Product data sheet
Characteristics
9012GBW21
pressure switch 9012G - adjustable scale - 2
thresholds - 13 to 425 psig
Main
Range of product 9012G
Pressure sensor type Electromechanical pressure switch
Pressure sensor name 9012G
Pressure sensor size 425 psi
Maximum pressure 850 psi
Contacts type and composition 2(NC-NO), DPDT-DB, Form ZZ, snap action, silver nickel contacts
Controlled fluid Air
Hydraulic oil (-40...250 °F)
Non-corrosive liquids
Non-corrosive gas
Fluid connection type 0.25 inch 18 NPTF conforming to UL 508
Pressure switch type of operation Regulation between 2 thresholds
Scale type Adjustable
Local display Without
Complementary
Range on decreasing pressure 13...425 psi
Approx differential at mid range 16...90 psi +/- 2.5 % full scale
Cable entry 0.5 inch NPT conduit entrance
Terminal block type 8 screw terminals
Electrical connection Screw-clamp terminals, AWG 22...AWG 12
Electrical circuit type Control circuit
Local signalling Without
[In] rated current 3 A (Ue = 240 V AC) contact code: A600 conforming to NEMA rating designation
6 A (Ue = 120 V AC) contact code: A600 conforming to NEMA rating designation
0.22 A (Ue = 125 V DC) contact code: R300 conforming to NEMA rating designation
0.11 A (Ue = 250 V DC) contact code: R300 conforming to NEMA rating designation
Setting Internal
Enclosure material Die cast aluminium alloy 380
Sep 14, 2017
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
1

Pressure actuator Diaphragm (nitrile (Buna-N))
Height 5.45 in
Depth 2.63 in
Width 3.5 in
Operating position Any position
Materials in contact with fluid Zinc plated steel
Short-circuit protection 10 A by gL (cartridge) overload and short-circuit protection
Operating rate <= 120 cyc/mn (-10...185 °F)
Mechanical durability 5000000 cycles
Repeat accuracy 4 %
Product weight 3 lb(US)
Nitrile (Buna-N)
Environment
Vibration resistance 2 gn conforming to IEC 68-2-6 (f = 40...150 Hz)
Shock resistance 50 gn conforming to IEC 58-2-27
Standards UL 508
Product certifications CE
NEMA degree of protection NEMA 4/4X/13 conforming to UL 50
Ambient air temperature for operation -10...185 °F
CSA C22.2 No 14
CE
UL listed file E12158 CCN NKPZ and CCN NTHT
CSA LR25490 class 3211 03
Offer Sustainability
Sustainable offer status Not Green Premium product
RoHS (date code: YYWW) Will not be compliant
Will not be compliant
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Available
End of life manual
Contractual warranty
Warranty period 18 months
2