Square D BDL36080LU Data Sheet

Product data sheet
Characteristics
BDL36080LU
PowerPact-circuit breaker-80A 3P AC 18kA at 480/440V(UL/IEC)-TMD-EverLink lug
Range PowerPact
Product name PowerPact B
Device short name BD 080
Product or component type Circuit breaker
Device application Distribution
Complementary
[In] rated current 80 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code D
Breaking capacity 25 kA at 240 V AC 50/60 Hz according to UL 489
18 kA at 480 V AC 50/60 Hz according to UL 489 Icu : 25 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2 Icu : 18 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2 Icu : 18 kA at 440 V AC 50/60 Hz according to IEC 60947-2 Icu : 14 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2 18 kA at 480Y/277 V AC 50/60 Hz according to UL 489 14 kA at 600Y/347 V AC 50/60 Hz according to UL 489 25 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 25 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
18 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2 18 kA : at 440 V AC 50/60 Hz according to IEC 60947-2 14 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV according to IEC 60947-2
Dec 3, 2018
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
[Ui] rated insulation voltage 800 V according to IEC 60947-2
Trip unit technology Thermal-magnetic
Trip unit name TM-D
Trip unit protection functions LI
Protection type Overload protection (thermal)
Trip unit rating 80 A at 40 °C
Magnetic hold current 800 A
Magnetic tripping current 1200 A
Suitability for isolation Yes according to IEC 60947-2
Utilisation category Category A
Mechanical durability 15000 cycles IEC 947-1 Annex K ed 5.2
Electrical durability 10000 cycles according to IEC 947-1 Annex K ed 5.2 for In at 440 V
Connection pitch 27 mm
Local signalling Green flag for presence of auxiliary contacts
Rotary handle padlocking Padlock in OFF or ON position
Connections - terminals Upside 1 EverLink lug with voltage tap-off wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded
Current of common 10 A for 0.5...6 mm² ( AWG 20...AWG 10) , (stranded or fine stranded)
Tightening torque 5 N.m for 2.5...16 mm² (AWG 14...AWG 4)
Number of slots 1 slot(s) for auxiliary switch OF (plug-in)
Wire stripping length 20 mm
Quality labels CE
Standards EN/IEC 60947-2
Colour Grey (RAL 7016)
9 mm pitches 9
Height 137 mm
Width 81 mm
Depth 80 mm
Product weight 1.074 kg
Quantity per set Set of 1
Short-circuit protection (magnetic)
copper Downside 1 Everlink lug wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded copper Upside 1 EverLink lug with voltage tap-off wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or stranded aluminium/copper Downside 1 Everlink lug wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or stranded aluminium/ copper
10 A for 1.5...6 mm² ( AWG 20...AWG 10) , (rigid)
9 N.m for 25...95 mm² (AWG 3...AWG 3/0)
1 slot(s) for voltage release MN or MX (plug-in) 1 slot(s) for alarm switch SD (plug-in)
EN/IEC 60947-5-1 GB 14048.2 NEMA AB1 UL 489 CSA C22.2 No 5 NMX J-266
Environment
Product certifications UL
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
2
CSA CCC EAC NOM IEC