90% 230 V AC
Output voltage adjustment 24...28 V
Power dissipation in W 6.5W
Current consumption < 1.5 A 115 V AC
Turn-on time < 2 s
Holding time > 20 ms 115 V AC
Startup with capacitive loads 3000µF
Residual ripple < 100 mV
Expected capacitor life time 10year(s)
Meantime between failure [MTBF] 1300000h at 77°F (25°C), full load
Output protection type Against overload and short-circuits automatic reset
Connections - terminals Screw connection 0.5...2.5 mm², AWG 20...AWG 14) without wire end ferrule output
Line and load regulation < 0.5 %line
Status LED Output voltage 1 LED Green)
Maximum Depth 2.19in (55.6mm)
Maximum Height 3.58in (91mm)
Maximum Width 2.09in (53mm)
Net Weight 0.49lb(US) (0.221kg)
Output coupling Serial
Mounting support Top hat type TH35-15 rail IEC 60715
< 1 A 230 V AC
> 60 ms 230 V AC
700000h at 131°F (55°C), 80 % load
Against over temperature manual reset
Against overvoltage manual reset
Screw connection 0.5...1.5 mm², AWG 20...AWG 16) with wire end ferrule output
Screw connection 0.5...1.5 mm², AWG 20...AWG 16) input
< 1 %load
Top hat type TH35-7.5 rail IEC 60715
Double-profile DIN rail
panel mounting
Environment
Standards EN 62368-1
Product certifications CE
Operating altitude < 6561.68 ft (2000 m) overvoltage category III
Shock resistance 100 m/s² 11ms
IP degree of protection IP20
Ambient air temperature for operation 14…131°F (-10…55°C) without current derating)
EN/IEC 61010-1
EN 61010-2-201
EN/IEC 61204-3
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
EN 61000-3-2
EN 61000-3-3
UL 62368-1
UL 61010-1
UL 61010-2-201
CSA C22.2 No 62368-1
CSA C22.2 No 61010-1
CSA C22.2 No 61010-2-201
CUL Listed
CUL Recognized
RCM
CB Scheme
EAC
KC
NEC class 2
2000 m...5000 m overvoltage category II
131…158°F (55…70°C) with current derating of 2.67 % per °C)
2

-13…14°F (-25…-10°C) with current derating of 1 % per °C)
Ambient air temperature for storage -40…185°F (-40…85°C)
Relative humidity 0…95% without condensation
Overvoltage category II
Safety level Cl 2 with PE connection
Pollution degree 2
Vibration resistance 3 mm 2…9Hz)IEC 60721-3-3
Electromagnetic immunity Immunity to electrostatic discharge 6 kV contact discharge) EN/IEC 61000-4-2
Electromagnetic emission Conducted emissions EN 61000-6-3
Dielectric strength 3000V AC input/output
10 m/s² 9…200Hz)IEC 60721-3-3
Immunity to electrostatic discharge 9 kV air discharge) EN/IEC 61000-4-2
Electromagnetic field immunity test 10 V/m 80 MHz...2 GHz) EN/IEC 61000-4-3
Electromagnetic field immunity test 5 V/m 2...2.7 GHz) EN/IEC 61000-4-3
Electromagnetic field immunity test 3 V/m 2.7...6 GHz) EN/IEC 61000-4-3
Immunity to fast transients 4 kV on input-output) EN/IEC 61000-4-4
Surge immunity test 3 kV between power supply and earth) EN/IEC 61000-4-5
Surge immunity test 1.5 kV between phases) EN/IEC 61000-4-5
Immunity to conducted disturbances 10 Vrms 0.15...80 MHz) EN/IEC 61000-4-6
Immunity to magnetic fields 30 A/m 50...60 Hz) EN/IEC 61000-4-8
Immunity to voltage dips 100 % 1 cycle) EN/IEC 61000-4-11
Immunity to voltage dips 60 % 10 cycles) EN/IEC 61000-4-11
Immunity to voltage dips 30 % 25 cycles) EN/IEC 61000-4-11
Disturbing field emission EN 55016-2-3
Limits for harmonic current emissions EN 61000-3-2
Conducted disturbance emission EN 55016-1-2
Conducted disturbance emission EN 55016-2-1
Radiated emissions EN 61000-6-4
Ordering and shipping details
Category 22525 - ABL8 AND ABL7 POWER SUPPLIE
Discount Schedule CP12
GTIN 00785901704713
Nbr. of units in pkg. 1
Package weight(Lbs) 1lb(US) (0.45kg)
Returnability Yes
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
EU RoHS Declaration
never end up in rubbish bins.
3

Product data sheet
ABLM1A24025
Dimensions Drawings
Electrical Safety
● If the unit is use in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
● For means of disconnection a switch or circuit breaker, located near the product, must be included in the installation. A marking as disconnecting device for th
● The device has an internal fuse. The unit is tested and approved with branch circuit protective device up to 20A. This circuit breaker can be used as disconne
● The power supply is only suitable for audio, video, information, communication, industrial and control equipment.
4

Product data sheet
Connections and Schema
Connections and Schema
Correct Parallel Connection
ABLM1A24025
(1) : Load
Incorrect Parallel Connection
(1) : Load
ABLx1Axxxxx-1 = ABLx1Axxxxx-2
max 2 x ABLx1Axxxxx
L1 = L2
∆V max 25 mV
L
< 90% 2 x L
Load
nom
6

Output Voltage Balancing
(1) : R
(2) : R
R
Load1
I1= I 2= ~ I
= R
Load1
Load2
Load2
nom
Series Connection
(1) : V
(2) : V
(3) : 2 x Diode, V
(4) : V
(5) : Load
out1
out2
Load
= 2 x V
RRM
out
> 2 x V
out1/2
, IF > 2 x I
nom1/2
7

Product data sheet
Performance Curves
Performance Curve
X : Ambient Temperature (ºC)
Y : Percentage of Max Load (%)
1 : Altitude @2000M with Mounting A
2 : Altitude @5000M with Mounting A
3 : Altitude @2000M with Mounting B
4 : Altitude @5000M with Mounting B
ABLM1A24025
9