Speed range 1…10
Speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn
Torque accuracy +/- 15 %
Transient overtorque 120% of nominal motor torque +/- 10 % 60 s
Asynchronous motor control profile Voltage/frequency ratio, 2 points
Regulation loop Adjustable PI regulator
Motor slip compensation Not available in voltage/frequency ratio motor control
Local signalling DC bus energized 1 LED red)
Output voltage <= power supply voltage
Isolation Electrical between power and control
Type of cable Without mounting kit 1 IEC cable 113°F (45°C), copper 90 °C / XLPE/EPR
Electrical connection VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.00in² (2.5mm²) / AWG 14
Tightening torque 5.31lbf.in (0.6N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
Supply Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10A overload and
Analogue input number 2
Analogue input type VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits
Sampling duration 2ms +/- 0.5 ms F discrete
Response time FM 2 ms +/- 0.5 ms analog
Accuracy +/- 0.6 % VIA) for a temperature variation 60 °C
Linearity error VIA +/- 0.15 % of maximum value input
Analogue output number 1
Analogue output type FM switch-configurable voltage 0...10 V DC 7620Ohm 10 bits
Discrete output number 2
Discrete output type Configurable relay logic FLA, FLC) NO - 100000cycles
Minimum switching current 3mA 24 V DC configurable relay logic
Maximum switching current 5A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)
Discrete input type F programmable 24 V DC level 1 PLC 4700 Ohm
Discrete input logic Positive logic (source) F, R, RES), <= 5 V, >= 11 V
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Flux vector control without sensor, standard
Voltage/frequency ratio - Energy Saving, quadratic U/f
Voltage/frequency ratio, 5 points
Adjustable
Automatic whatever the load
Without mounting kit 1 IEC cable 113°F (45°C), copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40°C, copper 75 °C / PVC
L1/R, L2/S, L3/T terminal 0.02in² (16mm²) / AWG 6
22.13lbf.in (2.5N.m), 22 lb.in L1/R, L2/S, L3/T)
short-circuit protection
Internal supply 24 V DC 21…27V), <200A overload and short-circuit protection
VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits
VIB configurable PTC probe 0...6 probes 1500 Ohm
VIA switch-configurable current 0...20 mA 250 Ohm 10 bits
2ms +/- 0.5 ms R discrete
2ms +/- 0.5 ms RES discrete
3.5ms +/- 0.5 ms VIA analog
22ms +/- 0.5 ms VIB analog
FLA, FLC 7 ms +/- 0.5 ms discrete
FLB, FLC 7 ms +/- 0.5 ms discrete
RY, RC 7 ms +/- 0.5 ms discrete
+/- 0.6 % VIB) for a temperature variation 60 °C
+/- 1 % FM) for a temperature variation 60 °C
VIB +/- 0.15 % of maximum value input
FM +/- 0.2 % output
FM switch-configurable current 0...20 mA 970Ohm 10 bits
Configurable relay logic FLB, FLC) NC - 100000cycles
Configurable relay logic RY, RC) NO - 100000cycles
5A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R)
2A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R)
2A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R)
R programmable 24 V DC level 1 PLC 4700 Ohm
RES programmable 24 V DC level 1 PLC 4700 Ohm
Negative logic (sink) F, R, RES), >= 16 V, <= 10 V
2

