SSAC HRPU Series, HRIU Series Data Sheet

HRPU / HRIU SeriesTimer
L1 N/L2
Connection:
HRIU
Isolated Output
The HRPU/HRIU Series combines an electromechanical relay output with microcontroller timing circuitry. Its switching capacity allows direct control of loads like compressors, pumps, motors, heaters, and lighting. It is a factory programmed module available in any 1 of 14 standard functions. The HRPU/HRIU offers a single adjustable timer or counter function. Switch adjustment allows accurate selection of the time delay or number of counts. The HRPU has non-isolated relay contacts, the HRIU has isolated relay contacts. Encapsulation protects against shock, vibration, and humidity. The HRPU/HRIU Series is a cost effective approach for OEM applications that require small size, reliability and accurate switch adjustment.
See Appendix B, page 165, Figure 2 for dimensional
drawing.
Switch Adjustment:
Features:
• Choose 1 of 14 standard functions
• Special time ranges & functions available
Factory programmed
• Microcontroller circuitry, ±0.1% repeat
accuracy
• 30A, SPDT, NO output contacts
• Accurate switch adjustment
• 12 to 240V operations in 2 ranges
• Delays from 0.1s - 1023h Approvals:
Auxiliary Products:
• Female quick connect:
P/N: P1015-13 (AWG 10/12) P/N: P1015-64 (AWG 14/16)
• Mounting bracket: P/N: P1023-6
• Quick connect to screw adaptor:
P/N: P1015-18
• DIN rail: P/N: C103PM (Al)
• DIN rail adaptor: P/N: P1023-20
Available Models:
HRIUW2I HRIUW2M
If desired part number is not listed, please call us to see if it is technically possible to build.
L1 N/L2
HRPU
Non-isolated Output
S1 = Initiate Switch UTL = Optional Untimed Load L = Load V = Voltage
Order Table:
HRPU/ HRIU
X Input
W - 24 to 240VAC
24 to 110VDC
D - 12 to 48VDC
X
Time Delay/Counts
1 - 0.1 - 102.3s ─2 - 1 - 1023s ─3 - 0.1 - 102.3m ─4 - 1 - 1023m ─5 - 0.1 - 102.3h ─6 - 1 - 1023h ─7 - 1 - 165 counts (straight) w/ pulsed output ─8 - 1 - 1023 counts (binary) w/ pulsed output ─9 - 1 - 7 counts to start 1 - 63s or m interval time
Specications
Count Functions/Switch Type ..........Mechanical switch (counts on switch closure)
Count Range ..........................1 - 1023 counts
Counter Output (Variable 7 & 8) .........Pulse widths 300ms ±20%
Initiate Time ..........................≤ 20ms, ≤ 1500 operations per minute
Time Delay/Range *** .................Adjustable 0.1s - 1023h
Repeat Accuracy ......................0.1% or 20ms, whichever is greater
Reset Time ............................≤ 150ms
Time Delay vs Temp. & Voltage. .........±2%
Input
Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 to 48VDC; 24 to 240VAC/24 to 110VDC
AC Line Frequency / DC Ripple .........50/60Hz / ≤ 10%
Tolerance 12 to 48VDC ......-15% - 20%
24 to 240VAC/24 to 110VDC ......-20% - 10%
Power Consumption ...................AC ≤ 4VA; DC ≤ 2W
Output
Type .................................Electromechanical relay
Form .................................SPDT
SPDT-NO SPDT-NC
Ratings: General Purpose 125/240VAC 30A 15A Resistive 125/240VAC 30A 15A 28VDC 20A 10A
X
Function
─Specify function
Functions:
M, B, RE, RD, S, SD, I, TS, PSD, US, AM, UB, C, CI
For a complete list of functions with descriptions and diagrams, see Appendix A - Timer Functions, pages 156-164.
1/4
Motor Load 125VAC 1 hp* 240VAC 2 hp** 1 hp**
Life ..................................Mechanical - 1 x 10
Electrical - 1 x 105, *3 x 104, ** 6,000
Protection
Surge ................................IEEE C62.41-1991 Level A
Circuitry .............................Encapsulated
Isolation Voltage ......................
Insulation Resistance ...................≥ 100 MΩ
Mechanical
Mounting ............................
Dimensions ...........................3 x 2 x 1.5 in. (76.7 x 51.3 x 38.1 mm)
Termination ..........................0.25 in. (6.35 mm) male quick connects
Environmental
Operating / Storage Temperature .......-40° to 60°C / -40° to 85°C
Humidity .............................95% relative, non-condensing
Weight ............................... 3.9 oz (111 g)
***For CE approved applications, power must be removed from the unit when a switch position is changed.
≥ 1500V RMS input to output; isolated units
Surface mt. with one #10 (M5 x 0.8) screw
hp**
6
Loading...