THD1 SeriesTimer - Delay-on-Make
Connection:
S1 = Optional Low Current Initiate
Switch
RT is used when external adjustment
is ordered.
L1 N/L2
The THD1 Series combines accurate timing
circuitry with high power solid-state switching.
It can switch motors, lamps, and heaters directly
without a contactor. You can reduce labor,
component cost, and increase reliability with these
small, easy-to-use, Digi-Power timers.
Operation (Delay-on-Make):
Upon application of input voltage, the time delay begins.
The output is de-energized before and during the time
delay. At the end of the time delay, the output energizes
and remains energized until input voltage is removed.
Reset: Removing input voltage resets the time delay
and output.
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams.
Appendix B, page 165, Figure 4 for dimensional drawing.
External Resistance vs. Time Delay:
Features:
• High load currents up to 20A,
200A inrush
• Fixed or adjustable delays from
0.1s - 1000m
• ±0.5% repeat accuracy
• ±1% factory calibration
• 24, 120, or 230VAC
• Metallized mounting surface for
heat transfer
• Totally solid state & encapsulated
Approvals:
Auxiliary Products:
• External adjust potentiometer:
P/N: P 1004-95
P/N: P1004-95-X
• Female quick connect:
P / N : P 1 01 5 - 1 3 ( AW G 1 0 / 1 2 )
P /N : P 1 0 1 5 - 6 4 ( AW G 1 4/ 16 )
• Quick connect to screw adaptor:
P/N: P1015-18
• Versa-knob: P/N: P0700-7
Available Models:
THD1B410.5S
THD1C231
THD1C232
THD1C233
THD1C234
THD1C235
THD1C415M
If desired part number is not listed, please call
us to see if it is technically possible to build.
THD1C431
THD1C432
THD1C433
THD1C434
THD1C435
THD1C6110S
Order Table:
THD1
X
Output Rating
─A - 6A
─B - 10A
─C - 20A
X
Input Voltage
─2 - 24VAC
─4 - 120VAC
─6 - 230VAC
X
Adjustment
Specications
Time Delay
Range ............................0.1s - 1000m in 6 adjustable ranges or xed
Repeat Accuracy ..................±0.5% or 20ms, whichever is greater
Tolerance (Factory Calibration) ......≤ ±1%
Recycle Time ......................≤ 150ms
Time Delay vs Temp. & Voltage ......≤ ±2%
Input
Voltage ...........................24, 120, or 230VAC
Tolerance .........................±20%
Line Frequency ....................50/60 Hz
Power Consumption ...............≤ 2VA
Output
Type .............................Solid state
Form .............................NO, open during timing
Maximum Load Current Output Steady State Inrush**
A 6A 60A
B 10A 100A
C 20A 200A
32
─1 - Fixed
─2 - External adjust
─3 - Onboard adjust
X
Time Delay*
─0 - 0.1 - 10s
─1 - 1 - 100s
─2 - 10 - 1000s
─3 - 0.1 - 10m
─4 - 1 - 100m
─5 - 10 - 1000m
Minimum Load Current ............100mA
Voltage Drop ......................≅ 2.5V @ rated current
OFF State Leakage Current .........≅ 5mA @ 230VAC
Protection
Circuitry .........................Encapsulated
Dielectric Breakdown ..............≥ 2000V RMS terminals to mounting surface
Insulation Resistance ...............≥ 100 MΩ
Mechanical
Mounting ** ......................Surface mount with one #10 (M5 x 0.8) screw
Dimensions .......................2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4 mm)
Termination .......................0.25 in. (6.35 mm) male quick connect
terminals
Environmental
Operating / Storage Temperature ....-40° to 60°C / -40° to 85°C
Humidity .........................95% relative, non-condensing
Weight ...........................≅ 3.9 oz (111 g)
**Must be bolted to a metal surface using the included heat sink compound. The
maximum mounting surface temperature is 90°C. Inrush: Non-repetitive for 16ms.
*If xed delay is selected, insert
delay (0.1 - 1000) followed by (S) sec.
or (M) min.
www.ssac.com • 800-843-8848 • fax: 605-348-5685