Acceleration and deceleration ramps Automatic based on the load
Braking to standstill By DC injection
Protection type Overheating protection drive
Dielectric strength 3535V DC between earth and power terminals
Insulation resistance >= 1 mOhm 500 V DC for 1 minute
Frequency resolution Display unit 0.1 Hz
Communication port protocol METASYS N2
Connector type 1 open style
Physical interface 2-wire RS 485
Transmission frame RTU
Transmission rate 9600 bps or 19200 bps
Data format 8 bits, 1 stop, odd even or no configurable parity
Type of polarization No impedance
Number of addresses 1…247
Communication service Read holding registers (03) 2 words maximum
Option card Communication card for LonWorks
Operating position Vertical +/- 10 degree
Width 7.09in (180mm)
Height 9.13in (232mm)
Depth 6.69in (170mm)
Net Weight 14.22lb(US) (6.45kg)
Power dissipation in W 430W
Air flow 38833.99Gal/hr(US) (147m3/h)
Functionality Mid
Specific application HVAC
IP degree of protection IP21
Variable speed drive application
selection
Motor power range AC-3 7…11kW at 380…440V 3 phases
Motor starter type Variable speed drive
Linear adjustable separately from 0.01 to 3200 s
Thermal power stage drive
Short-circuit between motor phases drive
Input phase breaks drive
Overcurrent between output phases and earth drive
Overvoltages on the DC bus drive
Break on the control circuit drive
Against exceeding limit speed drive
Line supply overvoltage and undervoltage drive
Line supply undervoltage drive
Against input phase loss drive
Thermal protection motor
Motor phase break motor
With PTC probes motor
5092V DC between control and power terminals
Analog input 0.024/50 Hz
APOGEE FLN
LonWorks
BACnet
Modbus
1 RJ45
Time out setting from 0.1 to 100 s
Write single register (06)
Monitoring inhibitable
Write multiple registers (16) 2 words maximum
Read device identification (43)
Compressor for scroll Building - HVAC
Fan Building - HVAC
Pump Building - HVAC
7…11kW 480…500V 3 phase
Environment
Electromagnetic compatibility Electrostatic discharge immunity test level 3 IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
3

Electrical fast transient/burst immunity test level 4 IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5
Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Voltage dips and interruptions immunity test IEC 61000-4-11
Pollution degree 2 IEC 61800-5-1
IP degree of protection IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1
Vibration resistance 1.5 mm 3…13Hz)EN/IEC 60068-2-6
Shock resistance 15 gn 11ms IEC 60068-2-27
Environmental characteristic Classes 3C1 IEC 60721-3-3
Noise level 51dB 86/188/EEC
Operating altitude 3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network
Relative humidity 5…95% without condensation IEC 60068-2-3
Ambient air temperature for operation -10…40°C (without derating)
Ambient air temperature for storage -13…158°F (-25…70°C)
Standards EN 61800-3 category C2
Product certifications C-tick
Marking CE
IP20 on upper part without blanking plate on cover EN/IEC 60529
IP21 EN/IEC 61800-5-1
IP21 EN/IEC 60529
IP41 on upper part EN/IEC 61800-5-1
IP41 on upper part EN/IEC 60529
1 gn 13…200Hz)EN/IEC 60068-2-8
Classes 3S2 IEC 60721-3-3
with current derating 1 % per 100 m
<= 3280.84 ft (1000 m) without derating
5…95% without dripping water IEC 60068-2-3
40…50°C (with derating factor)
EN 61800-3 environments 1 category C2
IEC 61800-3 category C3
EN 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C3
UL Type 1
IEC 61800-3 environments 1 category C1
IEC 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C3
EN 61800-3 environments 2 category C2
EN 61800-3
IEC 61800-3 category C2
EN 61800-3 environments 1 category C1
EN 61800-5-1
EN 55011 class A group 1
IEC 61800-3 environments 2 category C2
EN 61800-3 category C3
IEC 61800-5-1
EN 61800-3 environments 2 category C1
IEC 61800-3
IEC 61800-3 environments 1 category C2
IEC 61800-3 environments 2 category C1
NOM 117
CSA
UL
Ordering and shipping details
Category 22157 - ATV212 1 - 25 HP 460 VOLT
Discount Schedule CP4D
GTIN 00785901945048
Nbr. of units in pkg. 1
Package weight(Lbs) 13.57lb(US) (6.16kg)
Returnability Yes
Country of origin ID
Packing Units
Unit Type of Package 1 PCE
4

Package 1 Height 10.63in (27cm)
Package 1 width 11.81in (30cm)
Package 1 Length 9.06in (23cm)
Package 2 Weight 163.52lb(US) (74.17kg)
Offer Sustainability
Sustainable offer status Green Premium product
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
is known to the State of California to cause cancer and birth defects or other reproductive harm. For
more information go to www.P65Warnings.ca.gov
EU RoHS Declaration
never end up in rubbish bins.
Contractual warranty
Warranty 18 months
5