Product data sheet
ATV630D37N4
variable speed drive ATV630 - 37kW/50HP -
380...480V - IP21/UL type 1
Dec 16, 2016
1
Page 2
Main
Range of product Altivar Process ATV600 Product or component
type Product specific appli-
cation Device short name ATV630 Variant Standard version Product destination Asynchronous motors
Mounting mode Wall mount EMC filter Integrated EN/IEC 61800-3 category C2 50 m
IP degree of protection IP21 IEC 61800-5-1
Degree of protection UL type 1 UL 508C Type of cooling Forced convection Supply frequency 50...60 Hz - 5...5 % Network number of
phases [Us] rated supply volt-
age Motor power kW 37 kW normal duty
Motor power hp 50 hp normal duty
Line current 66.2 A 380 V normal duty
Prospective line Isc 50 kA Apparent power 47.6 kVA 480 V normal duty
Continuous output cur­rent
Maximum transient cur­rent
Asynchronous motor control profile
Synchronous motor control profile
Output frequency 0.0001...0.5 kHz Nominal switching fre-
quency Switching frequency 2...12 kHz adjustable
Safety function STO (safe torque off) SIL 3 Discrete input logic 16 preset speeds
Variable speed drive
Process and utilities
Synchronous motors
Integrated EN/IEC 61800-3 category C3 150 m
IP21 IEC 60529
3 phases
380...480 V - 15...10 %
30 kW heavy duty
40 hp heavy duty
57.3 A 480 V normal duty
54.8 A 380 V heavy duty
48.3 A 480 V heavy duty
40.2 kVA 480 V heavy duty
74.5 A 4 kHz normal duty
61.5 A 4 kHz heavy duty 82 A 60 s normal duty
92.3 A 60 s heavy duty Constant torque standard
Variable torque standard Optimized torque mode
Permanent magnet motor
4 kHz
4...12 kHz with derating factor
2
Page 3
Communication port protocol
Option card Communication module Profibus DP V1 slot A
Ethernet Modbus serial Modbus TCP
Communication module Profinet slot A Communication module DeviceNet slot A Communication module Modbus TCP/EtherNet/IP slot A Communication module CANopen daisy chain RJ45 slot A Communication module CANopen SUB-D 9 slot A Communication module CANopen screw terminals slot A Digital and analog I/O extension module slot A/slot B Output relay extension module slot A/slot B Communication module Ethernet IP/Modbus TCP/ MD-Link slot A
Complementary
Output voltage <= power supply voltage Permissible temporary current boost 1.1 x In 60 s normal duty
Motor slip compensation Adjustable
Acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s
Braking to standstill By DC injection Protection type Thermal protection motor
Frequency resolution 0.1 Hz display unit
Electrical connection Removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 control
Type of connector RJ45 Ethernet/Modbus TCP on the remote graphic terminal
Physical interface 2-wire RS 485 Modbus serial Transmission frame RTU Modbus serial Transmission rate 10/100 Mbit/s Ethernet IP/Modbus TCP
Exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP Data format 8 bits, configurable odd, even or no parity Modbus serial Type of polarization No impedance Modbus serial Number of addresses 1...247 Modbus serial Method of access Slave Modbus TCP Supply External supply for digital inputs 24 V DC 19...30 V <= 1.25 mA overload and
1.5 x In 60 s heavy duty
Automatic whatever the load Can be suppressed Not available in permanent magnet motor law
S, U or customized
Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive
0.012/50 Hz analog input
Screw terminal 35...50 mm² AWG 3...AWG 1 line side Screw terminal 35...50 mm² AWG 3...AWG 1 motor
RJ45 Modbus serial on the remote graphic terminal
4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <= 10 mA overload and short-circuit protection Internal supply for digital inputs and STO 24 V DC 21...27 V <= 200 mA overload and short-circuit protection
3
Page 4
Local signalling 3 LEDs local diagnostic
Width 226 mm Height 673 mm Depth 271 mm Product weight 28.2 kg Analogue input number 3 Analogue input type Software-configurable voltage AI1, AI2, AI3 0...10 V DC 30 kOhm 12 bits
Discrete input number 8 Discrete input type Programmable DI1...DI6 24 V DC <= 30 V 3.5 kOhm
Input compatibility Level 1 PLC EN/IEC 61131-2 DI1...DI6 discrete input
Discrete input logic Positive logic (source) DI1...DI6 < 5 V > 11 V
Analogue output number 2 Analogue output type Software-configurable voltage AO1, AO2 0...10 V DC 470 Ohm 10 bits
Sampling duration 2 ms +/- 0.5 ms DI1...DI4 discrete input
Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
Linearity error +/- 0.15 % of maximum value analog input AI1, AI2, AI3
Relay output number 3 Relay output type Configurable relay logic R1 fault relay NO/NC 100000 cycles
Refresh time 5 ms +/- 0.5 ms R1, R2, R3 relay output Minimum switching current 5 mA 24 V DC R1, R2, R3 relay output Maximum switching current 3 A 250 V AC resistive 1 R1, R2, R3 relay output
Isolation Between power and control terminals Functionality Full Specific application Utility IP degree of protection IP21
3 LEDs dual colour embedded communication status 4 LEDs dual colour communication module status 1 LED red presence of voltage
Software-configurable current AI1, AI2, AI3 0...20 mA 250 Ohm 12 bits
Programmable as pulse input DI5, DI6 0...30 kHz 24 V DC <= 30 V Safe torque off STOA, STOB 24 V DC <= 30 V > 2.2 kOhm
