Square D LC2D12F7 Data Sheet

Page 1
Product data sheet
Characteristics
LC2D12F7
REVERSING CONTACTOR 575VAC 12A IEC
Main
Range TeSys
Product or component type Reversing contactor
Device short name LC2D
Contactor application Resistive load
Utilisation category AC-1
Device presentation Preassembled with reversing power busbar
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage <= 300 V DC for power circuit
[Ie] rated operational current 12 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
Motor power kW 3 kW at 220...230 V AC 50/60 Hz
Motor power hp 1 hp at 115 V AC 50/60 Hz for 1 phase motors
Control circuit type AC 50/60 Hz
[Uc] control circuit voltage 110 V AC 50/60 Hz
Auxiliary contact composition 1 NO + 1 NC
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Overvoltage category III
Motor control
AC-3
<= 690 V AC 25...400 Hz for power circuit
25 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
7.5 kW at 500 V AC 50/60 Hz
7.5 kW at 660...690 V AC 50/60 Hz
5.5 kW at 380...400 V AC 50/60 Hz
5.5 kW at 415...440 V AC 50/60 Hz
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors 3 hp at 200/208 V AC 50/60 Hz for 3 phases motors 3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Sep 22, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Page 2
[Ith] conventional free air thermal current
Irms rated making capacity 250 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 105 A <= 40 °C 10 s power circuit
Associated fuse rating 25 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5 mOhm at 50 Hz - Ith 25 A for power circuit
[Ui] rated insulation voltage 600 V for power circuit certifications CSA
Electrical durability 2 Mcycles 12 A AC-3 at Ue <= 440 V
Power dissipation per pole 0.36 W AC-3
Protective cover With
Interlocking type Mechanical
Mounting support Rail
Standards CSA C22.2 No 14
Product certifications LROS (Lloyds register of shipping)
Connections - terminals Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
Tightening torque Power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Operating time 4...19 ms opening
25 A at <= 60 °C for power circuit 10 A at <= 60 °C for signalling circuit
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1
210 A <= 40 °C 1 s power circuit 30 A <= 40 °C 10 min power circuit 61 A <= 40 °C 1 min power circuit 100 A 1 s signalling circuit 120 A 500 ms signalling circuit 140 A 100 ms signalling circuit
40 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for power circuit certifications UL 690 V for power circuit conforming to IEC 60947-4-1 690 V for signalling circuit conforming to IEC 60947-1 600 V for signalling circuit certifications CSA 600 V for signalling circuit certifications UL
0.8 Mcycles 25 A AC-1 at Ue <= 440 V
1.56 W AC-1
Plate
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
GL UL CSA DNV RINA CCC BV GOST
end Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Power circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Power circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
12...22 ms closing
2
Page 3
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability 15 Mcycles
Operating rate 3600 cyc/h at <= 60 °C
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
Inrush power in VA 70 VA at 20 °C (cos ϕ 0.75) 60 Hz
Hold-in power consumption in VA 7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
Heat dissipation 2...3 W at 50/60 Hz
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V Signalling circuit
Non-overlap time 1.5 ms on de-energisation (between NC and NO contact)
Insulation resistance > 10 MOhm for signalling circuit
Power range 2.2...3 kW 200...240 V 3 phases
Motor starter type Reversing contactor
Contactor coil voltage 110 V AC standard
0.8...1.1 Uc operational at 60 °C, AC 50 Hz
0.85...1.1 Uc operational at 60 °C, AC 60 Hz
70 VA at 20 °C (cos ϕ 0.75) 50 Hz
7 VA at 20 °C (cos ϕ 0.3) 50 Hz
Type mirror contact (1 NC) conforming to IEC 60947-4-1
1.5 ms on energisation (between NC and NO contact)
4...6 kW 380...440 V 3 phases
4...6 kW 480...500 V 3 phases
Environment
IP degree of protection IP20 front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -20...60 °C
Ambient air temperature for storage -60...80 °C
Permissible ambient air temperature around the device
Operating altitude 3000 m without derating in temperature
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz
Height 77 mm
Width 90 mm
Depth 86 mm
Product weight 0.697 kg
-40...70 °C at Uc
Vibrations contactor closed 4 Gn, 5...300 Hz Shocks contactor open 10 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0627 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
3
Page 4
Product environmental
Product end of life instructions Available
End of life manual
Contractual warranty
Warranty period 18 months
4
Page 5
Product data sheet
Dimensions Drawings
Dimensions
LC2D12F7
LC2 or 2 x LC1 a b
D09 to D18 (AC) 90 77 86 4 1.5 80
D093 to D123 (AC) 90 99 86 80
D09 to D18 (DC) 90 77 95 4 1.5 80
D093 to D123 (DC) 90 99 95 80
D25 to D38 (AC) 90 85 92 9 5 80
D183 to D383 (AC) 90 99 92 80
D25 to D32 (DC) 90 85 101 9 5 80
D183 to D383 (DC) 90 99 101 80
e1 and e2: including cabling.
(1) With safety cover, without add-on block.
(1)
c
e1 e2 G
5
Page 6
Product data sheet
Connections and Schema
Wiring
LC2D12F7
6
Page 7
Product data sheet
LC2D12F7
Motor Starter BOM
Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power 5,5 kW and 415 VAC
Motor power
(kW)
5.5 15
Non contractual pictures.
Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.
ICU
(kA)
Breaker Contactor (*)
GV2ME16 LC2D12F7