SPX IBP600, IBP500, IBP900, IBP750, IBP1050 Instruction Manual

...
Page 1
INSTRUCTION MANUAL
IBP Series
Blower Purge Desiccant Compressed Air Dryer
FORM NO.: 3158144 R EVISION: 07/2014 READ AND U NDE RSTAND THIS MANUAL PRI OR TO OPERATING OR SERVICI NG THI S PRODUCT.
MODELS
IBP500 IBP600 IBP750 IBP900 IBP1050
IBP1300 IBP1500 IBP1800 IBP2200 IBP2600
IBP3200 IBP3600 IBP4300
RATED
FLOW
500 SCFM 600 SCFM 750 SCFM 900 SCFM 1050 SCFM
1300 SCFM 1500 SCFM 1800 SCFM 2200 SCFM 2600 SCFM
3200 SCFM 3600 SCFM 4300 SCFM
MODEL
500 600 750 900
1050
1300 1500 1800 2200 2600
3200 3600 4300
Page 2
Contents
1.0 General Safety Information ........................... 1
2.0 Receiving, Storing, and Moving ..................... 1
3.0 Description .................................................... 2
4.0 Installation ..................................................... 2
5.0 Instrumentation .............................................. 7
6.0 Operation ....................................................... 11
7.0 Maintenance .................................................. 28
8.0 Troubleshooting ............................................. 30
DRAWINGS
Electrical Schematic – 460VAC, 3 phase .............. 33
Electrical Schematic – 575VAC, 3 phase .............. 34
Electrical Data – Fusing & Wire Sizing .................. 35
P&ID Schematic - Models 500 through 600 ......... 36
P&ID Schematic - Models 750 through 4300 ....... 38
REPLACEMENT PARTS
Models 500 through 600 ........................................ 40
Models 750 through 1800 ...................................... 42
Models 2200 through 2600 .................................... 44
Models 3200 through 4300 .................................... 46
WARRANTY
Page 3

1.0 General Safety Information

This equipment is designed and built with safety as a prime consideration; industry-accepted safety factors have been used in the design. Each dryer is checked at the factory for safety and operation. All pressure ves­sels which fall under the scope of ASME Section VIII, are hydrostatically tested in accordance with the latest addenda. A factory-installed safety relief valve is standard on each dryer.
WARNING — The following safety rules must be observed to ensure safe dryer operation. Failure to follow these rules may void the warranty or result in dryer damage or personal injury.
1. Never install or try to repair any dryer that has been damaged in shipment. See the Receiving and In­spection instructions in this manual for appropriate action.
2. This equipment is a pressure-containing device. Never operate the dryer at pressures or temperatures above the maximum conditions shown on the data plate.
Never dismantle or work on any component of the
dryer or compressed air system under pressure. Vent internal air pressure to the atmosphere before servicing.
3. This equipment requires electricity to operate. Install equipment in compliance with national and local electrical codes. Standard equipment is supplied with NEMA 4, 4X electrical enclosures and is not intended for installation in hazardous environments.
Never perform electrical service on the dryer unless
the main power supply has been disconnected. Parts of the control circuit may remain energized when the power switch is turned off.
4. Air treated by this equipment may not be suitable
for breathing without further purication. Refer to
OSHA standard 1910.134 for the requirements for breathing quality air.
5. Certain parts of the dryer are not insulated and may become hot during normal operation of the dryer. Do
not touch any of these areas without rst determining
the surface temperature.
6. Use only genuine replacement parts from the manu­facturer. The manufacturer bears no responsibility for hazards caused by the use of unauthorized parts.
Safety instructions in this manual are boldfaced for emphasis. The signal words DANGER, WARNING and CAUTION are used to indicate hazard seriousness levels as follows:
DANGER—Immediate hazard which will result in severe injury or death.
WARNING—Hazard or unsafe practice which could result in severe injury or death.
CAUTION—Hazard or unsafe practice which could result in minor injury or in product or property damage.
The dryer data plate, attached to the electrical control box, contains critical safety and identication informa­tion. If the data plate is missing or defaced, immediately contact your local distributor for a replacement.

2.0 Receiving, Storing, and Moving

2.1 Receiving and Inspection
This shipment has been thoroughly checked, packed and inspected before leaving our plant. It was received in good condition by the carrier and was so acknowledged.
Immediately upon receipt, thoroughly inspect for visible loss or damage that may have occurred during shipping. If this shipment shows evidence of loss or damage at time of delivery to you, insist that a notation of this loss or damage be made on the delivery receipt by the car­rier’s agent. Otherwise no claim can be enforced against the carrier.
Also check for concealed loss or damage. When a ship­ment has been delivered to you in apparent good order, but concealed damage is found upon unpacking, notify the carrier immediately and insist on his agent inspecting the shipment. The carrier will not consider any claim for loss or damage unless an inspection has been made. If you give the carrier a clear receipt for goods that have been damaged or lost in transit, you do so at your own risk and expense. Concealed damage claims are not our responsibility as our terms are F.O.B. point of shipment. Shipping damage is not covered by the dryer warranty.
2.2 Storing
Store the dryer indoors to prevent damage to any electri­cal or mechanical components. All packaging material should be left in place until the dryer is in position.
2.3 Handling
The dryer is designed to be moved by means of the ship­ping skid or the base channels. The dryer may also have lifting lugs for use with an overhead crane. Be sure to attach all of the lift points and use appropriate spreader bars to prevent damage to the dryer.
CAUTION — Never lift the dryer by attaching hooks or slings to the piping, or to any part other than the lifting lugs. Severe structural damage could occur.
1
Page 4

3.0 Description

3.1 Function
Blower purge type regenerative dryers are an economi­cal and reliable way to dry compressed air to dew points below the freezing point of water. Desiccant dryers lower the dew point of compressed air by adsorbing the water vapor present in the compressed air onto the surface of the desiccant. Adsorption continues until equilibrium is reached between the partial pressure of the water vapor in the air and that on the surface of the desiccant.
These dryers continuously dry compressed air by using two identical towers, each containing a desiccant bed. While one tower is on-stream drying, the other tower is off-stream being regenerated (reactivated, i.e. dried out). The towers are alternated on- and off-stream so that dry desiccant is always in contact with the wet compressed air. In this way a continuous supply of dry air downstream of the dryer is possible. The switching from one tower to the other is controlled by a solid-state controller on
either a xed time basis (standard) or a demand basis
(optional).
When a tower is placed off-line, it is slowly depressur­ized and the desiccant is regenerated. First, a blower draws in ambient air which is heated. The heated air
ows through the desiccant bed, desorbs the moisture
from the desiccant, and carries the desorbed water out of the dryer. The blower and heater are turned off when
the desiccant bed is fully heated. When congured for
cooling, a portion of the dry compressed air is diverted
from the main air ow and throttled to near atmospheric
pressure. This extremely dry, low pressure air passes through the hot off-line tower, partially cooling the desic­cant bed and reducing the dew point spike after tower change over. At the end of the cooling stage, the tower is repressurized to full line pressure. This prevents desic­cant bed movement and downstream pressure loss when the tower goes back on-line.

4.0 Installation

be required upstream of the Oil Removal Filter if heavy liquid or solid loads are present.
To ensure downstream air purity (prevent desiccant dust from traveling downstream) adequate ltration down­stream of the dryer is required. A High Temperature
Afterlter, typically rated at 450°F (232°C) operating temperature and capable of removing all desiccant nes
1 micron and larger should be installed at the dryer outlet.
DANGER — This dryer must be tted with a high efciency coalescing lter and liquid drainer that is
maintained properly. Failure to do so could result
in an in-line re.
WARNING — The afterlter, if installed, must be rated
for 450°F (232°C).
4.2 Ambient Air Temperature
Locate the dryer under cover in an area where the ambi­ent air temperature will remain between 35°F (2°C) and 120°F (49°C).
NOTE: If dryer is installed in ambients below 35°F (2°C), low ambient protection requiring heat tracing
and insulation of the prelter bowls, auto drains and/
or sumps, and lower piping with inlet switching and purge/repressurization valves is necessary to prevent condensate from freezing. If installing heat tracing, ob­serve electrical class code requirements for type of duty
specied. Purge mufers and their relief mechanisms
must be kept clear from snow and ice buildup that could prevent proper discharge of compressed air.
4.3 Location and Clearance
Install the dryer on a level pad. Ensure the dryer is level by grouting or shimming as necessary. Holes are provided
in the dryer base members for oor anchors. Securely anchor the dryer frame to the oor. Allow 24 inches clear-
ance on all sides of the dryer for servicing. Provide ad-
equate clearance for prelter element, afterlter element
and heater element replacement. Provide protection for the dryer if it is installed where heavy vehicles or similar portable equipment is likely to cause
damage.
4.1 System Arrangement
Install the dryer downstream of an aftercooler, separator,
receiver, and high-efciency oil-removing lter(s) so that
the dryer inlet air is between 40°F (4.4°C) and 120°F (49°C) and contains no liquid water or oil. Liquid water and/or inlet air temperatures above 100°F (37.8°C) can reduce drying capacity. Contact your local distributor for information on proper dryer sizing at elevated inlet air temperatures.
