SSAC THD1 Series Data Sheet

THD1 SeriesTimer - Delay-on-Make
Connection:
S1 = Optional Low Current Initiate Switch RT is used when external adjustment is ordered.
L1 N/L2
The THD1 Series combines accurate timing circuitry with high power solid-state switching. It can switch motors, lamps, and heaters directly without a contactor. You can reduce labor, component cost, and increase reliability with these small, easy-to-use, Digi-Power timers.
Operation (Delay-on-Make):
Upon application of input voltage, the time delay begins.
The output is de-energized before and during the time delay. At the end of the time delay, the output energizes and remains energized until input voltage is removed.
Reset: Removing input voltage resets the time delay and output.
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams.
Appendix B, page 165, Figure 4 for dimensional drawing.
External Resistance vs. Time Delay:
Features:
• High load currents up to 20A, 200A inrush
Fixed or adjustable delays from
0.1s - 1000m
• ±0.5% repeat accuracy
• 24, 120, or 230VAC
Metallized mounting surface for heat transfer
• Totally solid state & encapsulated
Approvals:
Auxiliary Products:
• External adjust potentiometer:
P/N: P 1004-95 P/N: P1004-95-X
• Female quick connect:
P / N : P 1 01 5 - 1 3 ( AW G 1 0 / 1 2 ) P /N : P 1 0 1 5 - 6 4 ( AW G 1 4/ 16 )
• Quick connect to screw adaptor:
P/N: P1015-18
• Versa-knob: P/N: P0700-7
Available Models:
THD1B410.5S THD1C231 THD1C232 THD1C233 THD1C234 THD1C235 THD1C415M
If desired part number is not listed, please call us to see if it is technically possible to build.
THD1C431 THD1C432 THD1C433 THD1C434 THD1C435 THD1C6110S
Order Table:
THD1
X Output Rating
─A - 6A ─B - 10A ─C - 20A
X
Input Voltage
─2 - 24VAC ─4 - 120VAC ─6 - 230VAC
X
Adjustment
Specications
Time Delay
Range ............................0.1s - 1000m in 6 adjustable ranges or xed
Repeat Accuracy ..................±0.5% or 20ms, whichever is greater
Tolerance (Factory Calibration) ......≤ ±1%
Recycle Time ......................≤ 150ms
Time Delay vs Temp. & Voltage ......≤ ±2%
Input
Voltage ...........................24, 120, or 230VAC
Tolerance .........................±20%
Line Frequency ....................50/60 Hz
Power Consumption ...............≤ 2VA
Output
Type .............................Solid state
Form .............................NO, open during timing
Maximum Load Current Output Steady State Inrush**
A 6A 60A B 10A 100A C 20A 200A
32
─1 - Fixed ─2 - External adjust ─3 - Onboard adjust
X
Time Delay*
─0 - 0.1 - 10s ─1 - 1 - 100s ─2 - 10 - 1000s ─3 - 0.1 - 10m ─4 - 1 - 100m ─5 - 10 - 1000m
Minimum Load Current ............100mA
Voltage Drop ...................... 2.5V @ rated current
OFF State Leakage Current ......... 5mA @ 230VAC
Protection
Circuitry .........................Encapsulated
Dielectric Breakdown ..............≥ 2000V RMS terminals to mounting surface
Insulation Resistance ...............≥ 100 MΩ
Mechanical
Mounting ** ......................Surface mount with one #10 (M5 x 0.8) screw
Dimensions .......................2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4 mm)
Termination .......................0.25 in. (6.35 mm) male quick connect
terminals
Environmental
Operating / Storage Temperature ....-40° to 60°C / -40° to 85°C
Humidity .........................95% relative, non-condensing
Weight ...........................3.9 oz (111 g)
**Must be bolted to a metal surface using the included heat sink compound. The
maximum mounting surface temperature is 90°C. Inrush: Non-repetitive for 16ms.
*If xed delay is selected, insert
delay (0.1 - 1000) followed by (S) sec. or (M) min.
www.ssac.com • 800-843-8848 • fax: 605-348-5685
Loading...