The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Product data sheet
Characteristics
XB4BD53
black selector switch Ø22 3-position spring
return 2NO 600V
Main
Range of product Harmony XB4
Product or component
type
Device short name XB4
Bezel material Chromium plated metal
Fixing collar material Zamak
Mounting diameter 22 mm
Sale per indivisible
quantity
Shape of signaling unit
head
Type of operator Spring return to centre
Operator profile Black standard handle
Operator position information
Contacts type and composition
Contacts operation Slow-break
Connections - terminals Screw clamp terminals : <= 2 x 1.5 mm² with cable
Complete selector switch
1
Round
3 positions +/- 45°
2 NO
end conforming to EN/IEC 60947-1
Screw clamp terminals : >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1
Complementary
Height 47 mm
Width 30 mm
Depth 68 mm
Terminals description ISO n°1 (13-14)NO
Product weight 0.105 kg
Resistance to high pressure washer 7000000 Pa at 55 °C,distance: 0.1 m
Contacts usage Standard contacts
Positive opening Without positive opening
Torque value 0.14 N.m (NO changing electrical state)
Mechanical durability 1000000 cycles
Tightening torque 0.8...1.2 N.m conforming to EN 60947-1
Shape of screw head Cross head compatible with Philips no 1 screwdriver
Contacts material Silver alloy (Ag/Ni)
Short circuit protection 10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal current 10 A conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage 600 V (degree of pollution: 3) conforming to EN 60947-1
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-1
[Ie] rated operational current 3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
(23-24)NO
Cross head compatible with pozidriv No 1 screwdriver
Slotted head compatible with flat Ø 4 mm screwdriver
Slotted head compatible with flat Ø 5.5 mm screwdriver
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
Nov 30, 2016
1

Electrical durability 1000000 cycles, AC-15, 2 A at 230 V, operating rate: 3600 cyc/h, load factor: 0.5
Electrical reliability IEC 60947-5-4 Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to EN/IEC
conforming to EN 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate: 3600 cyc/h, load factor:
0.5 conforming to EN 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate: 3600 cyc/h, load factor: 0.5
conforming to EN 60947-5-1 appendix C
60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC
60947-5-4
Environment
Protective treatment TH
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -25...70 °C
Overvoltage category Class I conforming to IEC 60536
IP degree of protection IP69K conforming to IEC 60529
NEMA degree of protection NEMA 13
IK degree of protection IK06 conforming to IEC 50102
Standards EN/IEC 60947-1
Product certifications BV
Vibration resistance 5 gn (f = 2...500 Hz) conforming to IEC 60068-2-6
Shock resistance 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC
NEMA 4X
EN/IEC 60947-5-1
EN/IEC 60947-5-4
EN/IEC 60947-5-5
JIS C 4520
UL 508
CSA C22.2 No 14
CSA
DNV
GL
LROS (Lloyds register of shipping)
RINA
UL
60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC
60068-2-27
2