Adequate ltration is required upstream of the dryer in
order to protect the desiccant bed from liquid and solid contamination. Use an Air Line Filter in systems sup­plied by a non-lubricated (oil-free) air compressor. In systems supplied by a lubricated air compressor, use a
High Efciency Oil Removal Filter. A coarser lter will
2
4.3.1 Blower Installation (
NOTE: Field installation of the purge blower to the dryer
unit is required on model sizes 3200, 3600, and 4300. Refer to Figure 3b for assistance in connecting the purge blower to the dryer unit.
1. Align and install the purge blower skid to the dryer
Models 3200 through 4300 only)
unit utilizing the expansion joint provided (shipped mounted to the purge blower). Use the mounting
hardware (nuts, bolts, ange gasket, etc.) provided
to connect the purge blower skid to the dryer unit.
Ensure the purge blower skid is level by grouting or shimming as necessary. Holes are provided in the
purge blower skid base members for oor anchors. Securely anchor the purge blower skid to the oor.
Page 5
Compressor Aftercooler Separator Receiver Prefilters Afterfilters ReceiverDesiccant Dryer
Typical System Conguration
2.
Remove all mounting bolts from blower base which MAY have been used for shipping purposes. The blower is designed to vibrate freely on its vibration pad during operation.
NOTE: The blower manufacturer cautions that the blower should not be bolted down during operation.
3. Reconnect
the blower motor power connections to the dryer unit according to the electrical drawings in the back of this manual. Be sure to follow all applicable electrical codes.
CAUTION: The blower and motor have been completely checked and operated prior to shipment from the fac­tory. After connecting the power supply to the motor, momentarily energize the blower motor starter. Blower rotation should match the indicator arrow on the blower housing. If not, disconnect power and reverse the wiring connections.
4.4 Piping and Connections
All external piping must be supplied by the user unless
otherwise specied. Refer to Figure 2 for connection
sizes. Inlet and outlet isolation valves and a vent valve are recommended so the dryer can be isolated and depressurized for servicing. The connections and pipe ttings must be rated for or exceed the maximum oper­ating pressure given on the dryer nameplate and must be in accordance with industry-wide codes. Be sure all piping is supported. Do not allow the weight of any pip-
ing to bear on the dryer or lters. Piping should be the
same size as or larger than the dryer connection. Piping smaller than the dryer connections will cause high pres­sure drop and reduce drying capacity.
If the purge exhaust piping must be extended outside the dryer area, choose a combination of diameters, lengths, and turns that limits the additional pressure drop to 1/4 psid or less. BACK PRESSURE WILL CAUSE DRYER MALFUNCTION. Consult the factory for piping details if required.
WARNING — Do not operate dryer without installed
mufers. Exhausting compressed air directly to
atmosphere will result in noise levels above OSHA
permissible levels and rapidly expanding gas could
potentially cause harm to persons or property.
Figure 1
Dryer bypass piping may be installed to allow uninter­rupted airow during servicing. If the downstream appli­cation cannot tolerate unprocessed air for short periods, install a second dryer in the bypass line.
CAUTION — Do not hydrostatically test the piping with the dryer in the system. The desiccant will be damaged if saturated with water.
4.5 Electrical Connections
WARNING — These procedures require entering
gaining access to the dryer’s electrical enclosure(s).
All electrical work must be performed by a qualied
electrical technician.
Connect the proper power supply to the dryer according to the electrical drawings in the back of this manual. Be sure to follow all applicable electrical codes.
NOTE: A disconnect switch is not provided as standard equipment and therefore, must be supplied by the cus­tomer.
Dry contacts (voltage free) are provided in the low ten­sion electrical enclosure for a remote alarm. The contact ratings are shown on the electrical drawing.
Connections to voltage-free common alarm contacts with a minimum 5-amp rating can be made at terminals TB4-1 through 3.
• Terminal TB4-3 is the common alarm connection.
• Terminal TB4-1 is the N.O.. (normally open) contact
connection.
• Terminal TB4-2 is the N.C. (normally closed) contact
connection.
• The alarm relay coil is energized when power is
supplied to the controller input terminals and there is no alarms.
• The coil is de-energized when power is removed or
when an alarm condition exists.
• The common alarm is designed to activate on:
a) either a dryer fault condition or a service reminder, or b) a dryer fault condition. This is user selectable.
3
Page 6
CENTERLINE OF
CUSTOMER DRY GAS
OUTLET CONNECTION
TOP VIEW
R
SLOT
(TYP 4 PLACES)
CENTERLINE OF
CUSTOMER WET GAS
INLET CONNECTION
SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
T
GAS OUTLET
E
(MAX)
F
G
C
D
B
A
(MAX)
H
K
N
(MAX)
P
L
S
GAS INLET
M
FACE OF CUSTOMER
WET GAS INLET
CONNECTION
FACE OF CUSTOMER
DRY GAS OUTLET
CONNECTION
R
SLOT
(TYP 4 PLACES)
TOP VIEW
SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
S
GAS INLET
T
GAS OUTLET
H
E
(MAX)
F
G
C
D
B
A
(MAX)
N
(MAX)
P
L
M
K
E
(MAX)
R
SLOTS
(TYP 4 PLACES)
TOP VIEW
SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
S
AIR INLET
T
AIR OUTLET
F
C
D
B
A
N
(MAX)
M
L
P
K
G
Dimensions and Connections – Dryer Only
Figure 2 (continued on next page)
(For construction purposes, contact factory to request certied drawings when mounted lters are included with order)
VIEW III
3200 through 4300 scfm
VIEW II
750 through 2600 scfm
4
VIEW I
500 — 600 scfm
Page 7
Dimensions and Connections
Figure 2 (continued from previous page)
DIMENSIONS IN INCHES
A 53 55 60 60 64 66 80 80 85 85 85 85 109
B 46.3/4 47.9/16 52.11/16 52.11/16 56.7/16 57.5/16 69.13/16 69.13/16 73.3/8 73.3/8 82.7/8 82.7/8 93.3/8
MODEL 500 600 750 900 1050 1300 1500 1800 2200 2600 3200 3600 4300
VIEW REF. I I II II II II II II II II III III III
C 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4
E 59 60 68 68 62 73 79 79 86 89 107 116 123
D 23.3/8 23.13/16 26.5/8 26.5/8 29.9/16 30 34.7/8 34.7/8 38.9/16 38.9/16 36.9/16 36.9/16 41.13/16
F 45.1/2 45.1/2 53.1/2 53.1/2 53.1/2 53.1/2 53.1/2 53.1/2 59.1/2 59.1/2 59.1/2 59.1/2 63.1/2
G 22.3/4 22.3/4 26.3/4 26.3/4 26.3/4 26.3/4 26.3/4 26.3/4 29.3/4 29.3/4 29.3/4 29.3/4 31.3/4
DIMENSIONS IN MILLIMETERS
L 12.11/16 13.3/16 13.7/16 13.7/16 13.3/16 13.3/16 15.5/8 15.5/8 17.1/4 17.1/4 14.9/16 16.9/16 16.1/4
K 3 3 8 8 8 8 8 8 7.1/4 7.1/4 15.7/8 15.7/8 15.7/8
H 1.1/4 1.1/4 3.1/4 3.1/4 5.15/16 5.15/16 4.3/8 4.3/8 3/4 5 2
M 96.15/16 100.7/16 100.11/16 100.11/16 99.13/16 104.13/16 101.7/8 101.7/8 115.7/8 115.7/8 115.13/16 122.1/16 118.1/2
N 105 108 114 114 113 11 8 116 11 6 128 128 128 134 130
P 13.3/16 14.3/16 15.3/4 15.3/4 16.3/4 17.3/4 20.3/4 20.3/4 22.1/4 22.1/4 26.1/2 27.1/2 30.1/2
S 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE
R 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4
T 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE 6 FLANGE
WT/LBS 1,900 2,200 2,500 2,600 3,000 3,600 5,400 5,500 8,100 8,200 9,400 9,900 12,350
MODEL 500 600 750 900 1050 1300 1500 1800 2200 2600 3200 3600 4300
A 1346 1397 1524 1524 1626 1676 2032 2032 2159 2159 2159 2159 2769
B 1187 1208 1338 1338 1434 1456 1773 1773 1864 1864 2106 2106 2372
C 32 32 32 32 32 32 32 32 32 32 32 32 32
VIEW REF. I I II II II II II II II II III III III
D 594 604 677 677 750 761 886 886 980 980 929 929 1062
E 1491 1531 1734 1734 1580 1862 2009 2009 2186 2256 2708 2955 3132
F 1156 1156 1359 1359 1359 1359 1359 1359 1511 1511 1511 1511 1613
G 578 578 679 679 679 679 679 679 756 756 756 756 806
L 322 335 341 341 335 335 397 397 438 438 370 421 413
K 76 76 203 203 203 203 203 203 184 184 403 403 403
H 32 32 83 83 151 151 111 111 19 127 51
M 2462 2551 2557 2557 2535 2662 2588 2588 2943 2943 2942 3100 3010
N 2664 2753 2903 2903 2870 2997 2946 2946 3246 3246 3246 3404 3313
P 335 360 400 400 425 451 527 527 565 565 673 699 775
S 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE
R 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32
T 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE 6 FLANGE
WT/KGS 862 998 1,134 1,179 1,361 1,633 2,449 2,495 3,674 3,719 4,264 4,491 5,602
5
Page 8
• For the common alarm to activate on either a dryer
fault condition or a service reminder, the jumper at
JP6 is removed. This is the default conguration.
