TeSys K reversing contactor - 3P - AC-3 <= 440 V
12 A - 1 NO - 24 V AC coil
Product availability : Stock - Normally stocked in distribution facility
Main
RangeTeSys
Product nameTeSys K
Product or component typeReversing contactor
Device short nameLC2K
Device applicationControl
Contactor applicationMotor control
Utilisation categoryAC-1
Device presentationPreassembled with reversing power busbar
Poles description3P
Power pole contact composition3 NO
System Voltage690 V AC 50/60 Hz power circuit
[Ie] rated operational current20 A (<= 122 °F (50 °C)) at <= 440 V AC AC-1 power circuit
Motor power kW3 kW at 220...230 V AC 50/60 Hz
Control circuit typeAC 50/60 Hz
[Uc] control circuit voltage24 V AC 50/60 Hz
Auxiliary contact composition1 NO
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
Resistive load
AC-3
AC-4
<= 690 V AC 50/60 Hz signalling circuit
16 A (<= 158 °F (70 °C)) at 690 V AC AC-1 power circuit
12 A at <= 440 V AC AC-3 power circuit
4 kW at 480 V AC 50/60 Hz
4 kW at 500...600 V AC 50/60 Hz
4 kW at 660...690 V AC 50/60 Hz
5.5 kW at 380...415 V AC 50/60 Hz
5.5 kW at 440 V AC 50/60 Hz
May 2, 2019
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Page 2
[Ith] conventional free air thermal
current
Irms rated making capacity144 A at 690 V AC power circuit conforming to IEC 60947
Rated breaking capacity110 A at 440 V conforming to IEC 60947
[Icw] rated short-time withstand current25 A <= 122 °F (50 °C) >= 15 min power circuit
Associated fuse rating25 A gG at <= 440 V power circuit
Average impedance3 mOhm at 50 Hz - Ith 20 A power circuit
[Ui] rated insulation voltage690 V signalling circuit conforming to IEC 60947-4-1
Electrical durability0.3 Mcycles 20 A AC-1 at Ue <= 440 V
Tightening torque11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver Philips No 2
Operating time10...20 ms coil de-energisation and NO opening
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability5 Mcycles
Operating rate3600 cyc/h
20 A at <= 122 °F (50 °C) power circuit
10 A at <= 122 °F (50 °C) signalling circuit
144 A at 690 V AC power circuit conforming to NF C 63-110
110 A AC signalling circuit conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
80 A 1 s signalling circuit
90 A 500 ms signalling circuit
110 A 100 ms signalling circuit
115 A <= 122 °F (50 °C) 1 s power circuit
105 A <= 122 °F (50 °C) 5 s power circuit
100 A <= 122 °F (50 °C) 10 s power circuit
75 A <= 122 °F (50 °C) 30 s power circuit
55 A <= 122 °F (50 °C) 1 min power circuit
50 A <= 122 °F (50 °C) 3 min power circuit
25 A aM power circuit
10 A gG signalling circuit conforming to IEC 60947
10 A gG signalling circuit conforming to VDE 0660
690 V signalling circuit conforming to IEC 60947-5-1
600 V signalling circuit conforming to UL 508
600 V power circuit conforming to CSA C22.2 No 14
600 V signalling circuit conforming to CSA C22.2 No 14
690 V power circuit conforming to IEC 60947-4-1
600 V power circuit conforming to UL 508
11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
10...20 ms coil energisation and NO closing
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Complementary
Control circuit voltage limits0.2...0.75 Uc at <= 122 °F (50 °C) drop-out
Inrush power in VA30 VA at 68 °F (20 °C)
Hold-in power consumption in VA4.5 VA at 68 °F (20 °C)
Heat dissipation1.3 W
Auxiliary contacts typeType instantaneous 1 NO
2
0.8...1.15 Uc at <= 122 °F (50 °C) operational
Page 3
Signalling circuit frequency<= 400 Hz
Minimum switching current5 mA signalling circuit
Minimum switching voltage17 V signalling circuit
Non overlap distance0.02 in (0.5 mm)
Insulation resistance> 10 MOhm signalling circuit
Environment
IP degree of protectionIP20 conforming to VDE 0106
Protective treatmentTC conforming to IEC 60068
Ambient air temperature for operation-13...122 °F (-25...50 °C)
Ambient air temperature for storage-58...176 °F (-50...80 °C)
Operating altitude6561.68 ft (2000 m) without derating
Flame retardanceV1 conforming to UL 94
Mechanical robustnessShocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
Height2.28 in (58 mm)
Width3.54 in (90 mm)
Depth2.24 in (57 mm)
Product weight0.86 lb(US) (0.39 kg)
TC conforming to DIN 50016
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
Ordering and shipping details
Category22327 - CTR,K-LINE,AC,OPEN,REV
Discount ScheduleI12
GTIN00785901789895
Nbr. of units in pkg.1
Package weight(Lbs)0.80000000000000004
ReturnabilityY
Country of originFR
Offer Sustainability
Sustainable offer statusGreen Premium product
RoHS (date code: YYWW)Compliant - since 0706 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REAChReference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profileAvailable
Product end of life instructionsAvailable
California proposition 65WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer.
- - - - - - - More informationFor more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period18 months
3