TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V
80 A - 24 V DC standard coil
Main
Range of productTeSys D
RangeTeSys
Product nameTeSys D
Product or component typeContactor
Device short nameLC1D
Contactor applicationResistive load
Utilisation categoryAC-4
Poles description3P
Pole contact composition3 NO
[Ue] rated operational voltage<= 690 V AC for power circuit
[Ie] rated operational current125 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
Motor power kW22 kW at 220...230 V AC 50/60 Hz AC-3
Motor power hp20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
Control circuit typeDC standard
[Uc] control circuit voltage24 V DC
Auxiliary contact composition1 NO + 1 NC
Motor control
AC-3
AC-1
<= 300 V DC 25...400 Hz for power circuit
80 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
37 kW at 380...400 V AC 50/60 Hz AC-3
45 kW at 660...690 V AC 50/60 Hz AC-3
45 kW at 415...440 V AC 50/60 Hz AC-3
55 kW at 500 V AC 50/60 Hz AC-3
45 kW at 1000 V AC 50/60 Hz AC-3
15 kW at 400 V AC 50/60 Hz AC-4
7.5 hp at 115 V AC 50/60 Hz for 1 phase motors
15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
25 hp at 230/240 V AC 50/60 Hz for 3 phases motors
60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
60 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Sep 20, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Page 2
[Uimp] rated impulse withstand voltageConforming to IEC 60947
Overvoltage categoryIII
[Ith] conventional free air thermal
current
Irms rated making capacity1100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current135 A <= 40 °C 10 min power circuit
Associated fuse rating160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance0.8 mOhm at 50 Hz - Ith 125 A for power circuit
[Ui] rated insulation voltage1000 V for power circuit conforming to IEC 60947-4-1
Electrical durability0.8 Mcycles 125 A AC-1 at Ue <= 440 V
Tightening torquePower circuit : 9 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
Operating time20...35 ms opening
125 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
640 A <= 40 °C 10 s power circuit
990 A <= 40 °C 1 s power circuit
320 A <= 40 °C 1 min power circuit
200 A gG at <= 690 V coordination type 1 for power circuit
10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for power circuit certifications CSA
600 V for power circuit certifications UL
690 V for signalling circuit conforming to IEC 60947-1
600 V for signalling circuit certifications CSA
600 V for signalling circuit certifications UL
1.5 Mcycles 80 A AC-3 at Ue <= 440 V
12.5 W AC-1
Rail
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
LROS (Lloyds register of shipping)
GL
CSA
UL
CCC
RINA
BV
GOST
end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Control circuit : screw clamp terminals 1 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
end
Power circuit : connector 1 cable(s) 4...50 mm² - cable stiffness: flexible - without cable end
Power circuit : connector 2 cable(s) 4...25 mm² - cable stiffness: flexible - without cable end
Power circuit : connector 1 cable(s) 4...50 mm² - cable stiffness: flexible - with cable end
Power circuit : connector 2 cable(s) 4...16 mm² - cable stiffness: flexible - with cable end
Power circuit : connector 1 cable(s) 4...50 mm² - cable stiffness: solid - without cable end
Power circuit : connector 2 cable(s) 4...25 mm² - cable stiffness: solid - without cable end
Power circuit : 9 N.m - on connector hexagonal 4 mm
Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
2
Page 3
95...130 ms closing
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability4 Mcycles
Operating rate3600 cyc/h at <= 60 °C
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Complementary
Coil technologyWithout built-in suppressor module
Control circuit voltage limits0.1...0.3 Uc drop-out at 55 °C, DC
Time constant75 ms
Inrush power in W22 W at 20 °C
Hold-in power consumption in W22 W at 20 °C
Auxiliary contacts typeType mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency25...400 Hz
Minimum switching current5 mA for signalling circuit
Minimum switching voltage17 V for signalling circuit
Non-overlap time1.5 ms on de-energisation (between NC and NO contact)
Insulation resistance> 10 MOhm for signalling circuit
Power range15...25 kW 200...240 V 3 phases
Motor starter typeDirect on-line contactor
Contactor coil voltage24 V DC standard
0.85...1.1 Uc operational at 55 °C, DC
Type mirror contact (1 NC) conforming to IEC 60947-4-1
1.5 ms on energisation (between NC and NO contact)
30...50 kW 380...440 V 3 phases
30...50 kW 480...500 V 3 phases
55...100 kW 480...500 V 3 phases
Environment
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068-2-30
Pollution degree3
Ambient air temperature for operation-5...60 °C
Ambient air temperature for storage-60...80 °C
Permissible ambient air temperature
around the device
Operating altitude3000 m without derating in temperature
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Mechanical robustnessVibrations contactor open 2 Gn, 5...300 Hz
Height127 mm
Width85 mm
Depth186 mm
Product weight2.59 kg
-40...70 °C at Uc
Shocks contactor open 8 Gn for 11 ms
Vibrations contactor closed 3 Gn, 5...300 Hz
Shocks contactor closed 10 Gn for 11 ms
Offer Sustainability
Sustainable offer statusGreen Premium product
RoHS (date code: YYWW)Compliant - since 0706 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REAChReference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profileAvailable
3
Page 4
Product environmental
Product end of life instructionsNeed no specific recycling operations
Contractual warranty
Warranty period18 months
4
Page 5
Product data sheet
LC1D80BD
Dimensions Drawings
Dimensions
(1)Minimum electrical clearance
LC1D80 and D95
a85
b1with LAD 4BB3–
with LA4 DF, DT –
cwithout cover or add-on blocks181
with cover, without add-on blocks186
c1with LAD N (1 contact)204
with LAD N or C ( or 4 contacts)210
c2with LA6 DK10221
c3with LAD T, R, S229
with LAD T, R, S and sealing cover233
5
Page 6
Product data sheet
Connections and Schema
Wiring
LC1D80BD
6
Page 7
Product data sheet
LC1D80BD
Motor Starter BOM
Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power 37 kW and 415 VAC
Motor power
(kW)
3736
3715
Non contractual pictures.
Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and
must not be able to resume operation without repair or the replacement of parts.
ICU
(kA)
BreakerContactor (*)
GV7RE80LC1D80BD
GV3ME80LC1D80BD
7