Product data sheet
Characteristics
RM17TU00
multifunction control relay RM17-TU - range
183..528 V AC
Main
Range of product Zelio Control
Product or component type Modular measurement and control relays
Relay type Multifunction control relay
Product specific application For 3-phase supply
Relay name RM17TU
Relay monitored parameters Phase failure detection
Time delay type Adjustable 0.1...10 s, +/- 10 % of the full scale value
Switching capacity in VA 1250 VA
Measurement range 208...480 V voltage AC
Phase sequence
Undervoltage detection
Complementary
Reset time 1500 ms for time delay
Maximum switching voltage 250 V AC
Minimum switching current 10 mA at 5 V DC
Maximum switching current 5 A AC
Supply voltage limits 183...528 V AC
Control circuit voltage limits - 12 % + 10 % Un
Power consumption in VA <= 22 VA at 400 V AC 50 Hz
Control circuit frequency 50...60 Hz +/- 10 %
Output contacts 1 C/O
Nominal output current 5 A
Measurement voltage limits 183...528 V AC
Hysteresis 2 %
Run-up delay at power-up <= 650 ms
250 V DC
5 A DC
Jun 21, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1

Measuring cycle <= 150 ms measurement cycle as true rms value
Threshold adjustment voltage +2...+17 % in the range 480 V AC
Voltage range 208...480 V phase to phase
Adjustment of asymmetry threshold 5...15 % of Un selected
Repeat accuracy 0.5 % for input and measurement circuit
Measurement error < 0.05 %/°C with temperature variation
Phase failure sensitivity 0.7 Un
Response time < 200 ms in the event of a fault
Marking CE
Overvoltage category III conforming to IEC 60664-1
Insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60255-5
[Ui] rated insulation voltage 400 V conforming to IEC 60664-1
Supply frequency 50/60 Hz +/- 10 %
Operating position Any position without
Connections - terminals Screw terminals 1 x 0.5...1 x 4 mm² - AWG 20...AWG 11, solid cable without cable end
Tightening torque 0.6...1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing plastic
Local signalling LED green for power ON
Mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability 100000 cycles
Mechanical durability <= 30000000 cycles
Operating rate <= 360 operations/hour under full load
Utilisation category AC-12 conforming to IEC 60947-5-1
Safety reliability data MTTFd = 502.2 years
Width 17.5 mm
Product weight 0.13 kg
-2...-12 % in the range 208 V AC
-2...-17 % in the range 220 V AC
2...20 % of Un selected
3 % for time delay
< 1 % over the whole range with voltage variation
> 500 MOhm at 500 V DC conforming to IEC 60664-1
Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end
Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 12, flexible cable with cable end
Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with cable end
LED yellow for relay ON
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
B10d = 470000
Environment
Electromagnetic compatibility Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Standards EN/IEC 60255-1
Product certifications CSA
Directives 89/336/EEC - electromagnetic compatibility
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -20...50 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance 0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6
2
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC
61000-6-3
Immunity for industrial environments conforming to EN/IEC 61000-6-2
C-Tick
GL
GOST
UL
73/23/EEC - low voltage directive

1 gn (f = 57.6...150 Hz) conforming to IEC 60255-21-1
Shock resistance 15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection IP20 (terminals) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Dielectric test voltage 2 kV 1 min AC 50 Hz conforming to IEC 60255-5
Non-dissipating shock wave 4 kV conforming to IEC 60255-5
IP30 (casing) conforming to IEC 60529
2 kV 1 min AC 50 Hz conforming to IEC 60664-1
4 kV conforming to IEC 60664-1
4 kV conforming to IEC 61000-4-5
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0701 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
End of life manual
Product end of life instructions Available
Contractual warranty
Warranty period 18 months
3

Product data sheet
Dimensions Drawings
Multifunction 3-Phase Supply Control Relays
Dimensions and Mounting
RM17TU00
4

Product data sheet
Connections and Schema
Multifunction 3-Phase Supply Control Relays
Wiring Diagram
RM17TU00
5

Product data sheet
RM17TU00
Technical Description
Function Diagrams
Phase Sequence Control and Phase failure Detection (U measured < 0.7 x supply voltage)
Undervoltage Control
Legend
Un Nominal 3-phase supply voltage
Tt Time delay after crossing of threshold (adjustable on front panel)
H Hysteresis
U< Undervoltage threshold
L1, L2, L3 Phases of the supply voltage monitored
11-12, 11-14 Output relay connections (refer to Connections and Schema)
Relay status: black color = energized.
6