Product data sheet
RM35JA31MW
current control relay RM35-J - range 2..500 mA
Main
Range of product Zelio Control
Product or component type
Relay type Current control relay
Relay name RM35JA
Relay monitored pa­rameters
Time delay Adjustable 0.3...30 s, 0 + 10 % on crossing the
Switching capacity in VA
Minimum switching cur­rent
Maximum switching current
Power consumption in VA
Measurement range 50...500 mA E3-M terminals
Utilisation category DC-14 conforming to IEC 60947-5-1
Modular measurement and control relays
Overcurrent or undercurrent detection Overcurrent or undercurrent in window mode
threshold Tt Adjustable 1...20 s, 0 + 10 % on energisation Ti
1250 VA
10 mA at 5 V DC
5 A AC
<= 3.5 VA AC
2...500 mA current
2...20 mA E1-M terminals
10...100 mA E2-M terminals
DC-13 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-12 conforming to IEC 60947-5-1
Complementary
Reset time 1500 ms for time delay
Maximum switching voltage 250 V AC
[Us] rated supply voltage 24...240 V AC/DC, 50/60 Hz +/- 10 %
Supply voltage limits 20.4...264 V AC/DC
Operating voltage tolerance - 15 % + 10 % Un
Power consumption in W <= 0.6 W DC
Control circuit frequency 40...70 Hz +/- 10 %
Resistance across terminals 0.2 Ohm E3-M terminals
Output contacts 2 C/O
Nominal output current 5 A
Measuring cycle <= 30 ms measurement cycle as true rms value
Hysteresis 5...50 % of threshold setting
Delay at power up 0.3 s
Measurement accuracy +/- 10 % of the full scale value
Repeat accuracy +/- 2 % for time delay
Measurement error 1 by volt over the whole range with voltage variation
Polarity No DC
Threshold setting 10...100 %
5 Ohm E1-M terminals 1 Ohm E2-M terminals
+/- 0.5 % for input and measurement circuit
0.05 %/°C with temperature variation
Oct 13, 2015
1
Marking CE : 73/23/EEC
Overvoltage category III conforming to IEC 60664-1
Insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage 250 V conforming to IEC 60664-1
Insulation Between supply and measurement
Operating position Any position without derating
Connections - terminals Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with ca-
Tightening torque 0.6...1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing plastic
Local signalling LED yellow for relay ON
Mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Operating rate <= 360 operations/hour under full load
Contacts material Cadmium free
Width 35 mm
Product weight 0.13 kg
CE : EMC 89/336/EEC
> 500 MOhm at 500 V DC conforming to IEC 60255-5
ble end Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 12, flexible cable with ca­ble end Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end Screw terminals 1 x 0.5...1 x 4 mm² - AWG 20...AWG 11, solid cable without ca­ble end
LED green for power ON
Environment
Immunity to microbreaks 50 ms
Electromagnetic compatibility Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Standards EN/IEC 60255-6
Product certifications CSA
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -20...50 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance 1 gn (f = 57.6...150 Hz) conforming to IEC 60255-21-1
Shock resistance 15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection IP30 (casing) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Dielectric test voltage 2 kV AC 50 Hz, 1 min conforming to IEC 60664-1
Non-dissipating shock wave 4 kV conforming to IEC 61000-4-5
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Emission standard for industrial environments conforming to EN/IEC 61000-6-4
C-Tick GL GOST UL
0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6
IP20 (terminals) conforming to IEC 60529
2 kV AC 50 Hz, 1 min conforming to IEC 60255-5
4 kV conforming to IEC 60664-1 4 kV conforming to IEC 60255-5