• To have the common alarm activate on a dryer fault
condition only, the jumper at JP6 is installed.
NOTE: Before turning high voltage on to the dryer, an ohmic test should be performed on the heater ele­ments to insure they are dry before proceeding with start-up. This should be done after extended shut downs and long delays between delivery and start­up. Connect one lead of a megger to an unpainted surface of the control panel or dryer frame. Connect the other lead to each phase on the load side of the contactor. Adjust the megger to the 1500 volt setting. Perform the ohmic test on each zone of the heaters. A minimum value of 500k ohms must be obtained.
CAUTION - Failure to ohmic test heaters after ex­tended periods may cause heater failure.
4.5.1 RS-232 Connections
RS-232 connections can be made at the 3-pin connector labeled J3 and located at the upper left-handed corner of the control board. A cable for this connection can be purchased through your distributor.
3. Refer to Table 1 for desiccant quantity per tower.
When using Table 1 you will nd the desiccant quan-
tities listed in layers. Each layer will vary in depth due to the type, quantity and purpose of the desic-
cant. Layer 1 must be installed rst at the bottom of
the vessel followed by layer number 2 etc., until the complete charge of desiccant has been installed.
4. Utilizing an appropriate sized funnel, ll each desic­cant tower as follows:
a. Install the required quantity of tabular support or
activated alumina in layer 1 of each tower.
b. Level layer 1 and each subsequent layer of desic-
cant as added to each chamber.
c. Finish lling each tower with desiccant until all
desiccant has been installed. LIGHT tapping on the tower sides with a soft-face mallet should yield additional free space to allow installation of all desiccant required. DO NOT TAMP OR RAM DESICCANT.
5. Clean the ll port closure. Replace the ll plug using Teon tape or another pipe thread sealant suitable for compressed air service. Reinstall ll port ange
cover (where applicable) in each desiccant tower.
4.6 Initial Desiccant Charge
Blower purge type regenerative dryers use activated alumina as the desiccant in the dryer towers.
Models 500 through 1050 are shipped with activated alumina (1/8” bead) in the dryer towers. Desiccant is shipped loose with all other standard models.
All desiccant shipped loose must be added to the dryer chambers before the dryer is put into service
Refer to TABLE 1, DESICCANT REQUIREMENTS for desiccant type and quantity per tower.
TO ADD DESICCANT
WARNING — The following procedure provides in­structions for adding the initial desiccant to the tow­ers. If replacing desiccant, refer to the “Procedure for Desiccant Charge Replacement” in Section 7.0.
1. Verify pressure gauges of both towers indicate 0 psig. If not, depressurize the towers according to the shutdown instructions in Section 6.
2. Remove the pipe plug or ll port ange cover (where applicable) from the desiccant ll port at the top of each tower. Refer to Figure 3 for the ll port location.
CAUTION – Pouring desiccant creates a ne dust;
safety goggles, gloves and a dust mask should be worn by personnel installing desiccant. Refer to the Material Safety Data Sheet that accompanies desic­cant shipped loose for more complete information.
CAUTION – Do not tamp the desiccant in the towers. Tamping damages desiccant and causes dusting.
TABLE 1 DESICCANT REQUIREMENTS (Quantity per Tower)
Model
500 354 AA-4
600 453 AA-4
750 590 AA-4
900 590 AA-4
1050 710 AA-4
1300 48 AA-25 876 AA-4
1500 92 AA-25 1167 AA-4
1800 92 AA-25 1167 AA-4
2200 161 AA-25 1706 AA-4
2600 161 AA-25 1706 AA-4
3200 258 AA-25 2119 AA-4
3600 258 AA-25 2353 AA-4
4300 719 TS-50 146 AA-25 2679 AA-4
AA = Activated Alumina TS = Tabular Support
Layer #1 Layer #2 Layer #2
(lbs.) (p/n) (lbs.) (p/n) (lbs.) (p/n)
6
Page 9

5.0 Instrumentation

The following instrumentation helps in monitoring dryer operation and performance. Instruments which are available as options are so noted.
Blower Purge Air dryers are rated NEMA 4 and include the following:
• Solid State Controls
• Chamber Pressure Gauges
• Purge Flow Pressure Gauge
• Energy Management (Option A)
• Energy Management System & Dew Point Transmitter
(Option B)
5.1 Controls
The solid-state dryer controls are located in a polycarbonate, NEMA Class 4/4X, IP66 rated electrical enclosure mounted to a center panel located between the two desiccant towers. Control features include:
• 15 LED’s to indicate operating status and fault
conditions.
• Two line text display to provide status and diagnostic
messages.
• Upon power loss, dryer “fails safe” (inlet valve
remains in position). On power recovery, controller resumes where power was lost.
5.5 Dew Point Transmitter
This option monitors and displays outlet pressure dew points and provides an alarm signal if the dew point exceeds user-specified set point. Recommended calibration interval is 12 months. Contact the service department for details.
Operation – The dew point is measured at the dryer operating pressure and is displayed in the operator interface. If the dew point is outside of the temperature range, the display will indicate an over-range (high dew point) or under-range (low dew point) condition. A defective sensor assembly or an electronics malfunction could also cause the transmitter to indicate under-range.
5.2 Chamber Pressure Gauges
A gauge mounted on the gauge panel indicates which chamber is on-stream and which is regenerating. The gauge for the onstream tower indicates operating pressure; the gauge for the regenerating tower indicates 0 psig.
5.3 Purge Flow Pressure Gauge
A gauge mounted on the gauge panel of the dryer indicates purge air pressure.
5.4 Energy Management System
The optional Energy Management System (EMS) automatically adjusts dryer operation to compensate for changes in operating conditions. Air samples are continuously taken from the on-stream tower and passed over a moisture probe which senses both temperature and relative humidity. The moisture content of the air within the desiccant bed is then precisely determined. The on-stream tower will not depressurize and regenerate until a predetermined set point has been reached. This elimination of unnecessary regeneration reduces energy consumption and extends dryer desiccant and component life.
7
Page 10
ENERGY MANAGEMENT
SENSOR LOCATION
(OPTIONAL)
TOP VIEW
PURGE INLET CHECK VALVE
HEATER TEMP
THERMOCOUPLE
(CENTER END IN PIPE)
(OPPOSITE SIDE)
HEATER OVERTEMP RTD
PURGE
HEATER WITH
INSULATION
PURGE SUCTION
FILTER SILENCER
PURGE BLOWER
AND MOTOR
ASME RELIEF VALVE
OUTLET CHECK VALVE
DESICCANT
FILL PORT
REAR VIEW
HOT PIPE INSULATION
ASME CODE TAG
TOWER INLET VALVE
REPRESS VALVE
PURGE PRESSURE GAUGE
RIGHT TOWER PRESSURE GAUGE
CONTROL ENCLOSURE
LEFT TOWER
PRESSURE GAUGE
PRESSURE REGULATOR
& PILOT AIR FILTER
DEWPOINTER
(OPTIONAL)
TOWER PURGE
EXHAUST VALVE
TOWER
DEPRESS VALVE
FRONT VIEW
HIGH TENSION ENCLOSURE
TOWER INSULATION (OPTIONAL)
DESICCANT DRAIN PORT
TOWER BLOW­DOWN VALVE
Figure 3
General Layout Drawing
(Models 500 through 600)
8
Page 11
ENERGY MANAGEMENT
SENSOR LOCATION (OPTIONAL)
REPRESS VALVE
TOP VIEW
HEATER TEMP
THERMOCOUPLE
(CENTER END IN PIPE)
(OPPOSITE SIDE)
HEATER OVERTEMP RTD
PURGE
HEATER WITH
INSULATION
PURGE SUCTION FILTER SILENCER
PURGE BLOWER
AND MOTOR
ASME RELIEF VALVE
OUTLET CHECK VALVE
REAR VIEW
HOT PIPE INSULATION
PURGE INLET CHECK VALVE
ASME CODE TAG
CHAMBER INLET VALVE
PURGE PRESSURE GAUGE
DESICCANT
FILL PORT
LEFT TOWER
PRESSURE GAUGE
PRESSURE REGULATOR
& PILOT AIR FILTER
DEWPOINTER
(OPTIONAL)
TOWER PURGE
EXHAUST VALVE
TOWER
DEPRESS VALVE
FRONT VIEW
Figure 3a
General Layout Drawing
(Models 750 through 2600)
RIGHT TOWER PRESSURE GAUGE
CONTROL ENCLOSURE
HIGH TENSION ENCLOSURE
TOWER INSULATION (OPTIONAL)
DESICCANT DRAIN PORT
TOWER BLOW­DOWN VALVE
9
Page 12
ENERGY MANAGEMENT
SENSOR LOCATION
(OPTIONAL)
TOP VIEW
HEATER INLET TEMPERATURE SWITCH
OUTLET CHECK VALVE
ASME RELIEF VALVE
REPRESS
VALVE
HEATER TEMP
THERMOCOUPLE
(CENTER END
IN PIPE)
(OPPOSITE SIDE)
HEATER
OVERTEMP RTD
PURGE
HEATER WITH
INSULATION
PURGE SUCTION FILTER SILENCER
PURGE BLOWER
THROTTLING VALVE
PURGE BLOWER
AND MOTOR
DESICCANT
FILL PORT
REAR VIEW
HOT PIPE INSULATION
PURGE INLET CHECK VALVE
TOWER INLET VALVE
PURGE PRESSURE GAUGE
RIGHT TOWER PRESSURE GAUGE
10
LEFT TOWER
PRESSURE GAUGE
PRESSURE REGULATOR
& PILOT AIR FILTER
DEWPOINTER
(OPTIONAL)
TOWER PURGE
EXHAUST VALVE
TOWER BLOW-
DOWN VALVE
FRONT VIEW
Figure 3b
General Layout Drawing
(Models 3200 through 4300)
CONTROL ENCLOSURE
HIGH TENSION ENCLOSURE
TOWER INSULATION (OPTIONAL)
DESICCANT DRAIN PORT
TOWER DEPRESS VALVE
Page 13

6.0 Operation

6.1 Controls
A solid-state controller controls valve and heater opera­tion, monitors all critical operating conditions, and indi­cates operating status on a 2-line LCD display operator interface. The controller receives input data from pres­sure switches, temperature sensors and the operator interface. The operator interface displays information about the dryer operating status and is used to change the dryer operating mode.
