![](/html/95/950a/950ae2e9b47b45935510e283e3de9ca777656bf97aba8715e42dfcfce4fba324/bg1.png)
KVM SeriesVoltage Monitors
TP = Undervoltage Setpoint
R = Reset Point
The KVM Series is a single-phase undervoltage
monitor designed to protect sensitive equipment
against brownout undervoltage conditions. The
compact design and encapsulated construction
make the KVM an excellent choice for OEM
equipment.
For more information see:
Appendix B, page 165, Figure 1 for dimensional drawing.
Appendix C, page 169, Figure 16 for connection diagram.
Operation
The output relay is energized and the LED glows
green when the input voltage is above the reset
voltage threshold. If the input voltage drops below the
undervoltage setpoint, the output relay and LED will
de-energize. The output relay will remain de-energized
as long as the input voltage is below the reset voltage.
Reset is automatic when the input voltage returns to a
normal range.
Features:
• Economical single-phase brownout/
undervoltage protection
• Isolated, 8A, SPDT output contacts
• Protects sensitive 110 to 120VAC or 220
to 240VAC loads
• Adjustable low voltage trip point
• LED Indicator
Approvals:
Auxilary Products:
• Quick connect to screw adaptor:
P/N: P1015-18
• Female quick connect:
P/N: P1015-64 (AWG 14/16)
• DIN rail: P/N: C103PM (Al)
• DIN rail adaptor: P/N: P1023-20
Available Models:
KVM4
KVM6
Order Table:
Undervoltage Setpoint
78 to 99VAC
156 to 199VAC
Maximum Line Voltage
132VAC
264VAC
Specications
Line Voltage
Type ..................................Single phase
Input Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . 110 to 120VAC or 220 to 240VAC
AC Line Frequency .....................50/60 Hz
Power Consumption ....................2.5W @ 132VAC; 4.5W @ 264VAC
Power Off Reset Time ...................< 150ms
Undervoltage Detection
Undervoltage Setpoint KVM4 ......78 to 99VAC
KVM6 ......156 to 199VAC
Undervoltage Reset Point KVM4 ......Fixed at 104VAC
KVM6 ......Fixed at 209VAC
Repeatability ...........................± 0.5% under xed conditions
±1% over temperature range
Voltage Sensing Accuracy ................±2% at 25°C
Output
Type ..................................Electromechanical relay
Form ..................................SPDT
Rating .................................8A resistive @ 120VAC,
1/3 hp @ 120/240VAC
Part Number
KVM4
KVM6
Life ...................................Mechanical - 1 x 106; Electrical - 1x105
LED Indicator ..........................Glows green when output is energized
Protection
Surge .................................IEEE C62.41-1991 Level A
Circuitry ...............................Encapsulated
Isolation Voltage ........................> 1500V RMS input to output
Insulation Resistance ....................> 100 MΩ minimum
Mechanical
Mounting ..............................Surface mount with one #10
(M5 x 0.8) screw
Dimensions ............................2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
Termination ............................0.25 in. (6.35 mm) male quick
connect terminals
Environmental
Operating / Storage Temperature .........-25 to 55°C / -40 to 85°C
Humidity ..............................95% relative, non-condensing
Weight ................................2.6 oz (74 g)