Product data sheet
LC1D258G7
TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 ­<= 440 V 40 A - 120 V AC coil
Oct 26, 2015
1
Page 2
Main
Range TeSys
Product name TeSys D
Product or component type
Device short name LC1D
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
Power pole contact composition
[Ue] rated operational voltage
[Ie] rated operational current
Control circuit type AC 50/60 Hz
Control circuit voltage 120 V AC 50/60 Hz
Auxiliary contact com­position
[Uimp] rated impulse withstand voltage
Overvoltage category III
[Ith] conventional free air thermal current
Irms rated making ca­pacity
Rated breaking capac­ity
[Icw] rated short-time withstand current
Associated fuse rating 40 A gG at <= 690 V coordination type 2 for power
Average impedance 2 mOhm at 50 Hz - Ith 40 A for power circuit
[Ui] rated insulation voltage
Electrical durability 1.4 Mcycles 40 A AC-1 at Ue <= 440 V
Power dissipation per pole
Safety cover With
Mounting support Plate
Standards EN 60947-4-1
Contactor
2 NO + 2 NC
<= 300 V DC for power circuit <= 690 V AC 25...400 Hz for power circuit
40 A (<= 60 °C) at <= 440 V AC AC-1 for power cir­cuit
1 NO + 1 NC
6 kV conforming to IEC 60947
40 A at <= 60 °C for power circuit 10 A at <= 60 °C for signalling circuit
450 A at 440 V for power circuit conforming to IEC 60947 250 A DC for signalling circuit conforming to IEC 60947-5-1 140 A AC for signalling circuit conforming to IEC 60947-5-1
450 A at 440 V for power circuit conforming to IEC 60947
140 A 100 ms signalling circuit 120 A 500 ms signalling circuit 100 A 1 s signalling circuit 120 A <= 40 °C 1 min power circuit 50 A <= 40 °C 10 min power circuit 380 A <= 40 °C 1 s power circuit 240 A <= 40 °C 10 s power circuit
circuit 63 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for signalling circuit certifications UL 600 V for signalling circuit certifications CSA 690 V for signalling circuit conforming to IEC 60947-1 600 V for power circuit certifications UL 600 V for power circuit certifications CSA 690 V for power circuit conforming to IEC 60947-4-1
3.2 W AC-1
Rail
EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
2
Page 3
Product certifications BV
Connections - terminals Power circuit : connector 2 cable(s) 2.5...16 mm² -
Tightening torque Power circuit : 1.8 N.m - on connector - with screw-
Operating time 4...19 ms opening
Safety reliability level B10d = 20000000 cycles contactor with mechanical
Mechanical durability 15 Mcycles
Operating rate 3600 cyc/h at <= 60 °C
CCC CSA DNV GL GOST RINA UL LROS
cable stiffness: solid - without cable end Power circuit : connector 1 cable(s) 2.5...16 mm² ­cable stiffness: solid - without cable end Power circuit : connector 2 cable(s) 2.5...10 mm² ­cable stiffness: flexible - with cable end Power circuit : connector 1 cable(s) 2.5...10 mm² ­cable stiffness: flexible - with cable end Power circuit : connector 2 cable(s) 2.5...10 mm² ­cable stiffness: flexible - without cable end Power circuit : connector 1 cable(s) 2.5...10 mm² ­cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 2 cable(s)
1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 cable(s)
1...2.5 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 2 cable(s)
1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 1 cable(s)
1...4 mm² - cable stiffness: flexible - without cable end
driver Philips No 2 Power circuit : 1.8 N.m - on connector - with screw­driver flat Ø 6 mm Control circuit : 1.7 N.m - on screw clamp terminals ­with screwdriver Philips No 2 Control circuit : 1.7 N.m - on screw clamp terminals ­with screwdriver flat Ø 6 mm
12...22 ms closing
load conforming to EN/ISO 13849-1 B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.85...1.1 Uc at 60 °C operational 60 Hz
0.8...1.1 Uc at 60 °C operational 50 Hz
0.3...0.6 Uc at 60 °C drop-out 50/60 Hz
Inrush power in VA 70 VA at 20 °C (cos ϕ 0.75) 50 Hz
70 VA at 20 °C (cos ϕ 0.75) 60 Hz
Hold-in power consumption in VA 7 VA at 20 °C (cos ϕ 0.3) 50 Hz
7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
Heat dissipation 2...3 W at 50/60 Hz
Auxiliary contacts type Type mirror contact (1 NC) conforming to IEC 60947-4-1
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 ms on energisation (between NC and NO contact)
1.5 ms on de-energisation (between NC and NO contact)
Insulation resistance > 10 MOhm for signalling circuit
3
Page 4
Environment
IP degree of protection IP2x front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -20...60 °C
Ambient air temperature for storage -60...80 °C
Permissible ambient air temperature around the de­vice
Operating altitude 3000 m without derating in temperature
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Shocks contactor open 8 Gn for 11 ms
Height 105 mm
Width 45 mm
Depth 99 mm
Product weight 0.425 kg
-40...70 °C at Uc
Shocks contactor closed 15 Gn for 11 ms Vibrations contactor closed 4 Gn, 5...300 Hz Vibrations contactor open 2 Gn, 5...300 Hz
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW)
REACh Reference not containing SVHC above the threshold
Product environmental profile
Product end of life instructions Need no specific recycling operations
Compliant - since 0702 - Schneider Electric declaration of conformity
Available Download Product Environmental
4