6.2 Operating Modes
6.2.1 Automatic and Manual Advance
The drying and regeneration cycles are divided into discrete steps. The operator selects either one of the automatic advance modes (Energy Management, Dew Point Control, or Fixed Cycle) or manual advance mode (Test Cycle) through the operator interface.
Selecting any of the automatic advance modes enables a timer in the controller to advance the program step-by­step according to the programmed schedule.
Setting up the controller for manual advance disables the timer and the operator can advance the program one step at a time. This mode is used for diagnostic purposes.
6.2.2 Fixed, Energy Management or Dew Point
Control Operation
The operator interface is used to select either Fixed, Energy Management or Dew Point Control operation. In Fixed Cycle operation, each tower is on-line (drying) for a
xed time period regardless of the operating conditions.
In Energy Management or Dew Point Control operation, a tower remains on-line until the desiccant bed has been fully utilized. For lower than designed moisture loads, this results in longer drying cycles, longer time between regenerations and, therefore lower energy consumption. Energy Management or Dew Point Control operation are optional features.
6.3 Operating Sequence Description
1. Left Tower Drying – Right Tower Regenerating At the start of the Left Tower Drying cycle, Left Inlet
Valve V1 opens, Right Inlet Valve V2 closes to iso-
late the two towers. Wet, compressed air ows up
through the left tower where it is dried. The dry air exits the dryer through the Left Outlet Check Valve V7.
Next, the Right Depressurization Valve V10 is
opened and the right tower is slowly depressurized. Air exits through exhaust mufer M2.
After the right tower has depressurized, the Right
Purge Valve V4 is opened and the Blower M and Heater H1 are energized. The heated air ows through the Right Purge Check Valve V6, down through the right tower, and exits through the Right Purge Valve V4. The Blower intake air is ltered to keep dust and dirt from entering the dryer. The Blower M and Heater H1 are de-energized when the temperature at the bottom of the right tower, as sensed by the Right Tower Temperature Sensor RTD2, reaches the Heat Termination set point. This indicates that the bed has been fully heated.
NOTE: Blower will continue to run briey at the end
of the Heating Step to sweep residual heat from the heater.
The Repressurization Valve V11 is opened. A portion
of the dry air from the left tower now ows through
Repressurization Valve V11. This air is throttled to near atmospheric pressure by Repressurization/
Sweep Orice O2. The dry, low pressure air ows
down through the right tower cooling the desiccant bed, and exits through the Right Tower Purge Ex­haust Valve V4.
The Cooling Step continues until:
a) the right tower bed temperature falls to 150°F
or,
b) it is time to repressurize the right tower,
whichever occurs rst.
NOTE: In xed cycle, the bed will normally be
partially cooled because the repressurization step will occur before the bed temperature can fall to 150°F.
NOTE: In Energy Management or Dew Point Con-
trol, as the drying time extends beyond 4 hours, additional cooling time becomes available thus the cooling step will frequently terminate based on tem­perature providing complete bed cooling.
At the end of the Cooling Step, the Right Tower Purge
Exhaust Valve V4 is closed. The right tower slowly repressurizes to full line pressure and is ready to go back on-line.
NOTE: Bed cooling can be disabled by moving JP4
to the “ON” position.
2. Right Tower Drying – Left Tower Regenerating At the start of the Right Tower Drying cycle, Right
Inlet Valve V2 opens, Left Inlet Valve V1 closes to
isolate the two towers. Wet, compressed air ows
up through the right tower where it is dried. The dry air exits the dryer through the Right Outlet Check Valve V8.
Next, the Left Depressurization Valve V9 is opened
and the left tower is slowly depressurized. Air exits through exhaust mufer M1.
11
Page 14
SET @ 165 PSIG
DRY GAS
OUTLET
LEFT
V7 V8
F1 O1 O2
M
PI3
PI1 PI2
SET @
45 PSIG
1PS
SET @ 5 PSIG
3PS
EXH.
SET @ 176°F
RTD 1
(RTD4/HS1)
ENERGY MGMT OPTION
SOL 'F'
2
SOL 'C'
V12 V13
H1
3
1
V11
1TC
SET @ 370°F
RTD 3
SET @ 650°F
SOL 'D'
SOL 'E'
V14
F2
DPA
DEWPOINTER OPTION
V6V5
SOL 'G'
PR&G
SET @
45 PSIG
SET @
5 PSIG
SET AT 100 PSIG
2PS
4PS
SET @ 176°F
RTD 2
CHAMBERCHAMBER
RIGHT
REGENDRYING
WET GAS
INLET
V9
M1
BD1 BD2
V3
V4
V1 V2
NOTES SYMBOLS ARE PER ANSI Y32.10 "GRAPHIC SYMBOLS FOR FLUID POWER DIAGRAMS."
1. AS SHOWN FLOW DIRECTION IS:
2.
SOLENOID VALVES 'B', 'D', & 'G' ARE SHOWN ENERGIZED,
3. SOLENOID VALVES 'A', 'C', 'E', & 'F' ARE SHOWN DE-ENERGIZED.
4.
V10
INDICATES OPTION
M2
LEFT CHAMBER DRYING RIGHT CHAMBER REGEN PILOT GAS LINE
Figure 4
Sequence of Operation — Fixed Cycle Operation
Left Chamber Drying – Right Chamber Regenerating (shown)
(continued on next page)
SOL 'A'
SOL 'B'
12
Page 15
After the left tower has depressurized, the Left Purge
P
EMS
LEFT
TOWER
RIGHT
TOWER
Valve V3 is opened and the Blower M and Heater H1 are energized. The heated air ows through the
Left Purge Check Valve V5, down through the left tower, and exits through the Left Purge Valve V3.
The Blower intake air is ltered to keep dust and dirt
from entering the dryer. The Blower M and Heater H1 are de-energized when the temperature at the
bottom of the left tower, as sensed by the Left Tower Temperature Sensor RTD1, reaches the Heat Ter­mination set point. This indicates that the bed has been fully heated.
The Repressurization Valve V11 is opened. A portion
of the dry air from the right tower now ows through
Repressurization Valve V11. This air is throttled to near atmospheric pressure by Repressurization/
Sweep Orice O1. The dry, low pressure air ows
down through the left tower cooling the desiccant bed, and exits through the Left Tower Purge Exhaust Valve V3.
The Cooling Step continues until:
a) the left tower bed temperature falls to 150°F
or,
b) it is time to repressurize the left tower,
whichever occurs rst.
6.3.1 Energy Management Control (optional)
Operation of the Energy Management Control cycle is
identical to the xed cycle except the cycle is extended
until the desiccant bed in the on-line tower has been fully utilized. The off-line tower is regenerated and remains in a stand-by mode after being repressurized.
Figure 5 shows the air sampling system for the Energy Management System – EMS option. A 3-way pilot valve directs an air sample from the drying tower to the EMS sensor. The EMS sensor detects the relative humidity and temperature of the air sample. The air sample then exhausts to atmosphere. The drying tower remains on­line until the moisture front arrives at the sensor.
NOTE: In xed cycle, the bed will normally be
partially cooled because the repressurization step will occur before the bed temperature can fall to 150°F.
NOTE: In Energy Management or Dew Point Con-
trol, as the drying time extends beyond 4 hours, additional cooling time becomes available thus the cooling step will frequently terminate based on tem­perature providing complete bed cooling.
