Product data sheet
Characteristics
9070T500D13
TRANSFORMER CONTROL 500VA
120V-12/24V
Product availability : Stock - Normally stocked in distribution facility
Main
Product or component type Industrial Control Transformer
Power Rating 500 VA
Primary Voltage 120 V
Secondary Voltage 12/24 V
Type T
Complementary
Phase 1 phase
Power Rating 500 VA per UL
Primary to Secondary Voltage 120 V : 12/24 V
Temperature rise 115 °C
Electrical connection Screw clamp terminals
Height 3.84 in
Width 4.5 in
Depth 5.49 in
Material Copper winding
Fingersafe Cover Compatibility FSC2
500 VA per CSA
500 VA per NOM
300 VA per CE
Environment
Product certifications CE
UL listed file E61239
CSA file LR37055 guide 184-N-90
Enclosure Type Not rated (open device)
Insulation temperature 356 °F (180 °C)
Apr 22, 2019
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1

Ordering and shipping details
Category 16201 - 9070 T (NOT TF) 250-2000VA
Discount Schedule CP8
GTIN 00785901905363
Nbr. of units in pkg. 1
Package weight(Lbs) 11.9
Returnability Y
Country of origin MX
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1227 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Phenyl glycidyl ether, which is known to the State of California to cause cancer and birth defects or
- - - - - - - More information For more information go to www.p65warnings.ca.gov
other reproductive harm.
Contractual warranty
Warranty period 10 years