Level 1 PLC IEC 65A-68 DI5, DI6 discrete input Level 1 PLC EN/IEC 61131-2 STOA, STOB discrete input
Negative logic (sink) DI1...DI6 > 16 V < 10 V Positive logic (source) DI5, DI6 < 0.6 V > 2.5 V Positive logic (source) STOA, STOB < 5 V > 11 V
Software-configurable current AO1, AO2 0...20 mA 10 bits
5 ms +/- 1 ms DI5, DI6 discrete input 5 ms +/- 0.1 ms AI1, AI2, AI3 analog input 10 ms +/- 1 ms AO1 analog output
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
+/- 0.2 % analog output AO1, AO2
Configurable relay logic R2 sequence relay NO 100000 cycles Configurable relay logic R3 sequence relay NO 100000 cycles
3 A 30 V DC resistive 1 R1, R2, R3 relay output 2 A 250 V AC inductive 0.4 7 ms R1, R2, R3 relay output 2 A 30 V DC inductive 0.4 7 ms R1, R2, R3 relay output
Environment
Insulation resistance > 1 mOhm 500 V DC for 1 minute to earth Noise level 63.5 dB 86/188/EEC Power dissipation in W 106 W natural convection 380 V 4 kHz
Volume of cooling air 240 m3/h Operating position Vertical +/- 10 degree THDI <= 48 % from 80...100 % of load IEC 61000-3-12 Electromagnetic compatibility Electrostatic discharge immunity test level 3 IEC 61000-4-2
Pollution degree 2 EN/IEC 61800-5-1
4
796 W forced convection 380 V 4 kHz
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Page 5
Vibration resistance 1.5 mm peak to peak 2...13 Hz IEC 60068-2-6
Shock resistance 15 gn 11 ms IEC 60068-2-27 Relative humidity 5...95 % without condensation IEC 60068-2-3 Ambient air temperature for operation -15...50 °C without derating
Ambient air temperature for storage -40...70 °C Operating altitude <= 1000 m without derating
Environmental characteristic Chemical pollution resistance class 3C3 EN/IEC 60721-3-3
Standards UL 508C
Product certifications ATEX INERIS
Marking CE Discrete and process manufacturing Building - HVAC : compressor
Power range 30...50 kW Voltage range 380...440 V
Network number of phases 3 phases
1 gn 13...200 Hz IEC 60068-2-6
50...60 °C with derating factor
1000...4800 m with current derating 1 % per 100 m
Dust pollution resistance class 3S3 EN/IEC 60721-3-3
EN/IEC 61800-3 EN/IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
ATEX zone 2/22 CSA TÜV UL REACH DNV-GL
Building - HVAC : compressor centrifugal Food and beverage processing : other application Mining mineral and metal : fan Mining mineral and metal : pump Oil and gas : compressor Oil and gas : fan Oil and gas : pump Others : compressor Water and waste water : other application
480...500 V
Offer Sustainability
Sustainable offer status Green Premium product RoHS (date code: YYWW)
REACh
Product environmental profile
Product end of life instructions Available
Compliant - since 1426 - Schneider Electric declaration of conformity
Reference contains SVHC above the threshold - go to CaP for more details
Available Download Product Environmental
5
Page 6
Product data sheet
Dimensions Drawings
Dimensions
Views: Front - Left - Rear
ATV630D37N4
6
Page 7
Drive Without IP21 Top Cover
Views: Left - Rear
7
Page 8
Product data sheet
Mounting and Clearance
Clearances
ATV630D37N4
X1 X2 X3
≥ 100 mm (3.94 in.) ≥ 100 mm (3.94 in.) ≥ 10 mm (0.39 in.)
Mounting Types
Mounting Type A: Individual IP21
a ≥ = 110 mm (4.33 in.)
8
Page 9
Mounting Type B: Side by Side IP20 (Possible, 2 Drives Only)
Mounting Type C: Individual IP20
a ≥ = 110 mm (4.33 in.)
9
Page 10
Product data sheet
ATV630D37N4
Connections and Schema
Single or Three-Phase Power Supply with Upstream Breaking via Line Contactor
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1
(1) Use digital output R1 set to operating state Fault to switch Off the product once an error is detected. A1 : Drive KM1 :Line Contactor Q2,
Circuit breakers Q3 : S1,
Pushbuttons S2 : T1 : Transformer for control part
Single or Three-Phase Power Supply with Downstream Breaking via Switch Disconnector
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1
(1) Use digital output R1 set to operating state Fault to switch Off the product once an error is detected. A1 : Drive Q1 : Switch disconnector
Control Block Wiring Diagram
10
Page 11
(1) Safe Torque Off (2) Analog Output (3) Digital Input (4) Reference potentiometer (5) Analog Input A1 : ATV6.. Drive R1A,
Fault relay R1B, R1C : R2A,
Sequence relay R2C : R3A,
Sequence relay R3C :
Sensor Connection
It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.
Sink / Source Switch Configuration
The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
● Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
● Set the switch to Ext if using PLC outputs with NPN transistors.
Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs
11
Page 12
Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs
Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs
Switch Set to EXT Position Using an External Power Supply for the DIs
12
Page 13
Product data sheet
Performance Curves
Derating Curves
ATV630D37N4
40 °C (104 °F) - Mounting type A, B and C
50 °C (122 °F) - Mounting type A, B and C
60 °C (140 °F) - Mounting type B and C In : Nominal Drive Current SF : Switching Frequency
13