Product data sheet
Characteristics
M9F42103
Multi 9 - C60BP - MCB - 1P - 3 A - C Curve - 277
V - 10 kA - UL 489
Main
Range Multi 9
Product name Multi 9 C60
Product or component type Miniature circuit-breaker
Device short name C60BP
Device application Distribution
Poles description 1P
Number of protected poles 1
[In] rated current 3 A at 25 °C conforming to EN/IEC 60947-2
Network type AC
DC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity Icu 3 kA at 415 V AC conforming to EN/IEC 60947-2
Icu 10 kA at 240 V AC conforming to EN/IEC 60947-2
Icu 20 kA at 60 V DC conforming to EN/IEC 60947-2
Icu 3 kA at 415 V AC conforming to GB 14048.2
Icu 10 kA at 240 V AC conforming to GB 14048.2
Icu 20 kA at 60 V DC conforming to GB 14048.2
AIR 10 kA at 277 V AC conforming to UL 489
AIR 14 kA at 240 V AC conforming to UL 489
AIR 14 kA at 120 V AC conforming to UL 489
AIR 10 kA at 60 V DC conforming to UL 489
AIR 10 kA at 277 V AC conforming to CSA C22.2 No 5
AIR 14 kA at 240 V AC conforming to CSA C22.2 No 5
AIR 14 kA at 120 V AC conforming to CSA C22.2 No 5
AIR 10 kA at 60 V DC conforming to CSA C22.2 No 5
Suitability for isolation Yes conforming to EN/IEC 60947-2
Standards UL 489
CSA C22.2 No 5
GB 14048.2
EN/IEC 60947-2
Product certifications UL
CSA
Feb 28, 2019
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1

CCC
IEC
Complementary
[Ue] rated operational voltage 240 V AC 50/60 Hz
Magnetic tripping limit 8.5 x In +/- 20% AC
[Ics] rated service breaking capacity 2.25 kA 75 % x Icu at 415 V AC conforming to EN/IEC 60947-2
[Ui] rated insulation voltage 500 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2
Contact position indicator Yes
Control type Toggle
Local signalling ON/OFF indication
Mounting mode Clip-on
Mounting support DIN rail
9 mm pitches 2
Height 103 mm
Width 18 mm
Depth 72 mm
Colour Grey
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Provision for padlocking Padlockable
Connections - terminals Tunnel type terminal, top or bottom flexible with ferrule wire(s) 1...16 mm² max (AWG 18...AWG 8)
Wire stripping length 14 mm (top or bottom)
Tightening torque 2.5 N.m (top or bottom)
Earth-leakage protection Without
415 V AC 50/60 Hz
60 V DC
12 x In +/- 20% DC
7.5 kA 75 % x Icu at 240 V AC conforming to EN/IEC 60947-2
2.25 kA 75 % x Icu at 415 V AC conforming to GB 14048.2
7.5 kA 75 % x Icu at 240 V AC conforming to GB 14048.2
15 kA 75 % x Icu at 60 V DC conforming to GB 14048.2
15 kA 75 % x Icu at 60 V DC conforming to EN/IEC 60947-2
Tunnel type terminal, top or bottom rigid wire(s) 1...25 mm² max (AWG 18...AWG 8)
Tunnel type terminal, top or bottom flexible wire(s) 1...16 mm² max (AWG 18...AWG 8)
Environment
IP degree of protection IP40 for modular enclosure conforming to IEC 60529
Pollution degree 3 conforming to EN/IEC 60947-2
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % ( 55 °C )
Operating altitude 0...2000 m
Ambient air temperature for operation -30...70 °C
Ambient air temperature for storage -40...80 °C
IP20 conforming to IEC 60529
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1719 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
2