Square D LC1D80BD Data Sheet

Page 1
Product data sheet
Characteristics
LC1D80BD
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A - 24 V DC standard coil
Range of product TeSys D
Range TeSys
Product name TeSys D
Product or component type Contactor
Device short name LC1D
Contactor application Resistive load
Utilisation category AC-4
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage <= 690 V AC for power circuit
[Ie] rated operational current 125 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
Motor power kW 22 kW at 220...230 V AC 50/60 Hz AC-3
Motor power hp 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
Control circuit type DC standard
[Uc] control circuit voltage 24 V DC
Auxiliary contact composition 1 NO + 1 NC
Motor control
AC-3 AC-1
<= 300 V DC 25...400 Hz for power circuit
80 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
37 kW at 380...400 V AC 50/60 Hz AC-3 45 kW at 660...690 V AC 50/60 Hz AC-3 45 kW at 415...440 V AC 50/60 Hz AC-3 55 kW at 500 V AC 50/60 Hz AC-3 45 kW at 1000 V AC 50/60 Hz AC-3 15 kW at 400 V AC 50/60 Hz AC-4
7.5 hp at 115 V AC 50/60 Hz for 1 phase motors 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors 25 hp at 230/240 V AC 50/60 Hz for 3 phases motors 60 hp at 460/480 V AC 50/60 Hz for 3 phases motors 60 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Sep 20, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Page 2
[Uimp] rated impulse withstand voltage Conforming to IEC 60947
Overvoltage category III
[Ith] conventional free air thermal current
Irms rated making capacity 1100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 135 A <= 40 °C 10 min power circuit
Associated fuse rating 160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 0.8 mOhm at 50 Hz - Ith 125 A for power circuit
[Ui] rated insulation voltage 1000 V for power circuit conforming to IEC 60947-4-1
Electrical durability 0.8 Mcycles 125 A AC-1 at Ue <= 440 V
Power dissipation per pole 5.1 W AC-3
Protective cover With
Mounting support Plate
Standards CSA C22.2 No 14
Product certifications DNV
Connections - terminals Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
Tightening torque Power circuit : 9 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
Operating time 20...35 ms opening
125 A at <= 60 °C for power circuit 10 A at <= 60 °C for signalling circuit
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1
100 A 1 s signalling circuit 120 A 500 ms signalling circuit 140 A 100 ms signalling circuit 640 A <= 40 °C 10 s power circuit 990 A <= 40 °C 1 s power circuit 320 A <= 40 °C 1 min power circuit
200 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for power circuit certifications CSA 600 V for power circuit certifications UL 690 V for signalling circuit conforming to IEC 60947-1 600 V for signalling circuit certifications CSA 600 V for signalling circuit certifications UL
1.5 Mcycles 80 A AC-3 at Ue <= 440 V
12.5 W AC-1
Rail
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
LROS (Lloyds register of shipping) GL CSA UL CCC RINA BV GOST
end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end Power circuit : connector 1 cable(s) 4...50 mm² - cable stiffness: flexible - without cable end Power circuit : connector 2 cable(s) 4...25 mm² - cable stiffness: flexible - without cable end Power circuit : connector 1 cable(s) 4...50 mm² - cable stiffness: flexible - with cable end Power circuit : connector 2 cable(s) 4...16 mm² - cable stiffness: flexible - with cable end Power circuit : connector 1 cable(s) 4...50 mm² - cable stiffness: solid - without cable end Power circuit : connector 2 cable(s) 4...25 mm² - cable stiffness: solid - without cable end
Power circuit : 9 N.m - on connector hexagonal 4 mm Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
2
Page 3
95...130 ms closing
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability 4 Mcycles
Operating rate 3600 cyc/h at <= 60 °C
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.1...0.3 Uc drop-out at 55 °C, DC
Time constant 75 ms
Inrush power in W 22 W at 20 °C
Hold-in power consumption in W 22 W at 20 °C
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 ms on de-energisation (between NC and NO contact)
Insulation resistance > 10 MOhm for signalling circuit
Power range 15...25 kW 200...240 V 3 phases
Motor starter type Direct on-line contactor
Contactor coil voltage 24 V DC standard
0.85...1.1 Uc operational at 55 °C, DC
Type mirror contact (1 NC) conforming to IEC 60947-4-1
1.5 ms on energisation (between NC and NO contact)
30...50 kW 380...440 V 3 phases
30...50 kW 480...500 V 3 phases
55...100 kW 480...500 V 3 phases
Environment
IP degree of protection IP20 front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -5...60 °C
Ambient air temperature for storage -60...80 °C
Permissible ambient air temperature around the device
Operating altitude 3000 m without derating in temperature
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz
Height 127 mm
Width 85 mm
Depth 186 mm
Product weight 2.59 kg
-40...70 °C at Uc
Shocks contactor open 8 Gn for 11 ms Vibrations contactor closed 3 Gn, 5...300 Hz Shocks contactor closed 10 Gn for 11 ms
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0706 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
3
Page 4
Product environmental
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
4
Page 5
Product data sheet
LC1D80BD
Dimensions Drawings
Dimensions
(1) Minimum electrical clearance
LC1 D80 and D95
a 85
b1 with LAD 4BB3
with LA4 DF, DT –
c without cover or add-on blocks 181
with cover, without add-on blocks186
c1 with LAD N (1 contact) 204
with LAD N or C ( or 4 contacts)210
c2 with LA6 DK10 221
c3 with LAD T, R, S 229
with LAD T, R, S and sealing cover233
5
Page 6
Product data sheet
Connections and Schema
Wiring
LC1D80BD
6
Page 7
Product data sheet
LC1D80BD
Motor Starter BOM
Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power 37 kW and 415 VAC
Motor power
(kW)
37 36
37 15
Non contractual pictures.
Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.
ICU
(kA)
Breaker Contactor (*)
GV7RE80 LC1D80BD
GV3ME80 LC1D80BD
7
Loading...