At the end of the Cooling Step, the Left Tower Purge
Exhaust Valve V3 is closed. The left tower slowly repressurizes to full line pressure and is ready to go back on-line.
NOTE: Bed cooling can be disabled by moving JP4
to the “ON” position.
Figure 5
Optional Moisture Sensing
Energy Management System (EMS)
13
Page 16
6.4 Control Board Jumpers
In the upper left hand corner of the control board there are eight two-pin jumpers labeled JP1 through JP8. Only six of the eight jumper pairs are utilized. Pairs JP7-JP8 are used for factory settings and testing. NOTE: Do
not install jumpers in the ON position on pairs JP7 through JP8. The jumper is a removable bridge that is
used to make or break continuity between two pins that form a pair. When installed in the ON position, the jumper is place on both pins of the pair and continuity between the pins is established. When installed in the OFF posi­tion, the jumper is removed or stored on a single pin and continuity is broken. Jumper functions are as follows:
7. JP7 – Download Language Text Jumper JP7 is factory installed in the OFF position
to disable Language Text download. The jumper is installed in the ON position to allow for language text download due to either language corrections or new language installation.
8. JP8 – Set Up Jumper JP8 is factory installed in the OFF position
to disable access to “factory” set up screens. The jumper is installed in the ON position during nal
inspection at the factory to set controller to match customer requirements.
1. JP1 – Dryer Type Jumper JP1 is used to select the dryer type congu-
ration. It is installed in the ON position for Blower
Purge dryer conguration.
2. JP2 – Energy Management Jumper JP2 is installed in the ON position when an
Energy Management sensor is installed. The jumper is installed in the OFF position when no Energy Management sensor is installed.
3. JP3 – Dew Point Transmitter Jumper JP3 is installed in the ON position when a
Dew Point Transmitter is installed. The jumper is installed in the OFF position when no Dew Point Transmitter is installed.
NOTE: “Energy Management” can co-exist with the
dew point transmitter option. Dryer control based on the ENERGY MANAGEMENT or DEWPOINT CONTROL is selected on Screen 1 of the Set Up Mode.
If DEWPOINT CONTROL is not selected then the
dew point signal does not control the dryer cycle but still serves a monitoring and alarm function.
4. JP4 – Cooling Cycle Jumper JP4 is installed in the ON position to disable
the Cooling Cycle. The jumper is installed in the OFF position to enable a Cooling Cycle.
5. JP5 – Switching Failure Jumper JP5 is installed in the ON position to enable
Switching Failure. The jumper is installed in the OFF position if Switching Failure is disabled.
6. JP6 – Common Alarm Jumper JP6 is installed in the OFF position to en-
able both the dryer fault alarms and service alarms to activate the common alarm. This is the default
conguration. Install jumper JP6 in the ON position
if the common alarm is to activated by a dryer fault alarm only.
6.5 Operator Interface
Refer to Figure 6 , Front Panel Overlay for information regarding the location and function of the LEDs, switches, and text display.
6.5.1 Front Panel LED’s
• Power On - green
• Alarm - red
• Service / Maintenance reminder - amber
• Filters (pre, after, and pilot) service / maintenance
reminders - amber
• Inlet switching and purge / repressurization valve sta­tus (On = valve open; Off = valve closed) - green
• Left and right tower status (heating) - amber
• Left and right tower status (drying) - green
• Left and right tower pressure switch status (On =
switch closed; Off = switch open) - green
6.5.2 Front Panel Switches
The front panel contains four momentary-contact push­button switches. Refer to Figure 6, Front Panel Overlay for the appropriate icon associated with each switch. Pushing on the overlay icon actuates the switch.
Data Display Switch
This switch is used to step through the display screens.
Select Switch
This button is located to the left of the text display window. Refer to the Front Panel Operation Section for additional information.
ENTER Switch
This button is located to the right of the text display window. Refer to the Front Panel Operation Section for additional information.
Alarm Reset Switch
This button is normally used to reset an alarm or service reminder. Refer to the Front Panel Operation Section for additional information.
NOTE: Jumpers JP7 and JP8 are used by the fac-
tory during nal inspection to download language
text and to enable ‘factory’ set-up screens.
14
Page 17
Left Tower Drying LED
Left Purge Valve LED On=valve open Off=valve closed
Left Inlet Valve LED On=valve open Off=valve closed
Left Tower Heating LED
Filter Service / Maintenance LED
Vacuum Fluorescent Text Display
Select switch
Power On LED
Data Display Switch
Communications Icon
Filter Service / Maintenance LED
Filter Service / Maintenance LED
Right Tower Pressure Switch LED: On=Tower pressurized
Right Tower Drying LED
Right Purge Valve LED On=valve open Off=valve closed
Right Tower Heating LED
Right Inlet Valve LED On=valve open Off=valve closed
Enter Switch
Maintenance / Service Reminder LED
Alarm LED
Reset Switch for Alarm
Left Tower Pressure Switch LED: On=Tower Pressurized
RS232
6.5.3 Front Panel Operation
1. There are five operating modes for the Heated
2. Each Mode is described below.
6.5.4 Program Mode
1. Press and hold and for 3 seconds to enter
2. Program Mode is comprised of the screens that are
3. There are three (3) ways to exit Program Mode.
Front Panel Overlay
Desiccant Dryer Control. a. Program Mode b. Setup Mode c. Alarm & Service Mode d. Display Mode e. Test Mode
Program Mode.
described below.
a. Press after making the selection in the nal
screen.
b. At any screen, press and hold for 3 sec-
onds.
c. The controller automatically exits Program Mode
if no button is pressed within 60 seconds.
Figure 6
4. Upon exiting Program Mode the controller will switch
to Display Mode.
Screen 1: Select the Language
1. Press to scroll through the choices: ENGLISH,
FRANCAIS and ESPANOL.
2. When nished, press to save the selection and
move to next screen.
ENGLISH
Screen 2: Select the Service Level
SERVICE LEVEL NORMAL
1. Press to toggle between NORMAL and
SEVERE. a. NORMAL Service Intervals are:
i. 4000 hours for lters
ii. 8000 hours for desiccant iii. 8000 hours for valves
15
Page 18
b. SEVERE Service Intervals are:
i. 2000 hours for lters
ii. 4000 hours for desiccant iii. 4000 hours for valves
2. When nished, press to save the selection and move to next screen.
Screen 3: Reset the Timer for Filter Service
FILTER SERVICE RESET? NO
1. Press to toggle between NO and YES.
2. When finished, press to acknowledge the selection and move to next screen.
Screen 4: Reset the Timer for Desiccant Service
DESICCANT SERVICE RESET? NO
1. Press to toggle between NO and YES.
2. When finished, press to acknowledge the selection and move to next screen.
Screen 5: Reset the Timer for Valve Service
VALVE SERVICE RESET? NO
Screen 7: Set Point for Dew Point Demand Control
(This feature is only active when JP3 is “on”)
DPNT CNTL SETPT ±XX°C ±XXX°F
1. Press to increment the setting to the desired value. a. Standard set point is
-30°C -22°F
.
b. The allowable range of values is from
-80°C -112°F
+10°C +50°F
to
in 5°C/9°F
increments.
NOTE: Must be set “drier” than Dew Point Sensor
Alarm Set Point (screen 6).
2. When finished, press to acknowledge the selection and exit the Program Mode.
Screen 8: Set the Heat Termination Set Point
HEAT TERM SET-PT XX°C XXX°F
1. Press to increment the setting to the desired temperature value. a. Refer to P&ID diagrams in the back of this manual
for Heat Termination set points (see set point values for RTD1 and RTD2).
b. The allowable range of values are:
60° - 160°C 140° - 320°F
in 10°C increments.
1. Press to toggle between NO and YES.
2. When nished, press to acknowledge the selec­tion and move to next screen.
Screen 6: Set Alarm Point for the Dew Point
Sensor (This feature is only active when
JP3 is “on”)
DEWPOINT ALARM ±XX°C ±XXX°F XX MIN SW DELAY
1. Press to increment the setting to the desired value. a. Standard set point is
-20°C -4°F
.
b. The allowable range of values is from
-80°C -112°F
+10°C +50°F
to
in 5°C/9°F
increments.
2. When nished, press to acknowledge the se­lection and scroll to the switchover delay set point screen. a. Standard set point is b. The allowable range of values are
60 MIN
.
30 to 120 MIN
in 10 minute increments.
3. When nished, press to acknowledge the selec­tion and move to next screen. Exit Program Mode when there are no more active screens to display.
2. When nished, press to acknowledge the selec­tion and move to next screen. Exit Program Mode when there are no more active screens to display.
Screen 9: Set the Sweep Termination Set Point
SWEEP TERM SET-PT XX°C XXX°F
1. Press to increment the setting to the desired temperature value.
The allowable range of values are:
48° - 60°C 118° - 150°F
in 2°C increments.
2. When nished, press to acknowledge the selec­tion and move to next screen. Exit Program Mode when there are no more active screens to display.
