Square D LC2D65AF7 Data Sheet

Page 1
Product data sheet
Characteristics
LC2D65AF7
TeSys D reversing contactor - 3P(3 NO) - AC-3 ­<= 440 V 65 A - 110 V AC coil
Range of product TeSys D
Range TeSys
Product name TeSys D
Product or component type Reversing contactor
Device short name LC2D
Contactor application Resistive load
Utilisation category AC-1
Device presentation Preassembled with reversing power busbar
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage <= 300 V DC for power circuit
[Ie] rated operational current 80 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
Motor power kW 30 kW at 380...400 V AC 50/60 Hz
Motor power hp 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
Control circuit type AC 50/60 Hz
[Uc] control circuit voltage 110 V AC 50/60 Hz
Auxiliary contact composition 1 NO + 1 NC
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Motor control
AC-3
<= 690 V AC 25...400 Hz for power circuit
65 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
37 kW at 500 V AC 50/60 Hz 37 kW at 660...690 V AC 50/60 Hz
18.5 kW at 220...230 V AC 50/60 Hz 37 kW at 415...440 V AC 50/60 Hz
5 hp at 115 V AC 50/60 Hz for 1 phase motors 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors 20 hp at 230/240 V AC 50/60 Hz for 3 phases motors 50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Sep 22, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Page 2
Overvoltage category III
[Ith] conventional free air thermal current
Irms rated making capacity 1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 100 A 1 s signalling circuit
Associated fuse rating 125 A gG at <= 690 V coordination type 1 for power circuit
Average impedance At 50 Hz - Ith 80 A for power circuit
[Ui] rated insulation voltage 600 V for power circuit certifications CSA
Electrical durability 1.45 Mcycles 65 A AC-3 at Ue <= 440 V
Power dissipation per pole 6.3 W AC-3
Protective cover With
Interlocking type Mechanical
Mounting support Rail
Standards CSA C22.2 No 14
Product certifications GOST
Connections - terminals Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
Tightening torque Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Operating time 12...26 ms closing
80 A at <= 60 °C for power circuit 10 A at <= 60 °C for signalling circuit
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1
120 A 500 ms signalling circuit 140 A 100 ms signalling circuit 520 A <= 40 °C 10 s power circuit 900 A <= 40 °C 1 s power circuit 110 A <= 40 °C 10 min power circuit 260 A <= 40 °C 1 min power circuit
125 A gG at <= 690 V coordination type 2 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for power circuit certifications UL 690 V for power circuit conforming to IEC 60947-4-1 690 V for signalling circuit conforming to IEC 60947-1 600 V for signalling circuit certifications CSA 600 V for signalling circuit certifications UL
1.4 Mcycles 80 A AC-1 at Ue <= 440 V
9.6 W AC-1
Plate
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
CCC CSA UL
end Power circuit : EverLink BTR screw connectors 1 cable(s) 1...35 mm² - cable stiffness: flexible ­without cable end Power circuit : EverLink BTR screw connectors 1 cable(s) 1...35 mm² - cable stiffness: flexible - with cable end Power circuit : EverLink BTR screw connectors 1 cable(s) 1...35 mm² - cable stiffness: solid - without cable end Power circuit : EverLink BTR screw connectors 2 cable(s) 1...25 mm² - cable stiffness: flexible ­without cable end Power circuit : EverLink BTR screw connectors 2 cable(s) 1...25 mm² - cable stiffness: flexible - with cable end Power circuit : EverLink BTR screw connectors 2 cable(s) 1...25 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit : 8 N.m - on EverLink BTR screw connectors - cable 25...35 mm² hexagonal 4 mm Power circuit : 5 N.m - on EverLink BTR screw connectors - cable 1...25 mm² hexagonal 4 mm
2
Page 3
4...19 ms opening
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability 6 Mcycles
Operating rate 3600 cyc/h at <= 60 °C
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
Inrush power in VA 140 VA at 20 °C (cos ϕ 0.75) 60 Hz
Hold-in power consumption in VA 13 VA at 20 °C (cos ϕ 0.3) 60 Hz
Heat dissipation 4...5 W at 50/60 Hz
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V Signalling circuit
Non-overlap time 1.5 ms on de-energisation (between NC and NO contact)
Insulation resistance > 10 MOhm for signalling circuit
Power range 15...25 kW 200...240 V 3 phases
Motor starter type Reversing contactor
Contactor coil voltage 110 V AC standard
0.8...1.1 Uc operational at 60 °C, AC 50 Hz
0.85...1.1 Uc operational at 60 °C, AC 60 Hz
160 VA at 20 °C (cos ϕ 0.75) 50 Hz
15 VA at 20 °C (cos ϕ 0.3) 50 Hz
Type mirror contact (1 NC) conforming to IEC 60947-4-1
1.5 ms on energisation (between NC and NO contact)
30...50 kW 380...440 V 3 phases
30...50 kW 480...500 V 3 phases
Environment
IP degree of protection IP20 front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -5...60 °C
Ambient air temperature for storage -60...80 °C
Permissible ambient air temperature around the device
Operating altitude 3000 m without derating in temperature
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz
Height 122 mm
Width 119 mm
Depth 120 mm
Product weight 1.89 kg
-40...70 °C at Uc
Vibrations contactor closed 4 Gn, 5...300 Hz Shocks contactor open 10 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms
Contractual warranty
Warranty period 18 months
3
Page 4
Product data sheet
Dimensions Drawings
Dimensions
LC2D65AF7
4
Page 5
Product data sheet
Connections and Schema
Wiring
LC2D65AF7
5
Page 6
Product data sheet
LC2D65AF7
Motor Starter BOM
Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power 30 kW and 415 VAC
Motor power
(kW)
30 50
Non contractual pictures.
Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.
ICU
(kA)
Breaker Contactor (*)
GV3P65 LC2D65AF7
6