Square D M9D11610 Data Sheet

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Product data sheet
M9D11610
Multi 9 - N40 Vigi - 1P + N - 10 A - C curve - 240 V - 30 mA - 10 kA
Main
Circuit breaker applica­tioncircuit breaker appli­cation
Rangerange Multi 9
Product nameproduct name
Product or component typeproduct or compo­nent type
Device short namede­vice short name
Poles descriptionpoles description
Neutral positionneutral position
Number of protected polesnumber of protect­ed poles
[In] rated current[In] rat­ed current
Network typenetwork type
Trip unit technologytrip unit technology
Curve codecurve code C
Earth-leakage sensitivi­tyearth-leakage sensitiv­ity
Earth-leakage protec­tion time delayearth­leakage protection time delay
Earth-leakage protec­tion classearth-leakage protection class
Breaking capacity­breaking capacity
Utilisation categoryutili­sation category
Distribution
N40 Vigi
Earth leakage circuit breaker
N40 Vigi
1P + N
Left
1
10 A
AC
Thermal-magnetic
30 mA
Instantaneous
Class AC
Icu 10 kA at 240 V AC 50 Hz conforming to EN/IEC 60947-2 Icn 6000 A at 240 V AC 50 Hz conforming to EN/IEC 61009-1
Category A
Complementary
Network frequencynetwork frequency 50 Hz
System VoltageSystem Voltage 240 V AC 50 Hz
Magnetic tripping limitmagnetic tripping limit 8.5 x In +/- 20 %
Residual current tripping technologyresidual current tripping technology
[Ics] rated service breaking capacity[Ics] rated ser­vice breaking capacity
Aug 8, 2016
Voltage independent
Ics 7.5 kA 240 V AC 50 Hz
1
Limitation classlimitation class 3 3  conforming to   conforming to  EN/IEC 61009-1 EN/IEC
[Ui] rated insulation voltage[Ui] rated insulation volt­age
[Uimp] rated impulse withstand voltage[Uimp] rated impulse withstand voltage
Contact position indicatorcontact position indicator Yes
Control typecontrol type Toggle
Local signallinglocal signalling ON/OFF indication
Mounting supportmounting support DIN rail
9 mm pitches9 mm pitches 4
Heightheight 3.19 in (81 mm)
Widthwidth 1.42 in (36 mm)
Depthdepth 2.76 in (70 mm)
Product weightproduct weight 0.28 lb(US) (0.125 kg)
Colourcolour Grey
Mechanical durabilitymechanical durability 20000 cycles
Electrical durabilityelectrical durability 20000 cycles
Provision for padlockingprovision for padlocking Padlockable
Connections - terminalsconnections - terminals Tunnel type terminal top or bottom 0.75...16 mm² rigid
Wire stripping lengthwire stripping length 0.51 in (13 mm) top or bottom
Tightening torquetightening torque 17.7 lbf.in (2 N.m) top or bottom
Earth-leakage protectionearth-leakage protection Integrated
61009-1
400 V AC 50 Hz
4 kV
Fault indication
Tunnel type terminal top or bottom 0.33...10 mm² flexible
Environment
Standardsstandards EN/IEC 61009-1
IP degree of protectionIP degree of protection IP20 conforming to IEC 60529
Pollution degreepollution degree 3
Overvoltage categoryovervoltage category IV
Tropicalisationtropicalisation 2 conforming to IEC 60068-1
Relative humidityrelative humidity 95 % ( 131 °F (55 °C) )
Ambient air temperature for operationambient air temperature for operation
Ambient air temperature for storageambient air tem­perature for storage
23...140 °F (-5...60 °C)
-22...158 °F (-30...70 °C)
Offer Sustainability
Sustainable offer statusSustainable offer status Green Premium product
RoHS (date code: YYWW)RoHS (date code: YY­WW)
REAChREACh Reference not containing SVHC above the threshold
Product environmental profileProduct environmental profile
Product end of life instructionsProduct end of life in­structions
Compliant  - since  1201  -  Schneider Electric declaration
of conformity Schneider Electric declaration of conformity
Available
Need no specific recycling operations
2