The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Product data sheet
Characteristics
LR9D32
TeSys LRD - electronic thermal overload relay 3P - 6.4...32 A
Main
Range TeSys
Product name TeSys LRD
Device short name LR9D
Product or component
type
Relay application Motor protection
Product compatibility LC1D09
Overload tripping class Class 5…30
Thermal protection ad-
justment range
Power consumption <= 300 mW
Mounting support Rail with specific accessories
Electronic thermal overload relay
LC1D12
LC1D18
LC1D25
LC1D32
LC1D38
6.4...32 A
Plate with specific accessories
Under contactor
Complementary
[Ue] rated operational voltage 660 V for signalling circuit
[Ui] rated insulation voltage 690 V signalling circuit
Control type Grey dial for full-load current adjustment mode
Time range 1.5...4 min - automatic reset time
[Uimp] rated impulse withstand voltage 6 kV
Connections - terminals Power circuit : screw clamp terminals 1 cable 16 mm² - cable stiffness: solid or
Tightening torque Power circuit : 3.1 N.m - on screw clamp terminals
Height 79.9 mm
Width 45 mm
Depth 72.5 mm
Product weight 0.18 kg
690 V for power circuit
1000 V power circuit
Red knob for automatic reset mode
White 2 microswitches adjustable trip class
Red push-button stop and manual reset
flexible - without cable end cable end
Control circuit : screw clamp terminals 1 cable 2.5 mm² - cable stiffness: solid or
flexible - without cable end cable end
Control circuit : 0.8 N.m - on screw clamp terminals
Environment
Standards IEC 60947-4-1
Product certifications CCC
IP degree of protection IP20 conforming to VDE 0106
CSA C22.2
GB 14048.4
UL 60947-4-1
CSA
CULus
TÜV
IP20 conforming to IEC 60529
Jan 28, 2016