3130
www.sunnyrooproducts.com
Specifications
Unit Model SR1500TL SR2000TL SR3000TL SR4200TL SR5000TL
Inverter Technology
Conversion Mode Sine-wave, Current source, High frequency PWM
Isolation Method Transformer-less Design*
DC Input Data
Nominal DC Voltage 360 VDC
Maximum DC Input Voltage 500 VDC
Work Range 120VDC~500VDC**
Maximum DC Input Current
(each MPPT follower)
10.5 Amp 14.6 Amp 22 Amp 14.7 Amp 18.3 Amp
MPPT Range 150 VDC ~ 450 VDC
MPPT Follower 1 2
AC Output Data
Nominal AC Power 1500 2000 3000 4000 5000
Nominal AC Voltage AC 230V
Output Connection Method 1-Phase / 2-Wires (L, N, E)
AC Voltage Range 207~264 Vac
Nominal AC Current 6.5 Amp 8.7 Amp 13 Amp 17.4 Amp 21.7 Amp
Frequency 47 ~ 50.5 Hz
Power Factor >0.99 with nominal AC current
DC Injection
< 20mA
Current Distortion
Total Harmonic current : Less than 5%
Single Harmonic current : Less than 3%
Efficiency Data
Maximum Cont. Efficiency >96%
Euro Efficiency >94%
Environment
Operating Temperature -20 °C ~ +50 °C
Humidity 0 to 90% (without condensation)
Altitude 0 ~ 2000 M / 0 ~ 6600 ft
Mechanical Data
Dimensions (H x W x D in mm) 455 x 430 x 170 455 x 510 x 170
Weight (Kgs) 23 28
Protection Class IP65, Outdoors
Cooling Free Convection
AC Connection Terminal
DC Connection Multi-Contact
Unit Model SR1500TL SR2000TL SR3000TL SR4200TL SR5000TL
Communication
Communication
Interface
Standard RS232
Optional USB, RS485, dry contact, TCP/IP
Front Panel
LCD
Boost input Voltage/Boost input Current/Boost input Power/AC output Voltage /AC output
frequency/AC output current /AC output power/AC Energy yield/Inner Temperature/Heat sink
Temperature /Status message/ Error message
LED
RED Leakage current fault or DC input isolation fault
Yellow Spec. of Utility is not matched with the Utility specifications of the inverter
Green Solar Cell power is greater or smaller than sleep power
Key Pad UP key/ Down key/ Function key/ Enter key
Protection
Utility Over/under Voltage, Over/ under Frequency, Earth fault, DC Isolation fault
Islanding operation
detection
Passive : Voltage phase jump detection
Active : Reactive power control
Over Temperature Reduced output power
Certification
Performance and
Safety Compliance
ER G83/1, VDE0126-1-1, EN50178, IEC62103
EMI/EMC EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
North American UL1741, IEEE1547
Australia AS3100, AS/NZS4777
* If isolation is necessary, option one extra transformer.
** The rated range should be 150VDC-500VDC in order to get the rated output.