Product data sheet
Characteristics
XMLP200PD230
pressure transmitter - XMLP - 200psi - 1/4"18NPT
- 4..20mA - M12 - set 1
Product availability : Stock - Normally stocked in distribution facility
Main
Range of product OsiSense XM
Product or component type Electronic pressure sensors
Pressure sensor type Pressure transmitter
Pressure sensor name XMLP
Electrical circuit type Control circuit
Pressure sensor size 1378.95kPa (200psi)
Local display Without
Controlled fluid Fresh water 32…275°F (0…135°C))
Fluid connection type 1/4" - 18 NPT (male)
Electrical connection 1 male connector M12 4 pins
[Us] rated supply voltage 12...24 V DC SELV 7…33V)
Current consumption < 23 mA
Type of output signal Analogue
Analogue output function 4...20 mA, 2-wire
Quantity per set Set of 1
Type of packing Individual
Air -40…275°F (-40…135°C))
Hydraulic oil -40…275°F (-40…135°C))
Gas -40…275°F (-40…135°C))
Refrigeration fluid -40…275°F (-40…135°C))
Complementary
Pressure setting range 0.00…1378.95kPa (0…200psi)
Maximum permissible accidental
pressure
Destruction pressure 9652.66kPa (1400psi)
Materials in contact with fluid Stainless steel AISI 316L
Feb 20, 2020
4136.85kPa (600psi)
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1

Operating position Any position
Protection type Reverse polarity
Electromagnetic compatibility Electrostatic discharge immunity test EN/IEC 61000-4-2 8 kV air, 4 kV contact
[Uimp] rated impulse withstand voltage 0.5kV
Response time on output <= 2 ms 10...90 % of full scale
Measurement accuracy +/- 0.5 % of the measuring range
Resolution 0.1 % of the measuring range
Drift of the sensitivity +/- 0.02 % of measuring range/°K
Drift of the zero point +/- 0.02 % of measuring range/°K
Mechanical durability 10000000cycles
Net weight 0.19lb(US) (0.088kg)
Diameter 1.02in (26mm)
Length 1.42in (36mm)
Load short-circuit
1.2/50 µs shock waves immunity test EN/IEC 61000-4-5 1 kV 42 Ohm
Immunity to magnetic fields EN/IEC 61000-4-8 100 A/m 50 Hz
Electrical fast transient/burst immunity test EN/IEC 61000-4-4 4 kV
Susceptibility to electromagnetic fields EN/IEC 61000-4-3 10 V/m 80...3000 MHz
Radiated RF fields EN/IEC 61000-4-6 10 V 0.01...80 MHz
Environment
Standards NSF ANSI 61
Product certifications CE
Protective treatment TC
Ambient air temperature for operation -22…185°F (-30…85°C)
Ambient air temperature for storage -58…212°F (-50…100°C)
Vibration resistance 20 gn (f = 15…2000Hz) conforming to EN/IEC 60068-2-6
Shock resistance 100 gn 11ms EN/IEC 60068-2-27
IP degree of protection IP65 EN/IEC 60529
EN/IEC 61326-2-3
EAC
CULus
RCM
IP67 EN/IEC 60529
IP69K EN/IEC 60529
Ordering and shipping details
Category 22419 - PRESSURE SWITCH IEC (HIGH,LOW,GEN)
Discount Schedule DS2
GTIN 00785901717430
Returnability Yes
Country of origin CH
Offer Sustainability
Sustainable offer status Green Premium product
California proposition 65 WARNING: This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and
REACh free of SVHC Yes
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free Yes
RoHS exemption information Yes
Environmental Disclosure Product Environmental Profile
Circularity Profile No need of specific recycling operations
2
Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and
Reproductive harm. For more information go to www.p65warnings.ca.gov
EU RoHS Declaration