Square D LC1D25BL Data Sheet

Page 1
Product data sheet
Characteristics
LC1D25BL
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 24 V DC coil
Range of product TeSys D
Range TeSys
Product name TeSys D
Product or component type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-1
AC-4 AC-3
Poles description 3P
Pole contact composition 3 NO
[Ue] rated operational voltage <= 300 V DC for power circuit
<= 690 V AC 25...400 Hz for power circuit
[Ie] rated operational current 25 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
40 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
Motor power kW 11 kW at 380...400 V AC 50/60 Hz AC-3
15 kW at 500 V AC 50/60 Hz AC-3 15 kW at 660...690 V AC 50/60 Hz AC-3
5.5 kW at 220...230 V AC 50/60 Hz AC-3 11 kW at 415...440 V AC 50/60 Hz AC-3
5.5 kW at 400 V AC 50/60 Hz AC-4
Motor power hp 2 hp at 115 V AC 50/60 Hz for 1 phase motors
7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Control circuit type DC low consumption
[Uc] control circuit voltage 24 V DC
Auxiliary contact composition 1 NO + 1 NC
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Sep 13, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Page 2
Overvoltage category III
[Ith] conventional free air thermal current
Irms rated making capacity 450 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 450 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 120 A <= 40 °C 1 min power circuit
Associated fuse rating 40 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2 mOhm at 50 Hz - Ith 40 A for power circuit
[Ui] rated insulation voltage 600 V for power circuit certifications CSA
Electrical durability 1.65 Mcycles 25 A AC-3 at Ue <= 440 V
Power dissipation per pole 3.2 W AC-1
Protective cover With
Mounting support Plate
Standards CSA C22.2 No 14
Product certifications GOST
Connections - terminals Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
Tightening torque Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
40 A at <= 60 °C for power circuit 10 A at <= 60 °C for signalling circuit
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1
240 A <= 40 °C 10 s power circuit 380 A <= 40 °C 1 s power circuit 50 A <= 40 °C 10 min power circuit 100 A 1 s signalling circuit 120 A 500 ms signalling circuit 140 A 100 ms signalling circuit
63 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for power circuit certifications UL 690 V for power circuit conforming to IEC 60947-4-1 690 V for signalling circuit conforming to IEC 60947-1 600 V for signalling circuit certifications CSA 600 V for signalling circuit certifications UL
1.4 Mcycles 40 A AC-1 at Ue <= 440 V
1.25 W AC-3
Rail
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
UL CSA LROS (Lloyds register of shipping) RINA BV CCC DNV GL
end Power circuit : screw clamp terminals 1 cable(s) 1.5...10 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 1 cable(s) 2.5...10 mm² - cable stiffness: flexible - without cable end Power circuit : screw clamp terminals 2 cable(s) 2.5...10 mm² - cable stiffness: flexible - without cable end Power circuit : screw clamp terminals 1 cable(s) 1...10 mm² - cable stiffness: flexible - with cable end Power circuit : screw clamp terminals 2 cable(s) 1.5...6 mm² - cable stiffness: flexible - with cable end Power circuit : screw clamp terminals 2 cable(s) 2.5...10 mm² - cable stiffness: solid - without cable end
Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit : 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit : 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
2
Page 3
Operating time 65.45...88.55 ms closing
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability 30 Mcycles
Operating rate 3600 cyc/h at <= 60 °C
20...30 ms opening
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Complementary
Coil technology Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits 0.1...0.3 Uc drop-out at 60 °C, DC
Time constant 40 ms
Inrush power in W 2.4 W at 20 °C
Hold-in power consumption in W 2.4 W at 20 °C
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 ms on energisation between NC and NO contact
Insulation resistance > 10 MOhm for signalling circuit
Power range 7...11 kW 380...440 V 3 phases
Motor starter type Direct on-line contactor
Contactor coil voltage 24 V DC low consumption
0.8...1.25 Uc operational at 60 °C, DC
Type mirror contact (1 NC) conforming to IEC 60947-4-1
1.5 ms on de-energisation between NC and NO contact
7...11 kW 480...500 V 3 phases
4...6 kW 200...240 V 3 phases
Environment
IP degree of protection IP20 front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -5...60 °C
Ambient air temperature for storage -60...80 °C
Permissible ambient air temperature around the device
Operating altitude 3000 m without derating in temperature
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz
Height 85 mm
Width 45 mm
Depth 101 mm
Product weight 0.53 kg
-40...70 °C at Uc
Vibrations contactor closed 4 Gn, 5...300 Hz Shocks contactor closed 15 Gn for 11 ms Shocks contactor open 8 Gn for 11 ms
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0721 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
3
Page 4
Product environmental
Product end of life instructions Available
End of life manual
Contractual warranty
Warranty period 18 months
4
Page 5
Product data sheet
LC1D25BL
Dimensions Drawings
Dimensions
(1) Minimum electrical clearance
LC1 D25…D38 D183…D323
b 85 99
c without cover or add-on blocks 99 99
with cover, without add-on blocks101 101
c1 with LAD N or C (2 or 4 contacts) 132 132
c2 with LA6 DK10 144 144
c3 with LAD T, R, S 152 152
with LAD T, R, S and sealing cover156 156
5
Page 6
Product data sheet
Connections and Schema
Wiring
LC1D25BL
6
Page 7
Product data sheet
LC1D25BL
Motor Starter BOM
Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power from 9 to 11 kW and 415 VAC
Motor power
(kW)
9 15
11 15
Non contractual pictures.
Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.
ICU
(kA)
Breaker Contactor (*)
GV2ME21 LC1D25BL
GV2ME22 LC1D25BL
7
Loading...