Square D LC1D18M7 Data Sheet

Page 1
Product data sheet
Characteristics
LC1D18M7
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 18 A - 220 V AC coil
Range TeSys
Product name TeSys D
Product or component type Contactor
Device short name LC1D
Contactor application Motor control
Utilisation category AC-1
Poles description 3P
Pole contact composition 3 NO
System Voltage <= 300 V DC power circuit
[Ie] rated operational current 18 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuit
Motor power kW 10 kW at 500 V AC 50/60 Hz
Motor power hp 1 hp at 115 V AC 50/60 Hz 1 phase motors
Control circuit type AC 50/60 Hz
Control circuit voltage 220 V AC 50/60 Hz
Auxiliary contact composition 1 NO + 1 NC
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Overvoltage category III
[Ith] conventional free air thermal current
Feb 06, 2017
Resistive load
AC-3
<= 690 V AC 25...400 Hz power circuit
32 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit
10 kW at 660...690 V AC 50/60 Hz 4 kW at 220...230 V AC 50/60 Hz
7.5 kW at 380...400 V AC 50/60 Hz 9 kW at 415...440 V AC 50/60 Hz
3 hp at 230/240 V AC 50/60 Hz 1 phase motors 5 hp at 200/208 V AC 50/60 Hz 3 phases motors 5 hp at 230/240 V AC 50/60 Hz 3 phases motors 10 hp at 460/480 V AC 50/60 Hz 3 phases motors 15 hp at 575/600 V AC 50/60 Hz 3 phases motors
32 A at <= 140 °F (60 °C) power circuit 10 A at <= 140 °F (60 °C) signalling circuit
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Page 2
Irms rated making capacity 300 A at 440 V power circuit conforming to IEC 60947
Rated breaking capacity 300 A at 440 V power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 145 A <= 104 °F (40 °C) 10 s power circuit
Associated fuse rating 35 A gG at <= 690 V coordination type 2 power circuit
Average impedance 2.5 mOhm at 50 Hz - Ith 32 A power circuit
[Ui] rated insulation voltage 600 V power circuit certifications CSA
Electrical durability 1.65 Mcycles 18 A AC-3 at Ue <= 440 V
Power dissipation per pole 0.8 W AC-3
Protective cover With
Mounting support Plate
Standards CSA C22.2 No 14
Product certifications CSA
Connections - terminals Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with
Tightening torque Power circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
140 A AC signalling circuit conforming to IEC 60947-5-1 250 A DC signalling circuit conforming to IEC 60947-5-1
240 A <= 104 °F (40 °C) 1 s power circuit 40 A <= 104 °F (40 °C) 10 min power circuit 84 A <= 104 °F (40 °C) 1 min power circuit 100 A 1 s signalling circuit 120 A 500 ms signalling circuit 140 A 100 ms signalling circuit
50 A gG at <= 690 V coordination type 1 power circuit 10 A gG signalling circuit conforming to IEC 60947-5-1
600 V power circuit certifications UL 690 V power circuit conforming to IEC 60947-4-1 690 V signalling circuit conforming to IEC 60947-1 600 V signalling circuit certifications CSA 600 V signalling circuit certifications UL
1 Mcycles 32 A AC-1 at Ue <= 440 V
2.5 W AC-1
Rail
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
LROS GOST GL UL DNV BV CCC RINA
cable end Power circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...6 mm²) - cable stiffness: flexible - with cable end Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible ­without cable end Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible ­without cable end Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible ­with cable end Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid ­without cable end Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid ­without cable end Power circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1.5...6 mm²) - cable stiffness: flexible ­without cable end Power circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...6 mm²) - cable stiffness: flexible ­without cable end Power circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - with cable end Power circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1.5...6 mm²) - cable stiffness: solid ­without cable end Power circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...6 mm²) - cable stiffness: solid ­without cable end
Power circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
2
Page 3
Control circuit: 15.04 lbf.in (1.7 N.m) - on screw clamp terminals - with screwdriver Philips No 2
Operating time 4...19 ms opening
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability 15 Mcycles
Operating rate 3600 cyc/h at <= 140 °F (60 °C)
12...22 ms closing
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc drop-out at 140 °F (60 °C), AC 50/60 Hz
Inrush power in VA 70 VA at 68 °F (20 °C) (cos ϕ 0.75) 60 Hz
Hold-in power consumption in VA 7.5 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz
Heat dissipation 2...3 W at 50/60 Hz
Auxiliary contacts type Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA signalling circuit
Minimum switching voltage 17 V signalling circuit
Non-overlap time 1.5 ms on energisation between NC and NO contact
Insulation resistance > 10 MOhm signalling circuit
0.8...1.1 Uc operational at 140 °F (60 °C), AC 50 Hz
0.85...1.1 Uc operational at 140 °F (60 °C), AC 60 Hz
70 VA at 68 °F (20 °C) (cos ϕ 0.75) 50 Hz
7 VA at 68 °F (20 °C) (cos ϕ 0.3) 50 Hz
Type mirror contact (1 NC) conforming to IEC 60947-4-1
1.5 ms on de-energisation between NC and NO contact
Environment
IP degree of protection IP2x front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -4...140 °F (-20...60 °C)
Ambient air temperature for storage -76...176 °F (-60...80 °C)
Permissible ambient air temperature around the device
Operating altitude 9842.52 ft (3000 m) without derating in temperature
Fire resistance 1562 °F (850 °C) conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz
Height 3.03 in (77 mm)
Width 1.77 in (45 mm)
Depth 3.39 in (86 mm)
Product weight 0.73 lb(US) (0.33 kg)
-40...158 °F (-40...70 °C) at Uc
Vibrations contactor closed 4 Gn, 5...300 Hz Shocks contactor open 10 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0627 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product Environmental Profile
3
Page 4
Product end of life instructions Available
End of life manual
Contractual warranty
Warranty period 18 months
4
Loading...