Square D FHP36025 Data Sheet

Product data sheet
Characteristics
FHP36025
FA/LA MOLDED CASE CIRCUIT BREAKER 600V, 25A,
Main
Product or component type Circuit breaker
Range of product I-Line
Trip Unit Type Thermal-magnetic
Rating Code H
Complementary
Line Rated Current 25 A
Number of Poles 3P
Interrupt Rating 65 kA at 240 V AC
System Voltage 250 V DC
Mounting mode Unit mount
Electrical connection Bolted connection line
Wire Gauge AWG 14...AWG 4 (copper) 1 cable(s)
Terminal Type AL50FA
Magnetic hold current 275 A
Magnetic tripping current 600 A
Phase connection ABC
Height 6.4 in
Width 4.5 in
Depth 4.13 in
18 kA at 600 V AC 10 kA at 250 V DC 25 kA at 480 V AC
600 V AC
Lugs load
AWG 12...AWG 4 (aluminium) 1 cable(s)
Feb 21, 2019
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Environment
Product certifications CSA
UL listed
Ordering and shipping details
Category 00903 - FAL/FHL 600V
Discount Schedule DE2
GTIN 00785901747413
Nbr. of units in pkg. 1
Package weight(Lbs) 4.8100000000000005
Returnability Y
Country of origin MX
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant ๎™„- since๎™„ 1304 ๎™„-๎™„ Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
FHP36025 is replaced by:
Unit Mount BGP36025
PowerPact - circuit breaker - 25A 3P AC 18kA at 600Y/347V (UL) - Everlink Lug Qty 1
Reason for Substitution: End of life | Substitution date: 30 June 2019 | (Ref #) is replaced by (New Ref #)
2