
HLMU SeriesVoltage Monitors
The HLMU Series is a universal voltage, encapsulated,
3-phase voltage monitor. It continuously measures
Features:
the voltage of each of the three phases with
microcontroller accuracy and compares the value to
preset trip points. It separately senses phase reversal
and loss; over, under and unbalanced voltages; and
over or under frequency. Protection is assured during
periods of large average voltage uctuations, or when
regenerated voltages are present. The unit trips within
200ms when phase loss is detected. Adjustable time
delays are included to prevent nuisance tripping and
short cycling of sensitive equipment. The isolated,
10A, DPDT relay contacts trip when a phase voltage
exceeds the trip limits for the trip delay. Nominal line
voltage, voltage unbalance, and time delays are knob
adjustable. The phase loss setpoint and the acceptable
frequency range are xed. Both delta and wye systems
can be monitored; no connection to neutral is required.
For more information see:
Appendix B, page 166, Figure 17 for dimensional drawing.
Appendix C, page 168, Figure 12 for connection diagram.
Operation
Upon application of line voltage, the output is de-energized and the restart delay begins. If all the three-phase voltages
are within the acceptable range, the output energizes at the end of the restart delay. The microcontroller circuitry
automatically senses the voltage range, and selects the correct operating frequency (50 or 60Hz). The over and under
voltage trip points are set at ± 10% of the adjusted line voltage. When the measured value of any phase voltage exceeds the
acceptable range limits (lower or upper) the trip delay begins. At the end of the trip delay the output relay de-energizes.
If the phase voltage returns to an acceptable value before the trip delay expires, the trip delay is reset and the output
remains energized. Under, over, and unbalanced voltages plus over or under frequency must be sensed for the complete
trip delay before the unit trips. The unit trips in 200ms when phase loss or reversal are sensed. The unit will not energize
if a fault is sensed as the line voltage is applied.
Reset: Reset is automatic upon correction of the voltage or frequency fault or phase sequence.
Restart Delay Options:
L= Lockout or minimum OFF time. The restart delay begins when the output trips. The unit cannot be re-energized until the restart delay is complete. This provides a minimum off time
or lockout time to allow equipment sensitive to short cycling, time to reset. If the fault is corrected after the restart delay is complete, the output energizes immediately. The restart delay
also occurs when line voltage is applied/reapplied.
R= Restart Delay on fault correction. The restart delay begins when line voltage is reapplied or when a voltage fault is corrected. This option is normally selected when staggered restarting
of multiple motors on a power system is required.
N= No Restart Delay. 0.6 second initialization delay on application of line voltage applies.
Restart Notes:
All restart options remain reset when the following conditions are detected:
1.) Phase loss (phase unbalance greater than 25%) 2.) Average line voltage less than 120VAC 3.) Phase reversal
The restart delay begins when the condition is corrected.
LED Operation
The LED ashes green during the restart delay, then glows green when the output energizes. It ashes red during the trip delay then glows red when the output de-energizes. It ashes
red/green if phase reversal is sensed. If a fault is sensed during the restart delay, the LED will glow red during that portion or the full restart delay.
Order Table:
HLMU
X
Output
─D - DPDT
─S - SPDT
X
Restart Function
─L - Lockout, Min Off Time
─R - Staggered Restarting
─N - No Restart Delay
X
Voltage Unbalance
─A - Adjustable 2-10%
─Fixed - Specify Unbalance
2-10% in 1% increments,
using two digits [04]
X
Trip Delay
─A - Adjustable 1-30s
─Fixed - Specify delay
1-30s in 1s increments,
using two digits [05]
• Protects against phase loss & reversal; over,
under & unbalanced voltages; & over &
under frequency
• Encapsulated circuitry
• Isolated, 10A, DPDT output contacts
• LED indicates relay status, faults, & time
delays
• Universal line voltage 200 to 480VAC in
one unit
• Compact design
• Finger-safe terminal blocks, up to 12 AWG
• ASME A17.1 rule 210.6
• NEMA MG1 14:30, 14:35
• IEEE C62.41-1991 Level B
Approvals:
Auxiliary Products:
• 3-Phase fuse block/disconnect:
P/N: FH3P
• 2 Amp fuse: P/N: P0600-11
• DIN rail: P/N: C103PM (Al)
• DIN rail adaptor: P/N: P1023-20
Available Models:
HLMUDLAAA
HLMUDN0405N
HLMUDNAAN
If desired part number is not listed, please call us to
see if it is technically possible to build.
