MINIATURE CIRCUIT BREAKER 120V 5A
Main
Device application Distribution
Range of product C60
Product or component type
Device short name C60 UL489
Poles description 1P
Number of protected poles
[In] rated current 5 A at 25 °C
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 5 kA AIR conforming to UL 489 - 240 V AC
Suitability for isolation Yes conforming to IEC 60947-2
Miniature circuit-breaker
1
10 kA AIR conforming to UL 489 - 60 V DC 10 kA AIR conforming to UL 489 - 120 V AC 10 kA Icu conforming to IEC 60947-2 - 60 V DC 10 kA Icu conforming to IEC 60947-2 - 240 V AC
Complementary
[Ue] rated operational voltage 60 V DC
Magnetic tripping limit 7...10 x In
Contact position indicator Yes
Control type Operating handle
Local signalling Positive break indication
Mounting mode Fixed
Mounting support 35 mm symmetrical DIN rail
9 mm pitches 2
Product weight 0.11 kg
Colour Grey
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Connections - terminals Tunnel type terminals 2.5...25 mm² max
Tightening torque 2.5 N.m
125 V DC
12...240 V AC
Environment
Standards IEC 60947-2
IP degree of protection IP40 IEC 60529
Tropicalisation 2
Relative humidity 95 % (55 °C)
Operating altitude 2000 m
Ambient air temperature for operation -30...70 °C
Ambient air temperature for storage -40...80 °C
UL 489 CSA C22.2 No 5.2
Aug 4, 2016
1
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW)
REACh Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Compliant - since 1201 - Schneider Electric declaration of conformity