Square D 5S1F Data Sheet

General Purpose Low Voltage Transformers Instruction Bulletin
Storing
ENGLISH
Store the transformer in a clean, dry location until installation. Temperature range for storage is -50°C to +85°C (-58°F to +185°F).
Preparation
Transformers must be installed and serviced only by qualified personnel in accordance with NFPA checklist will help ensure a successful installation.
Check the nameplate to be sure that the transformer is the correct kVA and voltage
Verify all markings on the leads and terminals. Ensure that these markings agree
Make sure that the area of installation is well ventilated. Proper operation requires
Designate an appropriate wall, column, or other surface for installation. Ensure that
Verify that sufficient mounting hardware is chosen to support the weight of the
®
70 (NEC®) and any other applicable codes and standards. The following
for the load.
with those on the transformer nameplate.
NOTE: Terminal designations are either printed on the wire leads or identified by wire marking tape on the leads.
an ambient room temperature not to exceed 40°C (104°F).
NOTE: Encapsulated transformers may be installed outdoors without additional protection against the weather. These are marked “Type 3R” in the enclosure field of the nameplate.
enough clearance is allowed for the lifting eye(s) to be in the up position and the terminal compartment to be at the bottom. Follow clearance requirements printed on the transformer nameplate.
transformer.
Seismic Qualifications
Seismic qualification of nonstructural components by Schneider Electric is just one link in the total chain of responsibility required to maximize the probability that the equipment will be intact and functional after a seismic event. The equipment manufacturer determines that the equipment will be functional following a seismic event via shake-table testing programs. The seismic qualification testing results validate that Schneider Electric equipment will perform the intended function after the earthquake. However,the foundation and the anchorage system must also meet the applicable building codes and standards for the entire installation to maintain post earthquake functionality. Equipment inadequately mounted or mounted to weak or flexible foundations will not meet the requirements. The equipment specifier/installer determines that the equipment is rigidly supported and will not leave its foundation during a seismic event. During an earthquake, the equipment must be able to transfer the loads that are created through the mounting pad and anchorage to the load-bearing path of the building structural system. If the equipment is not attached to the building structure in accordance with the minimum standards recommended herein, the complete equipment installation might become too flexible and may overturn or shear the attachment devices and slide off its foundation. The structural civil engineer or design engineer of record is responsible for detailing the equipment connection and anchorage requirements (including the lateral restraint system if appropriate) for the given installation. The installer and manufacturers of the anchorage and lateral restraint system are responsible for ensuring that the mounting requirements are met. Schneider Electric is not responsible for the specification and performance of these anchorage systems.
2 Rev. 00, 39000-243-01© 2000–2018 Schneider Electric All Rights Reserved
Instruction Bulletin General Purpose Low Voltage Transformers
Drawings are available that include specific mounting information for seismic qualifications. Contact your local Schneider Electric representative, or call 1-888-Square D (1-888-778-2733) to obtain these drawings.
Installation
Enclosure Temperature
NEMA Type 4X Units
1. Mount the transformer.
2. Connect the transformer primary according to the wiring diagram on the nameplate. For field connections, use wire rated for a minimum 90°C (194°F) and sized for 75°C (167°F) ampacity.
3. Ground the enclosure permanently a nd adequately in accordance with National Electrical Code requirements. The separately derived secondary system may require grounding. Refer to Section 250.20(D) of NFPA 70 (2008).
4. Energize the unit, and check the seconda ry voltage to be sure it is proper for the load.
NOTE: Measured voltage may be slightly higher than nominal because of compensated windings on transformers 3 kVA and below.
5. Shut off the primary supply.
6. Test with a properly rated voltage sensing device to ensure that the power is off.
7. Connect the load to the secondary.
8. Replace all enclosure covers.
9. Energize the unit.
The temperature of the enclosure exterior for encapsulated transformers should not exceed ambient plus 65°C (149°F) rise as indicated in UL
Conduit hubs, closure plates, and oth er eq uipment intended to be field installed on NEMA Type 4X units shall be selected and installed to maintain the environmental integrity of the enclosure.
®
Standard 506.
ENGLISH
3Rev. 00, 39000-243-01 © 2000–2018 Schneider Electric All Rights Reserved
Loading...
+ 8 hidden pages