Matrix Character N Unsigned 8 bit 0…25 5 ASCII character
0
Default setting
21
HYGRASGARD® AFTM- ⁄ KF TM - LQ - CO2 - Modbus
G
| Telegrams
Function 05 Write Single Coil
Register Parameter Data Type Value Range
0x0001 Reset ( Auto zero) CO2 Bit 0 0 / 1 OFF - ON
0x0002 Reset ( Auto zero) VOC Bit 1 0 / 1 OFF - ON
0x0003 Automatic calibration (Automatic) CO2 Bit 2 0 / 1 OFF - ON
0x0004 Automatic calibration (Automatic) VOC Bit 3 0 / 1 OFF - ON
0x0005 VOC sensibility "low" Bit 4 0 / 1 OF F - ON
0x0006 VOC sensibility "medium" Bit 5 0 / 1 OFF - ON
0x0007 VOC sensibility "high" Bit 6 0 / 1 OF F - ON
Function 08 Diagnostics
The following
Sub Function Code
00 Echo of transmission dat a
01 Restart Modbus
04 Activation listen-only mode No answer
10 Delete counter Echo telegram
11 Counter bus telegrams Unsigned 16 bit All valid bus telegrams
12 Counter communication errors
13 Counter exception telegrams Unsigned 16 bit Error counter
14 Counter slave telegrams Unsigned 16 bit Slave telegrams
15 Counter telegrams without answer Unsigned 16 bit Broadcast messages (address 0)
sub func tion codes
Parameter Data Type Answer
(Loopback)
(Reset listen-only mode)
(Parity, CRC, frame errors, etc.)
are supported
Unsigned 16 bit Faulty bus telegrams
Echo data
Echo telegram
Function 17 Report Slave ID
Composition of answer telegram
Byte No. Parameter Data Ty pe Answer
00 Number of bytes Unsigned 8 bit 6
01 Slave ID (device type) Unsigned 8 bit 14 =
02 Slave ID (device class) Unsigned 8 bit 60 =
03 S ta tus Unsigned 8 bit 255 = RUN, 0 = S TOP
04 Version number (release) Unsigned 8 bit 1…9
05 Version number (version) Unsigned 8 bit 1… 99
06 Version number (index) Unsigned 8 bit 1
22
AERSGARD® MODBUS
AERASGARD® /
AERASREG
®
HYGRASGARD® A FTM- ⁄ KF TM - LQ - CO2 - Modbus
G
General layout of bus struc ture
| Installation
MODBUS
RTU-Master
Rev. 2015 - 1.0 GB intro
Passive
branch
LA LA
Line termination
Stub line
Slave 1 Slave 2
Bus topology with terminating and bias resist ors
Line termination
Active
branch
MODBUS
RTU-Master
Trunk line
Stub line:
shorter 20m
A (D1) D+
B (D0) D–
RS-485
5 V
Slave n
Pull-up / bias resistor
Pull-down / bias resistor
Multiple branch n:
shorter 40m/n
Line termination
Line termination
Common
(GND)
Slave 1 Slave 2
Terminating resistor may only be installed at the ends of the bus line. In networks w ith repeaters not more than two line terminations are allowed. Line termination at the device can be activated via DIP switch 6. The bias r esistors for bus level definition in the resting state are usually activated at the Modbus master / repeater.
The maximum number of subscribers per Modbus segment is 32 devices. When the number of subscribers is greater, the bus must be subdivided into several segments separated by repeaters. The subscriber address can be set from 1 to 247.
For the bus line, a twisted-pair cable data line / power supply line and copper mesh wire shield must be used. Therefore, the line capacitance should be less than 100 pF / m (e.g. Profibus cable).
23
Mounting and Installation
G
Devices are to be connec ted under dead-volt age condition. Devices must only be connec ted t o safety extra- low voltage. Consequential damages caused by a fault in t his device are excluded f rom war rant y or liability. Installation of these devices must only be realized by authorized qualified personnel. The technical data and connect ing conditions shown on the device labels and in the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical pro gress and continuous improvement of our produc ts. In case of any modif ications made by t he user, all warr ant y claims are forfeited. Operating this device close to other dev ices that do not comply with EMC directives may inf luence functionality. This dev ice must not be used for monitoring applications, which solely ser ve the purpose of prot ect ing persons against hazards or injury, or as an EMERGENCY STOP swit ch for systems or machinery, or for any other similar safety-relevant purposes.
Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
Modif ications of these records are not permitted. In case o f a complaint, only complete devices returned in original
packing will be accepted.
Notes regarding mechanical mounting and attachment:
Mounting shall take place while observing all relevant regulations
-
and standards applicable for the place of measurement (e.g. such as welding instructions, etc.). Par ticularly the following
-
shall be regarded: – VDE ⁄ VDI direct ive technical t emperature measur ements,
measurement set - up for temperature measurements.
– The EMC direc tives must be adhered t o.
­– It is imperative to avoid parallel laying of current-carr ying lines.
– We recommend t o use shielded cables with
the shielding being attached at one side to the DDC ⁄ PLC.
Before mounting, make sure that the exis ting thermometer‘s techni
cal par ameters comply wit h the actual conditions at the place of utiliza tion, in par ticular in r espect of:
– Measuring range – Permissible max imum pressure, flow velocity – Installation length, tube dimensions – Oscillations, vibrations, shocks are to be avoided (< 0.5 g)
Attention! In any case, please observe the mechanical and thermal load limits of protective tubes according to DIN 43763 respect ively according to specific S+S standards!
-
Important notes
G
Our “General Terms and Conditions for Business“ t ogether with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
In addition, the f ollowing points are to be observed:
– Devices must only be connect ed to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors a t the device
(e.g. by volt age induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives ar e to be observed.
– This device shall only be used for its intended purpose. Respective safety regulations issued by t he VDE, t he states, their control authorities,
the TÜ V and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has t o prevent perils of any kind.
– No warranties or liabilities will be assumed for defect s and damages arising from impr oper use of this device.
– Consequential damages caused by a fault in this device are excluded from warranty or liability.
– These devices must be installed by authorised specialists only.
The technical data and connecting c onditions of the mounting and operating instructions delivered together with the device are exclusively valid.
Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
– In case of any modifications made by the user, all warranty claims are forf eited.
– This device must not be installed close to heat sources (e.g. radiators) or be exposed to their hea t flow. Dir ect sun irradiation or heat
irradiation by similar sour ces (po werful lamps, halogen spotlights) must absolutely be avoided.
– Operating this device close to other devices that do not comply with EMC directives may influence functionality.
– This device must not be used for monitoring applications, which serve the purpose of prot ecting persons against hazards or injury,
or as an EMERGENC Y STOP switch for systems or machinery, or f or any other similar safety- relevant purposes.
– Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
– Modifications of these records are not permitted.
– In case of a complaint, only complete devices returned in original packing will be accepted.
These instructions must be read befor e installation and putting in operation and all no tes provided therein ar e to be regarded!
24