X
Restart Delay
─A* - Adjustable 0.6-300s
─N - No Restart Delay
HLMUDRAAA
HLMUSR0604A
*Selection “A” is only
available for Restart
Functions “L” and “R”
Specications
Line Voltage
Type ............................... 3-phase delta or wye with no connection to neutral
Operating Voltage 200 - 480VAC Range Voltage Adj. Range Frequency
240 200-240VAC 50 or 60Hz
380 340-420VAC 50Hz
480 400-480VAC 60Hz
Line Voltage Max. . . . . . . . . . . . . . . . . . . . 550VAC
AC Line Frequency . . . . . . . . . . . . . . . . . . 50/60 Hz automatically detected
Phase Loss . . . . . . . . . . . . . . . . . . . . ≥ 25% unbalance
Response Time . . . . . . . . . . . . . . . . . . . . ≤200ms
Undervoltage & Voltage Unbalance
Type ............................... Voltage detection with delayed trip &
automatic reset
Overvoltage Trip Voltage .... 109 - 113% of the adjusted line voltage
Reset Voltage ... ≅ -3% of the trip voltage
Undervoltage Trip Voltage .... 88 - 92% of the adjusted line voltage
Reset Voltage ... ≅ +3% of the trip voltage
Voltage Unbalance Trip Setpoint .... Adjustable 2 - 10% or specify xed
unbalance of 2 - 10% in 1% increments
Reset on Balance ≅ -0.7% unbalance
Trip Delay Active On ...... Over/undervoltage, voltage unbalance,
over/under frequency
Range .......... Adjustable from 1 - 30s or specify xed
delay 1 - 30s in 1s increments
Tolerance ....... ± 15%
Restart Delay Range .......... Adjustable from 0.6 - 300s; if no restart
delay is selected a 0.6s initialization delay
applies
Tolerance ....... ± 15%
112
Over/Under Frequency . . . . . . . . . . . . . . . . . ±4%; Reset ±3%; 50/60 Hz
Phase Sequence . . . . . . . . . . . . . . . . . . . . . . . A, B, C, L1, L2, L3
Response Time-Phase Reversal & Phase Loss. . . . . . ≤200 ms
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Automatic
Output
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Isolated Electromechanical Relay
Form .................................. DPDT
Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10A resistive @ 240VAC; 8A resistive @ 277VAC;
NO-1/4 hp @ 120VAC; 1/3 hp @ 240VAC
Life ................... . . . . . . . . . . . . . . . . Mechanical - 1 x 10
Electrical (at 10A) - DPDT - 1 x 30
Protection
Surge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEEE C62.41-1991 Level B
Isolation Voltage . . . . . . . . . . . . . . . . . . . . . . . ≥ 2500V RMS input to output
Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Encapsulated
Mechanical
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Surface mount with one #10 (M5 x 0.7) screw
Note: 0.25 in.(6.35 mm) spacing between units or other devices is required
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 x 2 x 1.64 in. (76.7 x 51.3 x 41.7 mm)
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . Screw terminal connection up to
12 AWG (3.3 mm2) wire
Environmental
Operating / Storage Temperature ........ -40° to 60°C / -40° to 85°C
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95% relative, non-condensing
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≅ 3.9 oz (111 g)
6
www.ssac.com • 800-843-8848 • fax: 605-348-5685
3

Appendix C - Connection Diagrams
FIGURE 1 - FSU1000 Series
L1 N/L2
S1 = Optional low current switch
V = Voltage
L = Load
FIGURE 5 - FS300 Series
V = Voltage
L = Load
Note: Load may be in positive side.
FIGURE 2 - FS100 Series
L1 N
V = Voltage
L = Load
R = Red Wire
B = Black Wire
FIGURE 6 - FS400 Series
L1 N/L2
V = Voltage
L = Load
R = Red Wire
B = Black Wire
W= White Wire
FIGURE 3 - FS100 Series FIGURE 4 - FS200 Series
L1 N/L2
V = Voltage
V = Voltage
L = Load
FIGURE 7 - AF Series
L1 N/L2
V = Voltage
L = Load
L = Load
FIGURE 8 - FS500 Series
L1 N/L2
V = Voltage
FIGURE 11 - DLMU Series
FIGURE 9 - SC3/SC4 Series
SC4 shown;
for SC3, terminal 6 & load L4 are eliminated.
FIGURE 12 - HLMU Series
Note: Relay contacts are
L1, L2, L3 = Line Voltage Input
NO = Normally Open Contact
NC = Normally Closed Contact
C = Common, Transfer Contact
CAUTION: 2 amp max. fast acting fuses are
recommended to protect the equipment‘s
wiring. They are not required to protect the
HLMU.
isolated, 277VAC max.
FIGURE 10 - WVM Series
F = Fuses
NO = Normally Open
NC = Normally Closed
RS =
Optional Remote Reset Switch
Relay contacts are isolated.
CAUTION:
2 amp max fast acting fuses must
be installed externally in series
with each input. (3)
FIGURE 13 PLMU/PLM/PLR/PLS Series
F = Fuses
ØA = Phase A = L1
ØB = Phase B = L2
ØC = Phase C = L3
NO = Normally Open
NC = Normally Closed
2A fast acting fuses
recommended for safety (not
required)
Relay contacts are isolated.
!
L1, L2, L3 = Line Voltage Input
NO = Normally Open Contact
NC = Normally Closed Contact
C = Common, Transfer Contact
CAUTION: 2 amp max. fast acting
fuses are recommended to protect
the equipment‘s wiring. They are not
required to protect the DLMU.
! = Select alarm contact connection as N.O. or
N.C. when ordering; N.O. Shown.
FIGURE 14 TVM/TVW Series
L1 = Phase A
L2 = Phase B
L3 = Phase C
NO = Normally Open
NC = Normally Closed
C = Common, Transfer Contact
Relay contacts are isolated.
F = 2A Fast acting fuses are recommended,
but not required
168
www.ssac.com • 800-843-8848 • fax: 605-348-5685