SSAC KSDU Series, TDU Series Data Sheet

KSDU/ TDU SeriesTimer - Delay-on-Make
Connection:
L1 N/L2
The TDU and KSDU Series are encapsulated solid­state, delay-on-make timers that combine digital timing circuitry with universal voltage operation. The TDU offers DIP switch adjustment allowing accurate selection of the time delay over the full
time delay range. The KSDU is factory xed from
0.1s to 10,230s and does not include the DIP switch.
These series are excellent choices for process
control systems and OEM equipment.
Operation (Delay-on-Make):
Upon application of input voltage, the time delay begins.
The output is de-energized before and during the time delay. At the end of the time delay, the output energizes and remains energized until input voltage is removed.
Reset: Removing input voltage resets the time delay and output.
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams.
Appendix B, page 165, Figure 1 for dimensional drawing.
Digi-Set Binary Switch Operation:
Features:
• 2 universal voltage ranges from
24 to 240VAC/DC
• Digital integrated circuitry
• Switch selectable delays from 0.1s - 2.8h
in 3 ranges or factory xed
• ±0.5% repeat accuracy
• 1A steady, 10A inrush
• Totally solid state & encapsulated Approvals:
Auxiliary Products:
• Female quick connect:
P / N : P 1 01 5 - 6 4 ( A W G 14 / 1 6 )
• Quick connect to screw adaptor:
P/N: P1015-18
• Mounting bracket: P/N: P1023-6
• DIN rail: P/N: C103PM (Al)
• DIN rail adaptor: P/N: P1023-20
Available Models:
KSDU8110 KSDU811200 TDU3000A TDU3001A TDU3003A
If desired part number is not listed, please call us to see if it is technically possible to build.
TDUH3000A TDUH3001A TDUL3000A TDUL3001A
Load may be connected to terminal 3 or 1.
TDU has DIP switch adjustment; KSDU is xed.
Order Tables:
KSDU
TDU
X Input Voltage Range
─8 - 24 to 120VAC/DC ─9 - 100 to 240VAC/DC
Input Voltage Range
24 to 120VAC/DC
100 to 240VAC/DC
24 to 120VAC/DC
100 to 240VAC/DC
120 to 277VAC
24 to 120VAC/DC
100 to 240VAC/DC
X
Type
─1 - Fixed
X
Time Delay (Seconds)
Specify xed delay in
seconds 0.1 - 10230
Time Range - Seconds
0.1 - 102.3
0.1 - 102.3 1 - 1023 1 - 1023 1 - 1023
10 - 10230 10 - 10230
Part Number
TDUL3000A TDUL3001A
TDU3000A TDU3001A
TDU3003A TDUH3000A TDUH3001A
Specications
Time Delay
Type ...................................Digital integrated circuitry
Range* Adjustable (TDU) .....0.1 - 102.3s in 0.1s increments
Fixed (KSDU) .....Fixed from 0.1s - 10230s
Repeat Accuracy .........................±0.5% or 20ms, whichever is greater
Tolerance (Factory Calibration) ............±10%
Recycle Time ............................≤ 150ms
Time Delay vs Temp. & Voltage ............±5%
Input
Voltage .................................24 to 120VAC/DC; 100 to 240VAC/DC
AC Line Frequency ......................50/60 Hz
Tolerance ...............................±20%
Output
Type ...................................Solid state
Form ...................................NO, open during timing
Maximum Load Current ..................1A steady state, 10A inrush at 60°C
Minimum Holding Current ...............40mA
Voltage Drop ............................ 2.5V @ 1A
Protection
Circuitry ................................Encapsulated
Dielectric Breakdown ....................≥ 2000V RMS terminals to mounting surface
Insulation Resistance .....................≥100 MΩ
Mechanical
Mounting ...............................Surface mount with one #10 (M5 x 0.8) screw
Dimensions .............................2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
Termination .............................0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating / Storage Temperature ..........-40° to 60°C / -40° to 85°C
Humidity ...............................95% relative, non-condensing
Weight ................................. 2.4 oz (68 g)
* For CE approved applications, power must be removed from the unit when a switch