Product data sheet
Characteristics
GV2P10
TeSys GV2 - Motor circuit breaker - thermalmagnetic - 4…6.3 A
Main
Range TeSys
Product name TeSys GV2
Device short name GV2P
Product or component type Circuit breaker
Device application Motor
Trip unit technology Thermal-magnetic
Complementary
Poles description 3P
Network type AC
Utilisation category AC-3 conforming to IEC 60947-4-1
Network frequency 50/60 Hz conforming to IEC 60947-4-1
Mounting mode By clips
Mounting support Plate
Mounting position Horizontal
Motor power kW 3 kW at 500 V AC 50/60 Hz
Breaking capacity 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit
breaking capacity
Dec 06, 2017
Category A conforming to IEC 60947-2
By screws
Rail
Vertical
4 kW at 690 V AC 50/60 Hz
2.2 kW at 400/415 V AC 50/60 Hz
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1

100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Control type Rotary knob
[In] rated current 4...6.3 A
Trip unit rating 4...6.3 A
Magnetic tripping current 78 A
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal
current
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
Power dissipation per pole 2.5 W
Mechanical durability 100000 cycles
Electrical durability 100000 cycles for AC-3 at 440 V
Operating rate 25 cyc/h
Rated duty Continuous conforming to IEC 60947-4-1
Connections - terminals Screw clamp terminals 2 cable(s) 1...6 mm² - cable stiffness : solid
Tightening torque 1.7 N.m - on screw clamp terminals
Suitability for isolation Yes conforming to IEC 60947-1
Phase failure sensitivity Yes conforming to IEC 60947-4-1
Height 89 mm
Width 45 mm
Depth 97 mm
6.3 A conforming to IEC 60947-4-1
Screw clamp terminals 2 cable(s) 1.5...6 mm² - cable stiffness : flexible - without cable end
Screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness : flexible - with cable end
Environment
Standards EN 60204
Product certifications ATEX
Protective treatment TH
IP degree of protection IP20 conforming to IEC 60529
IK degree of protection IK04
Ambient air temperature for operation -20...60 °C
Ambient air temperature for storage -40...80 °C
Fire resistance 960 °C conforming to IEC 60695-2-1
Operating altitude 2000 m
IEC 60947-1
IEC 60947-2
IEC 60947-4-1
NF C 63-120
NF C 63-650
NF C 79-130
UL 508
VDE 0113
VDE 0660
CSA C22.2
BV
CCC
CSA
DNV
EZU
GL
LROS (Lloyds register of shipping)
RINA
TSE
UL
UL 508 type E
EAC
Offer Sustainability
Sustainable offer status Green Premium product
2

RoHS (date code: YYWW) Compliant - since 0631 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months