Delay On Make (Operate)
TDU, KSDU Digi-Set
Timing Modules
Description
The TDU and KSDU Series are encapsulated solid state delay on make timers that combine digital timing
circuitry with universal voltage operation. The TDU offers DIP switch adjustment allowing accurate selection of
the time delay over the full time delay range. The KSDU is factory fixed from 0.1 s to 10,230 s and does not
include the DIP switch. These series are excellent choices for process control systems and OEM equipment.
2 Universal Voltage Ranges
From 24 ... 240 V AC/DC
Digital Integrated Circuitry
Switch Selectable Delays
From 0.1 s ... 2.8 h in 3
Ranges or Factory Fixed
+/-0.5% Repeat Accuracy
1 A Steady - 10 A Inrush
Totally Solid State and
Encapsulated
Approvals:
Accessories
Female quick
connect
P/N:
P1015-64
(AWG 14/16)
Operation
Upon application of input voltage, the time delay
begins. The output is de-energized before and during
the time delay. At the end of the time delay, the output
energizes and remains energized until input voltage is
removed.
Reset: Removing input voltage resets the time delay
and output.
Connection
Function
Delay On Make
V = Voltage R = Reset TD = Time Delay
L = Load
= Undefined time
Quick connect to
screw adaptor
P/N: P1015-18
Mounting bracket
P/N: P1023-6
DIN rail P/Ns:
017322005 (Steel)
C103PM (Al)
→
DIN rail adaptor
P/N: P1023-20
See accessory pages for
specifications.
←
Dashed lines are internal connections.
Load may be connected to terminal 3 or 1.
TDU has DIP switch adjustment; KSDU is fixed.
Ordering Table
TDU
Series
KSDU
Series
Example P/N:
Input Voltage Range
24 ... 120 AC/DC
100 ... 240 AC/DC
24 ... 120 AC/DC
100 ... 240 AC/DC
24 ... 120 AC/DC
100 ... 240 AC/DC
X
Input Voltage Range
–8 - 24 ... 120 V AC/DC
–9 - 100 ... 240 V AC/DC
KSDU81300, KSDU910.1
Time Range - Seconds
0.1 ... 102.3
0.1 ... 102.3
1 ... 1023
1 ... 1023
10 ... 10230
10 ... 10230
X
Type
–1 - Fixed
X
Time Delay (Seconds)
–Specify fixed delay in
seconds 0.1 ... 10230
Part Number
TDUL3000A
TDUL3001A
TDU3000A
TDU3001A
TDUH3000A
TDUH3001A
TDKSDUB1 06.09.04
Low Voltage Products & Systems5.16

Technical Data
Delay On Make (Operate)
TDU, KSDU Digi-Set
Timing Modules
Time Delay
Type Digital integrated circuitry
Range* Adjustable (TDU) 0.1 ... 102.3 s in 0.1 s increments
1 ... 1023 s in 1 s increments
10 ... 10230 s in 10 s increments
Fixed (KSDU) Fixed from 0.1 s ...10,230 s
Repeat Accuracy +/-0.5% or 20 ms, whichever is greater
Tolerance (Factory Calibration) +/-10%
Recycle Time ≤ 150 ms
Time Delay vs. Temperature & Voltage +/-5%
Input
Voltage 24 ... 120 V AC/DC
100 ... 240 V AC/DC
Line Frequency 50 ... 60 Hz
Tolerance +/-20%
Output
Type Solid state
Form Normally Open, open during timing
Maximum Load Current 1 A steady state, 10 A inrush at 60°C
Minimum Holding Current 40 mA
Voltage Drop ≅ 2.5 V at 1 A
Protection
Circuitry Encapsulated
Dielectric Breakdown ≥ 2000 V RMS terminals to mounting surface
Insulation Resistance ≥100 MΩ
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw
Package 2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
Termination 0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating Temperature -40°C ... +60°C
Storage Temperature -40°C ... +85°C
Humidity 95% relative, non-condensing
Weight ≅ 2.4 oz (68 g)
* For CE approved applications, power must
be removed from the unit when a switch
position is changed.
Mechanical View
TDU Adjustment
Digi-Set Binary Switch Operation
Inches (Millimeters)
TDKSDUB1 06.09.04
Low Voltage Products & Systems 5.17
Adjustment Switches Shown Not Included
on KSDU Series.