Square D LC1D50AB7 Data Sheet

Page 1
Product data sheet
Characteristics
LC1D50AB7
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A - 24 V AC 50/60 Hz coil
Range of product TeSys D
Range TeSys
Product name TeSys D
Product or component type Contactor
Device short name LC1D
Contactor application Resistive load
Utilisation category AC-1
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage <= 300 V DC for power circuit
[Ie] rated operational current 50 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
Motor power kW 22 kW at 380...400 V AC 50/60 Hz AC-3
Motor power hp 3 hp at 115 V AC 50/60 Hz for 1 phase motors
Control circuit type AC 50/60 Hz
[Uc] control circuit voltage 24 V AC 50/60 Hz
Auxiliary contact composition 1 NO + 1 NC
Motor control
AC-4 AC-3
<= 690 V AC 25...400 Hz for power circuit
80 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
25 kW at 415 V AC 50/60 Hz AC-3 30 kW at 440 V AC 50/60 Hz AC-3 30 kW at 500 V AC 50/60 Hz AC-3 33 kW at 660...690 V AC 50/60 Hz AC-3 15 kW at 220...230 V AC 50/60 Hz AC-3 11 kW at 400 V AC 50/60 Hz AC-4
7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors 15 hp at 200/208 V AC 50/60 Hz for 3 phases motors 15 hp at 230/240 V AC 50/60 Hz for 3 phases motors 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors 40 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Sep 15, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Page 2
[Uimp] rated impulse withstand voltage Conforming to IEC 60947
Overvoltage category III
[Ith] conventional free air thermal current
Irms rated making capacity 900 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 900 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 100 A 1 s signalling circuit
Associated fuse rating 100 A gG at <= 690 V coordination type 1 for power circuit
Average impedance 1.5 mOhm at 50 Hz - Ith 80 A for power circuit
[Ui] rated insulation voltage 600 V for power circuit certifications CSA
Electrical durability 1.45 Mcycles 50 A AC-3 at Ue <= 440 V
Power dissipation per pole 3.7 W AC-3
Protective cover With
Mounting support Plate
Standards CSA C22.2 No 14
Product certifications GOST
Connections - terminals Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
Tightening torque Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Operating time 12...26 ms closing
80 A at <= 60 °C for power circuit 10 A at <= 60 °C for signalling circuit
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1
120 A 500 ms signalling circuit 140 A 100 ms signalling circuit 400 A <= 40 °C 10 s power circuit 810 A <= 40 °C 1 s power circuit 84 A <= 40 °C 10 min power circuit 208 A <= 40 °C 1 min power circuit
100 A gG at <= 690 V coordination type 2 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for power circuit certifications UL 690 V for power circuit conforming to IEC 60947-4-1 690 V for signalling circuit conforming to IEC 60947-1 600 V for signalling circuit certifications CSA 600 V for signalling circuit certifications UL
1.1 Mcycles 80 A AC-1 at Ue <= 440 V
9.6 W AC-1
Rail
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
CSA CCC RINA GL UL DNV BV LROS (Lloyds register of shipping)
end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Power circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: flexible - with cable end Power circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: solid - without cable end Power circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: flexible - without cable end Power circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: solid - without cable end Power circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: flexible - without cable end Power circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: flexible - with cable end
Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit : 8 N.m - on EverLink BTR screw connectors - cable 25...35 mm² hexagonal 4 mm Power circuit : 5 N.m - on EverLink BTR screw connectors - cable 1...25 mm² hexagonal 4 mm
4...19 ms opening
2
Page 3
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability 6 Mcycles
Operating rate 3600 cyc/h at <= 60 °C
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
Inrush power in VA 140 VA at 20 °C (cos ϕ 0.75) 60 Hz
Hold-in power consumption in VA 13 VA at 20 °C (cos ϕ 0.3) 60 Hz
Heat dissipation 4...5 W at 50/60 Hz
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 ms on de-energisation (between NC and NO contact)
Insulation resistance > 10 MOhm for signalling circuit
Power range 7...11 kW 200...240 V 3 phases
Motor starter type Direct on-line contactor
Contactor coil voltage 24 V AC standard
0.8...1.1 Uc operational at 60 °C, AC 50 Hz
0.85...1.1 Uc operational at 60 °C, AC 60 Hz
160 VA at 20 °C (cos ϕ 0.75) 50 Hz
15 VA at 20 °C (cos ϕ 0.3) 50 Hz
Type mirror contact (1 NC) conforming to IEC 60947-4-1
1.5 ms on energisation (between NC and NO contact)
15...25 kW 200...240 V 3 phases
15...25 kW 380...440 V 3 phases
30...50 kW 380...440 V 3 phases
30...50 kW 480...500 V 3 phases
Environment
IP degree of protection IP20 front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -5...60 °C
Ambient air temperature for storage -60...80 °C
Permissible ambient air temperature around the device
Operating altitude 3000 m without derating in temperature
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz
Height 122 mm
Width 55 mm
Depth 120 mm
Product weight 0.855 kg
-40...70 °C at Uc
Vibrations contactor closed 4 Gn, 5...300 Hz Shocks contactor open 10 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0001 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
3
Page 4
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Available
End of life manual
Contractual warranty
Warranty period 18 months
4
Page 5
Product data sheet
LC1D50AB7
Dimensions Drawings
Dimensions
(1) Minimum electrical clearance
LC1 D40A…D65A
a 55
b1 with LA4 D●2
with LA4 DB3 or LAD 4BB3136
with LA4 DF, DT 157
with LA4 DM, DW, DL166
c without cover or add-on blocks 118
with cover, without add-on blocks120
c1 with LAD N (1 contact)
with LAD N or C (2 or 4 contacts)150
c2 with LA6 DK10, LAD 6DK 163
c3 with LAD T, R, S 171
with LAD T, R, S and sealing cover175
5
Page 6
Product data sheet
Connections and Schema
Wiring
LC1D50AB7
6
Page 7
Product data sheet
LC1D50AB7
Motor Starter BOM
Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power 22 kW and 415 VAC
Motor power
(kW)
22 50
Non contractual pictures.
Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.
ICU
(kA)
Breaker Contactor (*)
GV3P50 LC1D50AB7
7