![](/html/1f/1fb5/1fb50ecfa532cd5f90e23781de4a02c38364a324f0cfbcedcf9199204f639d85/bg1.png)
Low Level Cutoff
LLC6 Series
Liquid Level Control
Technical Data
Control
Type ON/OFF (Single Level) Resistance sensor with built-in time delay to prevent rapid cycling
Sense Voltage 12 V AC nominal at probe terminals
Sense Resistance 5K ... 250K Ω factory xed
Sense Resistance Tolerance Fixed +/-10%
Time Delay
Range 1 ... 60 s in 1 s increments
Tolerance +/-20%
Repeat Accuracy +/-10%
Time Delay vs. Temperature & Voltage +/-10%
Power Outage Reset Delay ≤ 1 s
Input
Voltage 24, 120, or 230 V AC
Tolerance 24 V AC +20% ... -15%
120 or 230 V AC +10% ... -20%
Frequency 50 ... 60 Hz
Output
Type Electromechanical relay
Form Non-isolated (SPDT) contacts
Rating 10 A resistive at 240 V AC; 1/4 hp at 125 V AC; 1/2 hp at 250 V AC
Protection
Surge IEEE C62.41-1991 Level A
Isolation Voltage ≥ 2500 V RMS between input & output terminals
Mechanical
Mounting Plug-in socket
Termination 11 Pin relay type
Package 2.91 x 2.39 x 1.78 in. (73.9 x 60.7 x 45.2 mm)
Environmental
Operating Temperature -40°C ... +60°C
Storage Temperature -40°C ... +80°C
Humidity 95% relative, non-condensing
Weight ≅ 7.3 oz (207 g)
Liquid level
controls
Mechanical View
Inches (Millimeters)
LLC62B01 09.10
9.11
SSAC, LLC. • 800-377-7722 • customerservice@ssac.com • technicalsupport@ssac.com • www.ssac.com
• denotes a preferred product