soft starter for asynchronous motor - ATS48 - 414
A - 208..690 V - 110..500 KW
Main
Range of productAltistart 48
Product or component typeSoft starter
Product destinationAsynchronous motors
Product specific applicationHeavy duty industry and pumps
Device short nameATS48
[Us] rated supply voltage208...690 V (- 15...10 %)
Motor power kW110 kW at 230 V for severe applications
132 kW at 230 V for standard applications
220 kW at 400 V for severe applications
220 kW at 440 V for severe applications
250 kW at 400 V for standard applications
250 kW at 440 V for standard applications
250 kW at 500 V for severe applications
250 kW at 525 V for severe applications
315 kW at 500 V for standard applications
315 kW at 525 V for standard applications
355 kW at 660 V for severe applications
400 kW at 660 V for standard applications
400 kW at 690 V for severe applications
500 kW at 690 V for standard applications
Motor power hp125 hp at 208 V for severe applications
150 hp at 208 V for standard applications
150 hp at 230 V for severe applications
300 hp at 460 V for severe applications
350 hp at 460 V for standard applications
350 hp at 575 V for severe applications
400 hp at 575 V for standard applications
Power dissipation in WFor standard applications 1172 W
For standard applications 1386 W
Utilisation categoryAC-53A
Type of startStart with torque control (current limited to 5 In)
IcL starter rating410 A for standard applications
480 A for standard applications
IP degree of protectionIP00
Sep 28, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1
Complementary
Assembly styleWith heat sink
Function availableExternal bypass (optional)
Supply voltage limits177...759 V
Supply frequency50...60 Hz (- 5...5 %)
Network frequency47.5...63 Hz
Device connectionIn the motor supply line
Factory setting current414 A
[Uc] control circuit voltage110 - 15 % to 230 + 10 %, 50/60 Hz
Control circuit consumption80 W
Discrete output number2
Discrete output type(LO1) logic output 0 V common configurable
Output absolute accuracy precision+/- 5 %
Minimum switching currentRelay outputs 10 mA at 6 V DC
Maximum switching currentLogic output 0.2 A at 30 V DC
Discrete input number5
Discrete input typePTC, 750 Ohm at 25 °C
Discrete input voltage24 V (<= 30 V)
Discrete input logicPositive logic (Stop, Run, LI3, LI4) state 0 < 5 V and <= 2 mA, state 1 > 11 V and >= 5 mA
Supply inrush currentAdjustable 0.4...1.3 Icl
Analogue output type(AO) current output 0-20 mA or 4-20 mA <= 500 Ohm
Communication port protocolModbus
Connector type1 RJ45
Communication data linkSerial
Physical interfaceRS485 multidrop
Transmission rate4800, 9600 or 19200 bps
Installed device31
Protection typePhase failure (line)
MarkingCE
Type of coolingForced convection
Operating positionVertical +/- 10 degree
Height670 mm
Width400 mm
Depth300 mm
Product weight51.4 kg
Power range110...220 kW at 380...440 V 3 phases
Motor starter typeSoft starter
(LO2) logic output 0 V common configurable
(R1) relay outputs fault relay NO
(R2) relay outputs end of starting relay NO
(R3) relay outputs motor powered NO
Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5, L/R = 20 ms
Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5, L/R = 20 ms