Device presentationPreassembled with reversing power busbar
Poles description3P
Pole contact composition3 NO
[Ue] rated operational voltage<= 300 V DC for power circuit
[Ie] rated operational current200 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
Motor power kW30 kW at 220...230 V AC 50/60 Hz
Motor power hp30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
Control circuit typeAC 50/60 Hz
[Uc] control circuit voltage120 V AC 50/60 Hz
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947
Overvoltage categoryIII
[Ith] conventional free air thermal
current
Irms rated making capacity1260 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
Feb 22, 2018
Resistive load
AC-3
<= 1000 V AC 25...400 Hz for power circuit
115 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
55 kW at 380...400 V AC 50/60 Hz
65 kW at 1000 V AC 50/60 Hz
75 kW at 500 V AC 50/60 Hz
80 kW at 660...690 V AC 50/60 Hz
59 kW at 415...440 V AC 50/60 Hz
40 hp at 230/240 V AC 50/60 Hz for 3 phases motors
75 hp at 460/480 V AC 50/60 Hz for 3 phases motors
100 hp at 575/600 V AC 50/60 Hz for 3 phases motors
200 A at <= 60 °C for power circuit
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Page 2
[Icw] rated short-time withstand current1100 A <= 40 °C 1 s power circuit
Associated fuse rating200 A gG at <= 690 V coordination type 2 for power circuit
Average impedance0.6 mOhm at 50 Hz - Ith 200 A for power circuit
[Ui] rated insulation voltage1000 V for power circuit conforming to IEC 60947-4-1
Electrical durability0.95 Mcycles 115 A AC-3 <= 440 V
Tightening torqueControl circuit : 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Operating time6...20 ms opening
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability8000000 cycles
Operating rate2400 cyc/h at <= 60 °C
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
250 A <= 40 °C 10 min power circuit
550 A <= 40 °C 1 min power circuit
950 A <= 40 °C 10 s power circuit
250 A gG at <= 690 V coordination type 1 for power circuit
10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for power circuit certifications CSA
600 V for power circuit certifications UL
690 V for signalling circuit conforming to IEC 60947-1
600 V for signalling circuit certifications CSA
600 V for signalling circuit certifications UL
0.8 Mcycles 200 A AC-1 <= 440 V
7.9 W AC-3
Mechanical
Rail
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA
CCC
EAC
GL
BV
DNV
RINA
end
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
end
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: solid - without cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...2.5 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...2.5 mm² - cable stiffness: solid - without cable
end
Power circuit : connector 1 cable(s) 10...120 mm² - cable stiffness: flexible - without cable end
Power circuit : connector 2 cable(s) 10...50 mm² - cable stiffness: flexible - without cable end
Power circuit : connector 1 cable(s) 10...120 mm² - cable stiffness: flexible - with cable end
Power circuit : connector 2 cable(s) 10...50 mm² - cable stiffness: flexible - with cable end
Power circuit : connector 1 cable(s) 10...120 mm² - cable stiffness: solid - without cable end
Power circuit : connector 2 cable(s) 10...50 mm² - cable stiffness: solid - without cable end
Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit : 12 N.m - on connector hexagonal 4 mm
20...50 ms closing
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1