TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V
115 A - 24 V DC standard coil
Main
Range of productTeSys D
RangeTeSys
Product nameTeSys D
Product or component typeContactor
Device short nameLC1D
Contactor applicationMotor control
Resistive load
Utilisation categoryAC-1
AC-4
AC-3
Poles description3P
Pole contact composition3 NO
[Ue] rated operational voltage<= 300 V DC for power circuit
<= 1000 V AC 25...400 Hz for power circuit
[Ie] rated operational current200 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
115 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
Motor power kW55 kW at 380...400 V AC 50/60 Hz AC-3
75 kW at 500 V AC 50/60 Hz AC-3
80 kW at 660...690 V AC 50/60 Hz AC-3
30 kW at 220...230 V AC 50/60 Hz AC-3
59 kW at 415...440 V AC 50/60 Hz AC-3
65 kW at 1000 V AC 50/60 Hz AC-3
18.5 kW at 400 V AC 50/60 Hz AC-4
Motor power hp30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
40 hp at 230/240 V AC 50/60 Hz for 3 phases motors
75 hp at 460/480 V AC 50/60 Hz for 3 phases motors
100 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Control circuit typeDC standard
[Uc] control circuit voltage24 V DC
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltageConforming to IEC 60947
Overvoltage categoryIII
Sep 07, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
[Ith] conventional free air thermal
current
Irms rated making capacity1260 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current1100 A <= 40 °C 1 s power circuit
Associated fuse rating200 A gG at <= 690 V coordination type 2 for power circuit
Average impedance0.6 mOhm at 50 Hz - Ith 200 A for power circuit
[Ui] rated insulation voltage1000 V for power circuit conforming to IEC 60947-4-1
Electrical durability0.8 Mcycles 200 A AC-1 at Ue <= 440 V
Tightening torqueControl circuit : 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Operating time20...35 ms closing
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
200 A at <= 60 °C for power circuit
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
250 A <= 40 °C 10 min power circuit
550 A <= 40 °C 1 min power circuit
950 A <= 40 °C 10 s power circuit
250 A gG at <= 690 V coordination type 1 for power circuit
10 A gG for signalling circuit
600 V for power circuit certifications CSA
600 V for power circuit certifications UL
690 V for signalling circuit conforming to IEC 60947-1
600 V for signalling circuit certifications CSA
600 V for signalling circuit certifications UL
0.95 Mcycles 115 A AC-3 at Ue <= 440 V
7.9 W AC-3
Plate
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
BV
UL
GL
DNV
CCC
LROS (Lloyds register of shipping)
CSA
GOST
end
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
end
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: solid - without cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...2.5 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...2.5 mm² - cable stiffness: solid - without cable
end
Power circuit : connector 1 cable(s) 10...120 mm² - cable stiffness: flexible - without cable end
Power circuit : connector 2 cable(s) 10...50 mm² - cable stiffness: flexible - without cable end
Power circuit : connector 1 cable(s) 10...120 mm² - cable stiffness: flexible - with cable end
Power circuit : connector 2 cable(s) 10...50 mm² - cable stiffness: flexible - with cable end
Power circuit : connector 1 cable(s) 10...120 mm² - cable stiffness: solid - without cable end
Power circuit : connector 2 cable(s) 10...50 mm² - cable stiffness: solid - without cable end
Control circuit : 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit : 12 N.m - on connector hexagonal 4 mm
40...75 ms opening
2
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability8 Mcycles
Operating rate1200 cyc/h at <= 60 °C
Complementary
Coil technologyWith integral suppression device
Control circuit voltage limits0.75...1.2 Uc operational at 55 °C, DC
Time constant25 ms
Inrush power in W270...365 W at 20 °C
Hold-in power consumption in W2.4...5.1 W at 20 °C
Auxiliary contacts typeType mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Signalling circuit frequency25...400 Hz
Minimum switching current5 mA for signalling circuit
Minimum switching voltage17 V for signalling circuit
Non-overlap time1.5 ms on de-energisation (between NC and NO contact)
Insulation resistance> 10 MOhm for signalling circuit
Power range30...50 kW 200...240 V 3 phases
Motor starter typeDirect on-line contactor
Contactor coil voltage24 V DC standard
0.15...0.4 Uc drop-out at 55 °C, DC
Type mirror contact (1 NC) conforming to IEC 60947-4-1
1.5 ms on energisation (between NC and NO contact)
55...100 kW 380...440 V 3 phases
55...100 kW 480...500 V 3 phases
Environment
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068-2-30
Pollution degree3
Ambient air temperature for operation-5...60 °C
Ambient air temperature for storage-60...80 °C
Permissible ambient air temperature
around the device
Operating altitude3000 m without derating in temperature
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Mechanical robustnessVibrations contactor open 2 Gn, 5...300 Hz
Height158 mm
Width120 mm
Depth136 mm
Product weight2.5 kg
-40...70 °C at Uc
Vibrations contactor closed 4 Gn, 5...300 Hz
Shocks contactor closed 15 Gn for 11 ms
Shocks contactor open 6 Gn for 11 ms
Offer Sustainability
Sustainable offer statusGreen Premium product
RoHS (date code: YYWW)Compliant - since 0927 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REAChReference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profileAvailable
Product environmental
Product end of life instructionsAvailable
3
End of life manual
Contractual warranty
Warranty period18 months
4
Product data sheet
LC1D115BD
Dimensions Drawings
Dimensions
(1)Minimum electrical clearance
LC1D115 and D150 (3-pole)
a120
b1with LA4 DA2174
with LA4 DF, DT 185
with LA4 DM, DL 188
with LA4 DW188
cwithout cover or add-on blocks132
with cover, without add-on blocks136
c1with LAD N or C (2 or 4 contacts)150
c2with LA6 DK20155
c3with LAD T, R, S168
with LAD T, R, S and sealing cover172
5
Product data sheet
Connections and Schema
Wiring
LC1D115BD
6
Product data sheet
LC1D115BD
Motor Starter BOM
Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power 55 kW and 415 VAC
Motor power
(kW)
5535
Non contractual pictures.
Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and
must not be able to resume operation without repair or the replacement of parts.
ICU
(kA)
BreakerContactor (*)
GV7RE150LC1D115BD
7