Product data sheet
Characteristics
LC1D40AG7
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V
40 A - 120 V AC 50/60 Hz coil
Main
Range of product TeSys D
Range TeSys
Product name TeSys D
Product or component type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-3
AC-1
AC-4
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage <= 300 V DC for power circuit
<= 690 V AC 25...400 Hz for power circuit
[Ie] rated operational current 40 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
60 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
Motor power kW 18.5 kW at 380...400 V AC 50/60 Hz AC-3
22 kW at 500 V AC 50/60 Hz AC-3
30 kW at 660...690 V AC 50/60 Hz AC-3
11 kW at 220...230 V AC 50/60 Hz AC-3
9 kW at 400 V AC 50/60 Hz AC-4
22 kW at 415...440 V AC 50/60 Hz AC-3
Motor power hp 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
30 hp at 575/600 V AC 50/60 Hz for 3 phases motors
3 hp at 115 V AC 50/60 Hz for 1 phase motors
10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
30 hp at 460/480 V AC 50/60 Hz for 3 phases motors
Control circuit type AC 50/60 Hz
[Uc] control circuit voltage 120 V AC 50/60 Hz
Auxiliary contact composition 1 NO + 1 NC
[Uimp] rated impulse withstand voltage Conforming to IEC 60947
Sep 14, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1

Overvoltage category III
[Ith] conventional free air thermal
current
Irms rated making capacity 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 100 A 1 s signalling circuit
Associated fuse rating 80 A gG at <= 690 V coordination type 1 for power circuit
Average impedance 1.5 mOhm at 50 Hz - Ith 60 A for power circuit
[Ui] rated insulation voltage 600 V for power circuit certifications CSA
Electrical durability 1.5 Mcycles 40 A AC-3 at Ue <= 440 V
Power dissipation per pole 5.4 W AC-1
Protective cover With
Mounting support Plate
Standards CSA C22.2 No 14
Product certifications CCC
Connections - terminals Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
Tightening torque Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Operating time 12...26 ms closing
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability 6 Mcycles
Operating rate 3600 cyc/h at <= 60 °C
60 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
320 A <= 40 °C 10 s power circuit
720 A <= 40 °C 1 s power circuit
72 A <= 40 °C 10 min power circuit
165 A <= 40 °C 1 min power circuit
80 A gG at <= 690 V coordination type 2 for power circuit
10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for power circuit certifications UL
690 V for power circuit conforming to IEC 60947-4-1
690 V for signalling circuit conforming to IEC 60947-1
600 V for signalling circuit certifications CSA
600 V for signalling circuit certifications UL
1.4 Mcycles 60 A AC-1 at Ue <= 440 V
2.4 W AC-3
Rail
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
UL
GOST
CSA
end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Power circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: flexible - with cable end
Power circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: solid - without cable end
Power circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: flexible - without cable end
Power circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: solid - without cable end
Power circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: flexible - without cable end
Power circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: flexible - with cable end
Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit : 8 N.m - on EverLink BTR screw connectors - cable 25...35 mm² hexagonal 4 mm
Power circuit : 5 N.m - on EverLink BTR screw connectors - cable 1...25 mm² hexagonal 4 mm
4...19 ms opening
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
2

Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
Inrush power in VA 140 VA at 20 °C (cos ϕ 0.75) 60 Hz
Hold-in power consumption in VA 13 VA at 20 °C (cos ϕ 0.3) 60 Hz
Heat dissipation 4...5 W at 50/60 Hz
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 ms on de-energisation (between NC and NO contact)
Insulation resistance > 10 MOhm for signalling circuit
0.8...1.1 Uc operational at 60 °C, AC 50 Hz
0.85...1.1 Uc operational at 60 °C, AC 60 Hz
160 VA at 20 °C (cos ϕ 0.75) 50 Hz
15 VA at 20 °C (cos ϕ 0.3) 50 Hz
Type mirror contact (1 NC) conforming to IEC 60947-4-1
1.5 ms on energisation (between NC and NO contact)
Environment
IP degree of protection IP20 front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -5...60 °C
Ambient air temperature for storage -60...80 °C
Permissible ambient air temperature
around the device
Operating altitude 3000 m without derating in temperature
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz
Height 122 mm
Width 55 mm
Depth 120 mm
Product weight 0.85 kg
-40...70 °C at Uc
Vibrations contactor closed 4 Gn, 5...300 Hz
Shocks contactor open 10 Gn for 11 ms
Shocks contactor closed 15 Gn for 11 ms
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0001 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Available
End of life manual
Contractual warranty
Warranty period 18 months
3