Screen 10: Set Points for Energy Management (This feature is only active when JP2 is “on”)
ENRGY MGMT SETPT XX%RH XX MBAR .XXX PSI
1. Press to increment the setting to the desired maximum RH value. a. Factory set point is
60%RH
. The factory setting
should not require adjustment.
b. The allowable range of values are
20 to 80%RH
in 5% increments.
16
Page 19
2. When nished, press to acknowledge the selec­tion and scroll to the pressure set point screen.
3. Press to increment the setting to the desired maximum vapor pressure value.
a. Standard set point for a -40°F dew point dryer
16 MBAR (0.232 PSI)
.
is
NOTE: Standard set point for a -100°F dew point
dryer
b. The allowable range of values
3 to 34 MBAR (0.044 to 0.493 PSI)
4 MBAR (0.058 PSI)
is
.
in
is
1 MBAR
increments.
c. This setting may be eld adjusted to increase or
decrease the outlet dew point at tower switch­over.
4. When nished, press to acknowledge the selec­tion and move to next screen.
Screen 11: Set Points for High Humidity Alarm (This feature is only active when JP2 is “on”)
HIGH HUMIDITY XX%RH XX MBAR .XXX PSI XX MIN SW DELAY
1
. Press to increment the setting to the desired
maximum RH value. a. Factory set point is
75%RH
. The factory setting
should not require adjustment.
b. The allowable range of values are
20 TO 80%RH
in 5% increments.
NOTE: Value must be set above Energy Manage-
ment Maximum RH Value Set Point (screen 9).
2. When nished, press to acknowledge the selec­tion and scroll to the pressure set point screen.
5. When nished, press to acknowledge the selec­tion and move to next screen. Exit Program Mode when there are no more active screens to display.
6.5.5 Setup Mode
1. Press and hold for 3 seconds to enter Setup Mode.
2. Setup Mode is comprised of the screens that are described below.
3. There are two ways to exit Setup Mode.
a.
Press after making the selection in Screen 1.
b. The controller automatically exits Setup Mode if
no button is pressed with 60 seconds.
4. One of two things will happen upon exiting Setup Mode. a. The controller will switch to Display Mode if
ENERGY MANAGEMNT, FIXED CYCLE or DEWPOINT CONTROL is selected.
b. The controller will switch to Test Mode if TEST
CYCLE is selected.
Screen 1: Select the Cycle Type
CYCLE TYPE ENERGY MANAGEMNT
1. Press to scroll through the choices: a. ENERGY MANAGEMNT (displayed only when
JP2 is in the ON position)
b. DEWPOINT CONTROL (displayed only when JP3
is in the ON position) c. FIXED CYCLE d. MANUAL CYCLE
2. When nished, press to save the selection and exit the Setup Mode.
3. Press to increment the setting to the desired maximum vapor pressure value.
a. Factory set point for a -40°F dew point dryer is
24 MBAR (0.348 PSI)
.
NOTE: Factory set point for a -100°F dew point
dryer is
5 MBAR (0.073 PSI)
.
b. The allowable range of values is
3 to 34 MBAR (0.044 to 0.493 PSI)
in 1 MBAR incre-
ments.
NOTE: Value must be set above Energy Man-
agement Maximum Vapor Pressure Set Point (screen 9).
4. When nished, press to acknowledge the se­lection and scroll to the switchover delay set point screen. a. Factory set point is b. The allowable range of values are
60 MIN.
.
30 to 120 MIN
in 10 minute increments.
17
Page 20
6.5.6 Alarm & Service Mode
1. Alarm & Service Mode is active when the controller is in Display Mode. It is not active in Program Mode, Setup Mode, or Test Mode.
2. Local alarm consists of a blinking alarm LED and an alarm message display.
3. Alarm messages have priority over Service messages. Service messages have priority over Display Messages.
4. After an alarm condition has been corrected, if:
a. Alarm is “self-clearing” then,
i. The alarm LED stops blinking (LED on); the
alarm message continues to be displayed.
ii. The alarm reset button must be depressed to
clear the alarm LED (LED off) and the alarm message.
b. Alarm must be manually reset, then:
i. The alarm LED continues to blink and the
alarm message continues to be displayed.
ii. The alarm reset button must be depressed
to:
1. Clear the alarm LED (LED off)
2. Clear the alarm message and
3. Restart the dryer cycle.
5. When an alarm condition has not been corrected
and the “alarm reset” button is pressed, the alarm
will not clear except as follows: a. The alarm conditions will clear for 5 seconds,
then reappear if the alarm condition persists, this applies to the following alarms: i. Heater: High Inlet Temperature. ii. Heater: Low Temperature iii. Humidity Sensor: High Humidity Alarm iv. Humidity Sensor: Under-Range or Over-
Range Alarm v. Dew Point Sensor: High Dew Point Alarm vi. Dew Point Sensor: Under-Range or Over-
Range Alarm
6. There are three alarms for each tower that are triggered by the tower pressure switches. These alarms can occur in any operating mode (Manual, Fixed, Energy Management, or Dew Point Demand Cycle).
Following is a brief description of each alarm.
a. Left or Right tower, drying, low pressure
i. Drying tower pressure switch is open during
the drying cycle.
b. Left or Right tower, regenerating, high pressure
i. Regenerating tower pressure switch is closed
while purge valve is open (after an initial time delay).
c. Left or Right tower, regenerating, low pressure
i. Regenerating tower pressure switch is open
at the end of the regenerating cycle.
d. On alarm condition, the blower and heater are
de-energize, the cycle sequence is stopped, a local alarm is displayed and the common alarm relay is de-energized.
e. These alarms are self-clearing.
7. Heater High Inlet Temperature a. Model sizes 3200, 3600 and 4300 are equipped
with a temperature switch located in the piping between the blower and heater.
b. If during the Heat Cycle this temperature switch
opens, indicating a rise in temperature above the factory setting (refer to Electrical Schematic drawings at the back of this manual for set point), an alarm is activated.
c. On alarm condition, the blower and heater are
de-energized, the cycle sequence is stopped, a local alarm is displayed and the common alarm relay is de-energized.
d. This alarm must be manually reset.
8. The dryer is equipped with RTD temperature sensors. There are out of range alarms for each.
a. The standard left tower, right tower, and heater
RTDs (RTD1, RTD2, RTD3) are scaled from
-20°F(-28°C) to 890°F (477°C), “Out of Range”
conditions are as follows: i. Over-range - temperature above 850°F
(454°C)
ii. Under-range - temperature below -20°F
(-28°C)
iii. NOTE: The controller will annunciate a
“Heater Overtemperature” alarm in lieu of an “Over Range” alarm when the heater sensor
is disconnected.
b. The Energy Management RTD4 is scaled from
-20°F(-28°C) to 429°F(220°C), “Out of Range”
conditions are as follows:
i. Over-range - temperatures above 400°F
(204°C)
ii. Under-range - temperatures below -20°F (-
28°C)
c. On alarm condition, a local alarm is displayed and
the common alarm relay is de-energized.
d. Over-range and Under-range alarms are self-
clearing.
18
Page 21
ALARM MESSAGES
LEFT TOWER ALARMS RIGHT TOWER ALARMS OTHER ALARMS
ALARM LEFT TOWER DRYING LOW PRESSURE
ALARM LEFT TOWER REGENERATING HIGH PRESSURE
ALARM LEFT TOWER REGENERATING LOW PRESSURE
ALARM LEFT TOWER TEMP UNDER-RANGE
ALARM LEFT TOWER TEMP OVER-RANGE
ALARM LEFT TOWER OUTLET DEW POINT
ALARM RIGHT TWR DRYING LOW PRESSURE
ALARM RIGHT TWR REGENERATING HIGH PRESSURE
ALARM RIGHT TWR REGENERATING LOW PRESSURE
ALARM RIGHT TWR TEMP UNDER-RANGE
ALARM RIGHT TWR TEMP OVER-RANGE
ALARM RIGHT TWR OUTLET DEW POINT
ALARM HEATER OVER-TEMPERATURE
ALARM HEATER LOW TEMPERATURE
ALARM ENRGY MGNT UNDER-RANGE
ALARM ENRGY MGNT OVER-RANGE
ALARM BLOWER MOTOR OVERLOAD
ALARM HEATER HIGH TEMP IN
ALARM LEFT TOWER HIGH HUMIDITY
ALARM LEFT TOWER DEW POINT UNDER-RANGE
ALARM LEFT TOWER DEW POINT OVER-RANGE
ALARM RIGHT TWR HIGH HUMIDITY
ALARM RIGHT TWR DEW POINT UNDER-RANGE
ALARM RIGHT TWR DEW POINT OVER-RANGE
19
Page 22
9. Heat Low Temperature a. RTD3 is used to detect Heater Low Tempera-
ture.
b. Alarm if the heater temperature is less than 250°F
(121°C) within 15 minutes after the Heat Cycle is initiated (15 minute delay also applies after power recovery).
c. On alarm condition, display local alarm and de-
energize common alarm relay.
d. This alarm is self-clearing.
10. Heater Over-Temperature a. RTD3 is used to detect Heater Over-Tempera-
ture.
b. Alarms anytime that the Heater temperature
exceeds 650°F (343°C).
c. On alarm condition, de-energize heat cycle, stop
cycle sequence, display local alarm and de-ener­gize common alarm relay.
d. This alarm must be manually reset.
