SSAC THDM Series Data Sheet

Page 1
THDM SeriesTimer - Delay-on-Make
Connection:
Load may be connected to terminal 3 or 1. RT is used when external adjustment is ordered.
L1 N/L2
The THDM Series is a high power solid-state delay-on-make timer that is connected in series with the load. The THDM eliminates the need for a timer and a separate solid-state relay. A cost effective approach for controlling larger loads, such as motors, electric heating elements, and
lamps. When mounted on a metal surface, it can
switch loads up to 20A steady, 200A inrush.
Operation (Delay-on-Make):
Upon application of input voltage, the time delay begins.
The output is de-energized before and during the time delay. At the end of the time delay, the output is energized and remains energized until input voltage is removed.
Reset: Removing input voltage resets the time delay and output.
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams.
Appendix B, page 165, Figure 4 for dimensional drawing.
Features:
• High load currents up to 20A, 200A inrush
• Simple-to-use two terminal series connection
• ± 0.5% repeat accuracy
Fixed or adjustable delays from 1s - 1000m
• ± 10% factory calibration
• 24, 120, or 230VAC
Metallized mounting surface for heat transfer
• Solid state & encapsulated
Approvals:
Auxiliary Products:
• External adjust potentiometer:
P / N: P1 0 0 4- 13 P/N: P1004-13-X
• Female quick connect:
P / N : P 1 0 1 5- 13 ( A W G 1 0 / 1 2 ) P/ N: P1015-64 (AWG 14 /1 6)
• Quick connect to screw adaptor:
P/N: P1015-18
• Versa-knob: P/N: P0700-7
• Plug-on adjustment module:
P/N: VTP(X)(X)
Time Delay VTP P/N
1 - 1-100s 2 - 10-1000s 3 - 0.1-10m 4 - 1-100m 5 - 10-1000m
Selection Table for VTP Plug-on Adjustment Accessory.
VTP5G
VTP5K VTP5N VTP5P VTP5R
Order Table:
THDM
X Input Voltage
─2 - 24VAC ─4 - 120VAC ─6 - 230VAC
X
Adjustment
─1 - Fixed ─2 - External adjust
X
Time Delay*
─1 - 1 - 100s ─2 - 10 - 1000s ─3 - 0.1 - 10m ─4 - 1 - 100m ─5 - 10 - 1000m
Specications
Time Delay
Type .................................Digital intergrated circuitry
Range ................................ 1s - 1000m in 5 adjustable ranges or xed
Tolerance (Factory Calibration) ..........≤ ± 10%
Recycle Time ..........................After timing - ≤ 350ms;
During timing - ≤150ms
Time Delay vs Temp. & Voltage .......... ≤ ±2%
Input
Voltage ............................... 24, 120, or 230VAC
Tolerance .............................±20%
AC Line Frequency .................... 50/60 Hz
Output
Type .................................Solid state
Form ................................. NO, open during timing
Maximum Load Currents Output Steady State Inrush**
A 6A 60A B 10A 100A C 20A 200A
Available Models:
There are no part numbers currently active. Please call Technical Support with your requirements.
X
Output Rating
─A - 6A ─B - 10A ─C - 20A
*If xed delay is selected, insert delay (0.1 - 1000) followed by (S) sec. or (1 - 100) (M) min.
Minimum Load Current ................ 100mA
Effective Voltage Drop (V Line - V Load) Input Effective Drop
24VAC ≤ 3V 120VAC ≤ 3V 230VAC ≤ 5V
Protection
Circuitry .............................Encapsulated
Dielectric Breakdown .................. ≥ 2000V RMS terminals to mounting surface
Insulation Resistance ................... ≥ 100 MΩ
Mechanical
Mounting ** ..........................Surface mount with one #10 (M5 x 0.8) screw
Dimensions ........................... 2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4 mm)
Termination ...........................0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating/Storage Temperature ......... -40° to 60°C / -40° to 85°C
Humidity ............................. 95% relative, non-condensing
Weight ............................... 3.9 oz (111 g)
**Must be bolted to a metal surface using the included heat sink compound. The maximum
mounting surface temperature is 90°C. Inrush: Non-repetitive for 16ms.