Product data sheet
Characteristics
M9F22106
Multi 9 - C60SP - MCB - 1P - 6 A - C Curve - 277
V - 10 kA - UL 1077
Main
Range Multi 9
Product name Multi 9 C60
Product or component type Miniature circuit-breaker
Device short name C60SP
Device application Distribution
Poles description 1P
Number of protected poles 1
[In] rated current 6 A at 25 °C conforming to EN/IEC 60947-2
Network type DC
AC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity AIR 10 kA at 277 V AC conforming to UL 1077
AIR 14 kA at 240 V AC conforming to UL 1077
AIR 14 kA at 120 V AC conforming to UL 1077
AIR 10 kA at 65 V DC conforming to UL 1077
AIR 10 kA at 277 V AC conforming to CSA C22.2 No 235
AIR 14 kA at 240 V AC conforming to CSA C22.2 No 235
AIR 14 kA at 120 V AC conforming to CSA C22.2 No 235
AIR 10 kA at 65 V DC conforming to CSA C22.2 No 235
Icu 3 kA at 415 V AC conforming to EN/IEC 60947-2
Icu 10 kA at 240 V AC conforming to EN/IEC 60947-2
Icu 20 kA at 60 V DC conforming to EN/IEC 60947-2
Icu 3 kA at 415 V AC conforming to GB 14048.2
Icu 10 kA at 240 V AC conforming to GB 14048.2
Icu 20 kA at 60 V DC conforming to GB 14048.2
Suitability for isolation Yes conforming to EN/IEC 60947-2
Standards UL 1077
GB 14048.2
EN/IEC 60947-2
CSA C22.2 No 235
Product certifications CSA
CCC
Aug 17, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1

IEC
UR
Complementary
[Ue] rated operational voltage 240 V AC 50/60 Hz
Magnetic tripping limit 8.5 x In +/- 20% AC
[Ics] rated service breaking capacity 2.25 kA 75 % x Icu at 415 V AC conforming to EN/IEC 60947-2
[Ui] rated insulation voltage 500 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2
Contact position indicator Yes
Control type Toggle
Local signalling ON/OFF indication
Mounting mode Clip-on
Mounting support DIN rail
9 mm pitches 2
Height 81 mm
Width 18 mm
Depth 72 mm
Colour Grey
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Provision for padlocking Padlockable
Connections - terminals Tunnel type terminal, top or bottom flexible with ferrule wire(s) 1...16 mm² max (AWG 18...AWG 8)
Wire stripping length 14 mm (top or bottom)
Tightening torque 2.5 N.m (top or bottom)
Earth-leakage protection Without
415 V AC 50/60 Hz
60 V DC
12 x In +/- 20% DC
7.5 kA 75 % x Icu at 240 V AC conforming to EN/IEC 60947-2
20 kA 100 % x Icu at 60 V DC conforming to EN/IEC 60947-2
2.25 kA 75 % x Icu at 415 V AC conforming to GB 14048.2
7.5 kA 75 % x Icu at 240 V AC conforming to GB 14048.2
20 kA 100 % x Icu at 60 V DC conforming to GB 14048.2
Tunnel type terminal, top or bottom rigid wire(s) 1...25 mm² max (AWG 18...AWG 8)
Tunnel type terminal, top or bottom flexible wire(s) 1...16 mm² max (AWG 18...AWG 8)
Environment
IP degree of protection IP40 for modular enclosure conforming to IEC 60529
Pollution degree 3 conforming to EN/IEC 60947-2
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % ( 55 °C )
Operating altitude 0...2000 m
Ambient air temperature for operation -30...70 °C
Ambient air temperature for storage -40...80 °C
IP20 conforming to IEC 60529
Offer Sustainability
Sustainable offer status Not Green Premium product
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
2