11. Blower Overload a. Alarm condition when blower overload contact
closes.
13. Dew Point Sensor a. High Dewpoint Alarm
i. The user enters an alarm value through the
Program Mode.
ii. If the measured dew point exceeds the alarm
value, the outlet dew point alarm is indicat­ed.
b. Under-range alarm - Dew point below -148°F
(-100°C)
c. Over-range alarm - Dew point greater than
+109°F (+43°C)
d. On alarm condition,
i. Local alarm is displayed and the common
alarm relay is de-energized.
ii. If dryer is set up for Dewpoint Control, the dryer
sequence continues, but bypasses the “HOLD”
step and proceeds to tower switchover after 4 hours of drying.
iii. This alarm is self-clearing, at which time the
alarm LED stops blinking and control switches back to Dewpoint Control.
b. On alarm condition, de-energize heat cycle, stop
cycle sequence, display local alarm and de-ener­gize common alarm relay.
c. This alarm must be manually reset.
Alarms for Optional Devices
12. Energy Management ­a. High Humidity Alarm:
i. Measured moisture level exceeds the air alarm
value entered through the Program Mode.
b. Humidity Sensor:
i. Under-range: RH% < -15% ii. Over-range: RH% > 115%
c. RTD:
i. Over-range: Temperature above 448°F
(231°C) ii. Under-range: Temperature below -20°F (-28°C)
d. On alarm condition:
i. Local alarm is displayed and the common
alarm relay is de-energized. ii. If the dryer is set up for Energy Management
Control, the dryer sequence continues, but
bypasses the “HOLD” step and proceeds to
tower switchover after 4 hours of drying. iii. This alarm is self-clearing, at which time the
alarm LED stops blinking and control switches
back to Energy Management control.
20
Page 23
Service Due Messages
14. There are two service levels (normal and severe) as described in Program Mode. Each service level
has preset time intervals for servicing the lters,
desiccant, and valves. Time continues to accumulate as long as power is supplied to the controller, whether the controller is switched on or off.
When a service time interval expires (see also 14.d
below), the controller operates as follows.
a. The service LED blinks and the appropriate
service message is shown on the text display.
i. When the service interval for lters has expired
(see also d below), the three lter LED’s also
blink.
b. The dryer continues to cycle normally. The LED’s
for the valve’s, pressure switches, and desiccant towers are not used for service indication.
c. Press the Reset button to extinguish the service
LED and to clear the service message from the text display.
d. If the dryer has 1 or 2 lter monitors, the timer
for lter service is disabled. When the lter monitor(s) send an alarm signal (change lter)
to the controller, the controller displays the same
LED’s and messages it would if the timer for lter
service had expired.
6.5.7 Display Mode
1. Display Mode is active when the user exits Program Mode or Setup Mode and no alarms are active (unless MANUAL CYCLE was selected in Setup Mode).
2. Display Mode is comprised of dryer status screens and dryer display screens (described below). The controller automatically alternates the display between the Status Screens and selected Display Screens.
3. The user can override the automatic screen scroll by pressing to step through each of the Display Screens shown on the next page. Automatic scrolling will resume when is pressed or if not depressed for 60 seconds.
4. The Energy Savings and Service Reminders Display Screens (Filters, Desiccant, and Valves) are alternated in sequence with the current dryer status screen.
15. Examples of the text display are shown on page 18 and below for each alarm and service reminder. The second line of the alarm screens contains up to three messages which are scrolled through, displaying each one for 2 seconds.
SERVICE DUE MESSAGES
SERVICE DRYER FILTERS
SERVICE DRYER DESICCANT
SERVICE DRYER VALVES
21
Page 24
DRYER STATUS SCREENS
LEFT TOWER DRYING
LT DRYING RT DEPRESSURIZE
LT DRYING RT HEATING
LT DRYING RT COOLING
LT DRYING RT REPRESSURIZE
LT DRYING RT HOLDING
(Not displayed in FIXED Cycle)
TOWER SWITCHOVER TOWER SWITCHOVER
RIGHT TOWER DRYING
LT DEPRESSURIZE RT DRYING
LT HEATING RT DRYING
LT COOLING RT DRYING
LT REPRESSURIZE RT DRYING
LT HOLDING RT DRYING
(Not displayed in FIXED Cycle)
Energy Savings
(Not displayed in FIXED Cycle)
ENERGY SAVINGS XX%
NOTE: Energy Savings will appear after seven days of continuous use.
Service reminder (lters)
HOURS TO SERVICE FILTERS: XXXX
Service reminder (desiccant)
HOURS TO SERVICE DESICCANT: XXXX
Service reminder (valves)
HOURS TO SERVICE VALVES: XXXX
DRYER DISPLAY SCREENS
Outlet Dew Point
(Displayed only if JP3 is ON)
DEW POINT ±XX°C ±XXX°F
Left Tower Temperature
LT TEMP ±XX°C ±XXX°F
Right Tower Temperature
RT TEMP ±XX°C ±XXX°F
Heater Temperature
HEATER TEMP ±XX°C ±XXX°F
Dewpoint Demand SetPoint
(Displayed only if JP3 is ON)
DWPT CNTL SETPT ±XX°C ±XXX°F
Energy Mgmt Signal
(Displayed only if JP2 is ON)
ENERGY MGMT SGNL XX%RH XXX°F XX°C XX MBAR X.XX PSI
Energy Mgmt Setpoint
(Displayed only if JP2 is ON)
ENERGY MGMT SET XX MBAR X.XX PSI
(This is the calculated “hold” set-point,
which is based on the sample air tem­perature.)
22
Page 25
6.5.8 Test Mode
1. Test Mode is active when the user exits Program Mode after selecting operation in MANUAL CY­CLE.
2. Test Mode is comprised of twelve (12) screens (screen descriptions follow the table below on the next page). Each screen corresponds to one of twelve program steps (described in the table below).
5. To exit Test Mode: a. Press and hold for 3 seconds to exit Test
Mode. The display switches to Screen 2 of Setup Mode.
b. Use to select ENERGY MANAGEMENT,
DEWPOINT CONTROL or FIXED CYCLE.
c. Press and hold for 3 seconds to exit Setup
Mode and activate Display Mode.
d. Dryer operation continues from the last step active
3. Press to advance from one screen (test step) to
when exiting the Test Mode.
the next.
IMPORTANT: Be sure to read and understand all
cautions listed with the screen (program step) de­scriptions.
4. Upon entering Test Mode, the program can be at any one of the twelve steps.
Program Step 1 2 3 4 5 6 7 8 9 10 11 12
LT status Drying Drying Drying Drying Drying Drying Off Depress Heat
RT status Off Depress Heat
1PS Closed Closed Closed Closed Closed Closed Closed
2PS Closed
3PS Closed Closed Closed Closed Closed Closed Closed
4PS Closed
LT drying solenoid (B) On On On On On On Off Off Off Off Off Off
LT depress solenoid (F) Off Off Off Off Off Off Off On On On On Off
LT purge solenoid (C) Off Off Off Off Off Off Off Off On On On Off
RT drying solenoid (A) Off Off Off Off Off Off On On On On On On
RT depress solenoid (G) Off On On On On Off Off Off Off Off Off Off
RT purge solenoid (D) Off Off On On On Off Off Off Off Off Off Off
LT inlet valve (V1) Open Open Open Open Open Open Closed Closed Closed Closed Closed Closed
LT depress valve (V9) Closed Closed Closed Closed Closed Closed Closed Open Open Open Open Closed
LT purge valve (V3) Closed Closed Closed Closed Closed Closed Closed Closed Open Open Open Closed
RT inlet valve (V2) Closed Closed Closed Closed Closed Closed Open Open Open Open Open Open
RT depress valve (V10) Closed Open Open Open Open Closed Closed Closed Closed Closed Closed Closed
RT purge valve (V4) Closed Open Open Open Open Closed Closed Closed Closed Closed Closed Closed
Repress valve (V11) Closed Closed Closed Closed Open Open Closed Closed Closed Closed Open Open
Temp display - location Left Right Right Right Right Right Right Left Left Left Left Left
Closed
then Open
Closed
then Open
Open Open Open
Open Open Open
Cool
Down
Sweep Repress Drying Drying Drying Drying Drying Drying
Open then
Closed
Open then
Closed
Closed
then Open
Closed Closed Closed Closed Closed Closed
Closed
then Open
Closed Closed Closed Closed Closed Closed
Open Open Open
Open Open Open
Cool
Down
Sweep Repress
Open then
Closed
Open then
Closed
Table 2
Cycle Sequence Steps
23
Page 26
TEST MODE SCREENS
Screen 1: Step 1
TEST1: LT DRYING
LT: XX°C XXX°F
Screen 2: Step 2
TEST2: DEPR RT
RT: XX°C XXX°F
NOTE: Sequence step will not advance to HEAT until
tower has fully depressurized. Exception: If switching failure is disabled then pressure condition is ignored.
