SSAC LLC2 SERIES Data Sheet

Protection Relays
L1 N/L2
nk or use
Pump Controls and Liquid Level Controls
LLC2 SERIES
Open Board Liquid Level Controls
Wiring Diagram
V = Voltage L = Low Probe H = High Probe C = Probe Common P = Probe ∆S = Sensitivity Adjustment NC = Normally
Metal Ta additional Probe
Connect common to conductive tank. Additional probe is necessary for non-conductive or insulated tanks.
For dimensional drawing see: Appendix, page 514, Figure 41.
Closed NO = Normally Open
Description
The LLC2 Series is a dual-probe conductive liquid level control designed for OEM equipment and commercial appliance applications. Models are available for fill or drain operation. Transformer isolated 12VAC is provided at the probes to prevent electrolysis. A trickle current of less than 1mA determines the presence or absence of liquid between the probes and common. On adjustable units, the sensitivity adjustment allows accurate level sensing while ignoring foaming agents and floating debris. The LLC2 Series printed circuit board is conformal coated to resist moisture and corrosion.
Operation
Drain (Pump-Down Mode): When the liquid level rises and touches the high probe, the output relay energizes and remains energized until the liquid level falls below the low probe. The output relay then de-energizes and remains de-energized until the liquid again touches the high probe.
Fill (Pump-Up Mode): When the liquid level falls below the low probe, the output relay energizes and remains energized until the liquid level rises and touches the high probe. The output relay then de-energizes and remains de-energized until the liquid level again falls below the low probe.
Features & Benefits
FEATURES BENEFITS
Isolated 12VAC probes Prevents scale buildup on the probes
Open PCB design
Conformally coated PCB Protects against moisture and corrosion
Sensitivity adjustment
Cost effective design for OEM equipment and commercial appliances
Provides accurate level sensing while ignoring foam or floating debris
Accessories
8
PUMP CONTROLS & LIQUID LEVEL CONTROLS
Ordering Information
MODEL
LLC24A2AN
LLC24A2F50N
LLC24B1AC
LLC24B1F26C
LLC24B2F50N
LLC26A1F25C
©2017 Littelfuse Protection Relays & Controls
INPUT VOLTAGE
120VAC
120VAC
120VAC
120VAC
120VAC
230VAC
OPERATION TERMINATION
Drain Terminal block
Drain Terminal block Fixed 50kΩ
Fill
Fill
Fill Terminal block Fixed 50kΩ
Drain
0.25” Quick connect
0.25” Quick connect
0.25” Quick connect
SENSE RESISTANCE
Adjustable to 100kΩ
Adjustable to 100kΩ
Fixed 26kΩ
Fixed 25kΩ
143
P1015 -13 (AWG 10/12), P1015-64 (AWG 14/16), P1015 -14 (AWG 18/22) Female Quick Connect
These 0.25 in. (6.35 mm) female terminals are constructed with an insulator barrel to provide strain relief.
P1015-18 Quick Connect to Screw Adapter
Screw adapter terminal designed for use with all modules with 0.25 in. (6.35 mm) male quick connect terminals.
PHST-38QTN Electrode
Designed for a maximum steam pressure of 240 PSI; 400° F. UL353 Recognized.
LLP-24 Threaded Probe (24”)
Threaded stainless steel probe measuring 24” (61 cm) long. For use with PHST-38QTN liquid level control electrodes.