Square D LC1D1286G7 Data Sheet

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Product data sheet
LC1D1286G7
TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 ­<= 440 V 25 A - 120 V AC coil
Mar 17, 2016
1
Main
Range TeSys
Product name TeSys D
Product or component type
Device short name LC1D
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
Power pole contact composition
[Ue] rated operational voltage
[Ie] rated operational current
Control circuit type AC 50/60 Hz
Control circuit voltage 120 V AC 50/60 Hz
Auxiliary contact com­position
[Uimp] rated impulse withstand voltage
Overvoltage category III
[Ith] conventional free air thermal current
Irms rated making ca­pacity
Rated breaking capac­ity
[Icw] rated short-time withstand current
Associated fuse rating 25 A gG at <= 690 V coordination type 2 for power
Average impedance 2.5 mOhm at 50 Hz - Ith 25 A for power circuit
[Ui] rated insulation voltage
Electrical durability 0.8 Mcycles 25 A AC-1 at Ue <= 440 V
Power dissipation per pole
Safety cover With
Mounting support Plate
Standards EN 60947-4-1
Contactor
2 NO + 2 NC
<= 300 V DC for power circuit <= 690 V AC 25...400 Hz for power circuit
25 A (<= 60 °C) at <= 440 V AC AC-1 for power cir­cuit
1 NO + 1 NC
6 kV conforming to IEC 60947
10 A at <= 60 °C for signalling circuit 25 A at <= 60 °C for power circuit
250 A DC for signalling circuit conforming to IEC 60947-5-1 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A at 440 V for power circuit conforming to IEC 60947
250 A at 440 V for power circuit conforming to IEC 60947
140 A 100 ms signalling circuit 120 A 500 ms signalling circuit 100 A 1 s signalling circuit 61 A <= 40 °C 1 min power circuit 30 A <= 40 °C 10 min power circuit 210 A <= 40 °C 1 s power circuit 105 A <= 40 °C 10 s power circuit
circuit 40 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
600 V for signalling circuit certifications UL 600 V for signalling circuit certifications CSA 690 V for signalling circuit conforming to IEC 60947-1 600 V for power circuit certifications UL 600 V for power circuit certifications CSA 690 V for power circuit conforming to IEC 60947-4-1
1.56 W AC-1
Rail
EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 CSA C22.2 No 14
2
Product certifications BV
Connections - terminals Power circuit : lugs-ring terminals - external diame-
Tightening torque Power circuit : 1.7 N.m - on lugs-ring terminals - with
Operating time 4...19 ms opening
Safety reliability level B10d = 20000000 cycles contactor with mechanical
Mechanical durability 15 Mcycles
Operating rate 3600 cyc/h at <= 60 °C
CCC CSA DNV GL GOST RINA UL LROS
ter: 8 mm Control circuit : lugs-ring terminals - external diame­ter: 8 mm
screwdriver Philips No 2 screw : M3.5 Power circuit : 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 8 mm screw : M3.5 Control circuit : 1.7 N.m - on lugs-ring terminals ­with screwdriver Philips No 2 screw : M3.5 Control circuit : 1.7 N.m - on lugs-ring terminals ­with screwdriver flat Ø 6 mm screw : M3.5
12...22 ms closing
load conforming to EN/ISO 13849-1 B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Complementary
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.85...1.1 Uc at 60 °C operational 60 Hz
Inrush power in VA 70 VA at 20 °C (cos ϕ 0.75) 50 Hz
Hold-in power consumption in VA 7 VA at 20 °C (cos ϕ 0.3) 50 Hz
Heat dissipation 2...3 W at 50/60 Hz
Auxiliary contacts type Type mirror contact (1 NC) conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non-overlap time 1.5 ms on energisation (between NC and NO contact)
Insulation resistance > 10 MOhm for signalling circuit
0.8...1.1 Uc at 60 °C operational 50 Hz
0.3...0.6 Uc at 60 °C drop-out 50/60 Hz
70 VA at 20 °C (cos ϕ 0.75) 60 Hz
7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
1.5 ms on de-energisation (between NC and NO contact)
Environment
IP degree of protection IP2x front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Pollution degree 3
Ambient air temperature for operation -20...60 °C
Ambient air temperature for storage -60...80 °C
Permissible ambient air temperature around the de­vice
Operating altitude 3000 m without derating in temperature
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Shocks contactor closed 15 Gn for 11 ms
Height 85 mm
-40...70 °C at Uc
Shocks contactor open 10 Gn for 11 ms Vibrations contactor closed 4 Gn, 5...300 Hz Vibrations contactor open 2 Gn, 5...300 Hz
3
Width 45 mm
Depth 92 mm
Product weight 0.365 kg
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW)
REACh Reference not containing SVHC above the threshold
Product environmental profile
Product end of life instructions Need no specific recycling operations
Compliant - since 0719 - Schneider Electric declaration of conformity
Available Download Product Environmental
Contractual warranty
Period 18 months
4