Description
The PTHF Series can be used for a variety of applications from chemical metering, to temperature regulating, to
energy management. The infinite adjustability from 1 to 99% provides accurate percentage ON control over a wide
factory fixed cycle period. When mounted on a metal surface, it can be used to drive solenoids, contactors, relays,
or lamps, up to 20 Amps steady, 200 Amps inrush. PTHF is the suggested replacement for the PT Series.
ON/OFF Recycling
Percentage Control
Controls Loads up to 20 A,
200 A Inrush
Fixed Cycle Period 10 s...
1000 m
+/-0.5% Repeat Accuracy
+/-5% Factory Calibration
Totally Solid State &
Encapsulated
Onboard or External
Adjustment 1 to 99% ON
Approvals:
Operation
Upon application of input voltage, the output energizes
and the T1 ON time begins. At the end of the ON time,
the output de-energizes and the T2 OFF time begins.
At the end of the OFF time, the output energizes and
the cycle repeats as long as input voltage is applied.
Increasing the ON time decreases the OFF time. The
total cycle period is equal to the ON time plus the OFF
time. The total cycle period is factory fixed. ON time
range is 1 to 99 percent of cycle period.
Reset: Removing input voltage resets the output
and time delays, and returns the sequence to the T1
ON time.
Connection
Function
Percentage
V = Voltage L = Load CP = Cycle Period
R = Reset T1 = ON Time T2 = OFF Time
Accessories
External adjust
potentiometer
P/N:
P1004-95
Female quick
connect
P/Ns:
P1015-64
(AWG 14/16)
P1015-13 (AWG 10/12)
Quick connect to
screw adaptor
P/N: P1015-18
Versa-knob
P/N: P0700-7
Ordering Table
Example P/N:
See accessory pages for
specifications.
5.152 Low Voltage Products & Systems
1TRC 001 009 C0202 ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com
Dashed lines are internal connections.
RT = 100 KΩ S1 = Optional Low Current Initiate Switch
RT is used when external adjustment is ordered
T1 = ON Time T2 = OFF Time
PTHF
Series
Input Fixed Cycle Period Output Rating
XX
–2 - 24 V AC
–4 - 120 V AC
–6 - 230 V AC
–Specify 10 ... 1000
as the total fixed cycle
period in seconds.
X
–A - 6
–B - 10
–C - 20
–D - 1
Note: Part number for fixed
cycle period in minutes
insert (M) suffix.
PTHF210A = 24 V AC; Cycle Period 10 Seconds; 6 Amps; External Adjustment
PTHF410MA = 120 V AC; Cycle Period 10 Minutes; 6 Amps; External Adjustment
PTHF615MDK = 230 V AC; Cycle Period 15 Minutes; 1 Amp; Onboard Adjustment
X
Adjustment
–K- Onboard
Adjustment
–Blank - External
Adjustment
PTHFGen 11.15.06
![](/html/50/508b/508bc7cae459408606f09e0075204760d85a8a58d6c28248bdc8e6b87ca78e10/bg2.png)
Percentage Timing
PTHF Series
Power Timing Module
Technical Data
Time Delay
Type External or Onboard Knob
Range / External Adjustment Resistance Adjustable from 1 ... 99%; / RT = 100 KΩ
Cycle Period Fixed from 10 s ... 1000 m
Repeat Accuracy +/-0.5% or 20 ms, whichever is greater
Cycle Period Tolerance (Factory Calibration) ≤ +/- 5%
Reset Time ≤ 150 ms
Time Delay vs. Temperature & Voltage ≤ +/-10%
Input
Voltage 24, 120, or 230 V AC
Tolerance +/-20%
Line Frequency 50 ... 60 Hz
Power Consumption ≤ 2 VA
Output
Type Solid state
Maximum Load Currents Output Steady State Inrush* Minimum
A 6 A 60 A 100 mA
B 10 A 100 A 100 mA
C 20 A 200 A 100 mA
D 1 A 10 A - Voltage Drop ≅ 2.5 V at rated current
OFF State Leakage Current ≅ 5 mA at 230 V AC
Protection
Circuitry Encapsulated
Dielectric Breakdown ≥ 2000 V RMS terminals to mounting surface
Insulation Resistance ≥ 100 MΩ
Mechanical
Mounting * Surface mount with one #10 (M5 x 0.8) screw
Termination 0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating Temperature -40°C ... +60°C
Storage Temperature -40°C ... +85°C
Humidity 95% relative, non-condensing
Weight 1 A unit: ≅ 2.4 oz (68 g); 6, 10, 20 A units: ≅ 3.9 oz (111 g)
Dedicated
timers
*Units rated ≥ 6 A must be
bolted to a metal surface
using the included heat sink
compound. The maximum
mounting surface temperature
is 90°C. Inrush: Non-repetitive
for 16 ms.
Mechanical View
PTHFGen 11.16.06
Inches (Millimeters)
Low Voltage Products & Systems 5.153
ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com 1TRC 001 009 C0202