![](/html/0d/0d60/0d60ed212f5efa063a46057ffdc2e65a722e1a693efba27881161e0c74abb34d/bg1.png)
HRPU / HRIU SeriesTimer
Connection:
HRIU
Isolated Output
The HRPU/HRIU Series combines an
electromechanical relay output with
microcontroller timing circuitry. Its switching
capacity allows direct control of loads like
compressors, pumps, motors, heaters, and
lighting. It is a factory programmed module
available in any 1 of 14 standard functions. The
HRPU/HRIU offers a single adjustable timer
or counter function. Switch adjustment allows
accurate selection of the time delay or number
of counts. The HRPU has non-isolated relay
contacts, the HRIU has isolated relay contacts.
Encapsulation protects against shock, vibration,
and humidity. The HRPU/HRIU Series is a cost
effective approach for OEM applications that
require small size, reliability and accurate switch
adjustment.
See Appendix B, page 165, Figure 2 for dimensional
drawing.
Switch Adjustment:
Features:
• Choose 1 of 14 standard functions
• Special time ranges & functions available
• Factory programmed
• Microcontroller circuitry, ±0.1% repeat
accuracy
• 30A, SPDT, NO output contacts
• Accurate switch adjustment
• 12 to 240V operations in 2 ranges
• Delays from 0.1s - 1023h
Approvals:
Auxiliary Products:
• Female quick connect:
P/N: P1015-13 (AWG 10/12)
P/N: P1015-64 (AWG 14/16)
• Mounting bracket: P/N: P1023-6
• Quick connect to screw adaptor:
P/N: P1015-18
• DIN rail: P/N: C103PM (Al)
• DIN rail adaptor: P/N: P1023-20
Available Models:
HRIUW2I
HRIUW2M
If desired part number is not listed, please call us to
see if it is technically possible to build.
L1 N/L2
HRPU
Non-isolated Output
S1 = Initiate Switch
UTL = Optional Untimed Load
L = Load
V = Voltage
Order Table:
HRPU/
HRIU
X
Input
─W - 24 to 240VAC
24 to 110VDC
─D - 12 to 48VDC
X
Time Delay/Counts
─1 - 0.1 - 102.3s
─2 - 1 - 1023s
─3 - 0.1 - 102.3m
─4 - 1 - 1023m
─5 - 0.1 - 102.3h
─6 - 1 - 1023h
─7 - 1 - 165 counts (straight) w/ pulsed output
─8 - 1 - 1023 counts (binary) w/ pulsed output
─9 - 1 - 7 counts to start 1 - 63s or m interval time
Specications
Count Functions/Switch Type ..........Mechanical switch (counts on switch closure)
Count Range ..........................1 - 1023 counts
Counter Output (Variable 7 & 8) .........Pulse widths 300ms ±20%
Initiate Time ..........................≤ 20ms, ≤ 1500 operations per minute
Time Delay/Range *** .................Adjustable 0.1s - 1023h
Setting Accuracy ......................±1%, or 50ms, whichever is greater
Repeat Accuracy ......................0.1% or 20ms, whichever is greater
Reset Time ............................≤ 150ms
Time Delay vs Temp. & Voltage. .........±2%
Input
Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 to 48VDC; 24 to 240VAC/24 to 110VDC
AC Line Frequency / DC Ripple .........50/60Hz / ≤ 10%
Tolerance 12 to 48VDC ......-15% - 20%
24 to 240VAC/24 to 110VDC ......-20% - 10%
Power Consumption ...................AC ≤ 4VA; DC ≤ 2W
Output
Type .................................Electromechanical relay
Form .................................SPDT
SPDT-NO SPDT-NC
Ratings:
General Purpose 125/240VAC 30A 15A
Resistive 125/240VAC 30A 15A
28VDC 20A 10A
X
Function
─Specify function
Functions:
M, B, RE, RD, S, SD, I,
TS, PSD, US, AM, UB,
C, CI
For a complete list of functions with descriptions and diagrams,
see Appendix A - Timer Functions, pages 156-164.
1/4
Motor Load 125VAC 1 hp*
240VAC 2 hp** 1 hp**
Life ..................................Mechanical - 1 x 10
Electrical - 1 x 105, *3 x 104, ** 6,000
Protection
Surge ................................IEEE C62.41-1991 Level A
Circuitry .............................Encapsulated
Isolation Voltage ......................
Insulation Resistance ...................≥ 100 MΩ
Mechanical
Mounting ............................
Dimensions ...........................3 x 2 x 1.5 in. (76.7 x 51.3 x 38.1 mm)
Termination ..........................0.25 in. (6.35 mm) male quick connects
Environmental
Operating / Storage Temperature .......-40° to 60°C / -40° to 85°C
Humidity .............................95% relative, non-condensing
Weight ............................... ≅ 3.9 oz (111 g)
***For CE approved applications, power must be removed from the unit when a switch
position is changed.
≥ 1500V RMS input to output; isolated units
Surface mt. with one #10 (M5 x 0.8) screw
hp**
6