Screen 3: Step 3
TEST3: HEAT RT
RT: XX°C XXX°F
Screen 4: Step 4
TEST4: COOL RT
RT: XX°C XXX°F
Screen 7: Step 7
TEST7: RT DRYING
RT: XX°C XXX°F
Screen 8: Step 8
TEST8: DEPR LT
LT: XX°C XXX°F
NOTE: Sequence step will not advance to HEAT until
tower has fully depressurized. Exception: If switching failure is disabled then pressure condition is ignored.
Screen 9: Step 9
TEST9: HEAT LT
LT: XX°C XXX°F
Screen 10: Step 10
TEST10: COOL LT
LT: XX°C XXX°F
Screen 5: Step 5
TEST5: SWEEP RT
RT: XX°C XXX°F
NOTE: If sweep cycle is disabled then Test 5 is
ignored.
Screen 6: Step 6
TEST6: REPR RT
RT: XX°C XXX°F
NOTE: Sequence step will not advance to tower
SWITCHOVER until tower has fully pressurized. Exception: If switching failure is disabled then pressure condition is ignored.
Screen 11: Step 11
TEST11: SWEEP LT
LT: XX°C XXX°F
NOTE: If sweep cycle is disabled then Test 10 is
ignored.
Screen 12: Step 12
TEST12: REPR LT
LT: XX°C XXX°F
NOTE: Sequence step will not advance to tower
SWITCHOVER until tower has fully pressurized. Exception: If switching failure is disabled then pressure condition is ignored.
24
Page 27
6.6 Start-up
6.6.1 Controller Settings
Set or verify settings on Controller. Detailed operational points are presented in section 6.5.
WARNING - Enclosure may have live electric parts. De-energize dryer before opening enclosure.
6.6.2 Initial Pressurization
SLOWLY pressurize dryer to full line pressure. (If the
dryer was installed with inlet and outlet isolation valves, the inlet isolation valve should be slowly opened while the outlet isolation valve remains closed.)
During initial start-up, check the entire system for leaks. If necessary, de-pressurize the dryer and correct any leaks.
NOTE: Read the off-line tower pressure gauge when the
tower is purging (air exhausting from mufer).
6.7.5 Process Valves
Determine if air control valves are operating and sequencing correctly.
6.7.5.1 Valves – Models 500 and 600
Inlet switching valves are normally open, pneumatically piston-actuated, Y-angle poppet valves. A yellow indicator can be seen through a clear window at the top of the ac­tuator housing when the valve is in the open position.
Purge exhaust valves are normally closed, pneumati­cally piston-actuated, Y-angle poppet valves. A yellow indicator can be seen through a clear window at the top of the actuator housing when the valve is in the open position.
6.6.2.1 Energy Management Sensor (if installed)
Open and adjust the sample exhaust valve until a very slight, continuous gas bleed is felt exhausting out of the sample cell.
6.6.2.2 Dew Point Sensor (if installed)
Ensure that the supply air valve is open (one turn). Open and adjust the sample exhaust valve until a very slight, continuous gas bleed is felt exhausting out of the sample cell.
6.6.3 Energizing the Dryer
Energize the dryer controls.
NOTE: The switching failure alarm may be activated if the unit is energized before it is pressurized. To deactivate alarm, allow dryer to cycle to next step and press the reset button.
6.6.4 Bringing the Dryer On-line
Establish a normal ow through the dryer. Slowly open
the outlet isolation valve if present. Close any dryer bypass valves.
6.7 Operational Check Points
6.7.1 Power to unit
Check periodically that there is power to the unit (indicating lights illuminated).
6.7.2 Alarms
Periodically check for ashing red alarm LED.
6.7.3 Tower Status LEDs
Illuminated LEDs indicate which tower is on-line drying or off-line regenerating.
6.7.4 Tower Pressure Gauges
Periodically check tower pressure gauges to verify that the pressure gauge of the on-line tower reads line pressure and the pressure gauge of the off-line tower reads below 2 psig (0.14 kgf/ cm2).
12 volt DC, normally-closed, 3-way pilot solenoid valves are wired to the controller and are used to direct pilot air to the actuators of the inlet switching and purge/repres­surization valves.
Dryers are equipped with a safety relief valve that has been sized to provide overpressure protection due to a
re for both desiccant towers.
6.7.5.2 Valves – Models 750 through 4300
Inlet switching valves are resilient seated buttery valves
with double acting pneumatic rack and pinion actuators. A yellow arrow indicator located on the top of the actuator output shaft points to valve position indicator icons. Pilot air is directed to actuator ports to open both inlet valves upon loss of power.
(Model 750 only) Purge exhaust valves are normally closed, pneumatically piston-actuated, Y-angle poppet valves. A yellow indicator can be seen through a clear window at the top of the actuator housing when the valve is in the open position.
(Models 900 through 4300) Purge exhaust valves are
resilient seated buttery valves with spring return, fail
closed, pneumatic rack and pinion actuators. A yellow arrow indicator located on the top of the actuator output shaft points to valve position indicator icons. Pilot air is directed to actuator ports to close both purge/repres­surization valves upon loss of power.
12 volt DC, single solenoid, 4-way pilot valves are wired to the controller and are used to direct pilot air to the actuators of the inlet switching and purge/repressuriza­tion valves.
Two mainline outlet and two purge line check valves
are installed in the upper piping to control the ow of
outlet and purge air. Check valve sticking will result in
excessive air discharge through a mufer. Excessive air discharge through the mufer can be associated with a
leaking outlet check valve on the same side or a purge check valve of the opposite side tower.
25
Page 28
Dryers are equipped with a safety relief valve that has been sized to provide overpressure protection due to a
re for both desiccant towers.
b. Advances directly to the beginning of whichever
stage of HEAT or COOL it had been at when power was interrupted.
The tower pressure gauge of the on-line tower should read line pressure. Air should not be leaking from the purge-repressurization valve of the on-line tower.
The tower pressure gauge of the off-line tower should read below 2 psig (0.14 kgf/ cm2) while that tower is purging. If excessive air is exhausting during the purge cycle, the inlet-switching valve on the same side may have failed to close or a check valve may be sticking.
6.8 Dryer Shut Down
1. If the dryer installation is equipped with dryer bypass and inlet and outlet isolation valves, the bypass valve should be opened and the inlet and outlet isolation valves closed.
2. De-energize the dryer’s electrical supply.
3. SLOWLY open the tower blow down valves (refer to Figure 3 for general location) to vent the dryer internal pressure.
4. When all dryer pressure gauges indicate zero pres­sure, close the tower blow down valves. Depres­surization is complete.
2. If the off-line tower was at any other step (SWITCHOVER, DEPRESSURIZATION, REPRESSURIZATION or HOLD) when power was lost, then the sequence simply resumes at that step.
6.10 Operating Parameters
Control valves are designed so that upon loss of power the air dryer is capable of drying air until the desiccant
exposed to the airow is saturated.
6.11 Using the RS-232 Port
The RS-232 port is used to monitor dryer operation from a host computer.
RS-232 connections are made at the 3-pin connector labeled J3 and located at the upper left-hand corner of the control board.
Interface to a PC requires a (1 to 1) DB-9 cable.
Cable Pin Out:
- Data transmitted on pin 2
- Data received on pin 3
- Ground is pin 5
- Pins 7 and 8 are jumpered at the dryer
6.9 Loss of Power
Control valves are designed so that upon loss of power the air dryer is capable of drying air until the desiccant
exposed to the airow is saturated.
6.9.1 Power Recovery:
6.9.1.1 On loss of electrical power –
All controller outputs turn off causing the dryer operating valves to react as follows:
1a. For models with poppet style inlet valves (models
500 - 600): both inlet valves will open. Both towers will repressurize.
1b. For models with buttery inlet valves (models 750 -
4300): inlet valves will remain in position. Any minor leakage through the inlet valve or check valve will slowly repressurize the off-line tower.
2. Purge exhaust valves close.
3. Depressurization solenoid valves close.
4. Repressurization valve closes.
6.9.1.2 On restoration of power –
1. If power is lost when the off-line tower is in either the HEAT or COOL step, the off-line tower will be either partially or fully repressurized. On power recovery the sequence:
a. Resumes at the DEPRESSURIZATION step to
let down the pressure in the off-line tower then,
Operation:
1. Fixed baud rate of 9600
2. Asynchronous format is 8 bit, no parity, 1 stop bit
(“8,N,1”)
3. No check sum or error correction values are pro­vided. If required, request status string two (or more) times and compare for agreement.
4. Request data by sending ASCII ? character (3FH). Response may take up to two seconds as certain processing functions may require completion before the serial port is acknowledged.
5. The dryer responds with line feed (0AH), carriage return (0DH), and a character string as follows:
STX Start of text character 0x02
109 Three character ASCII device identier
, comma character x ASCII representation of the cycle type , xx ASCII representation of the cycle step , xxxxx ASCII representation of the current cycle time
in seconds , xxx ASCII representation of the inlet temperature
(°F)
26
Page 29
, xxx ASCII representation of the heater tempera-
ture (°F) , xxx ASCII representation of the left bed tempera-
ture (°F) , xxx ASCII representation of the right bed tem-
perature (°F) , xxx ASCII representation of the humidity sensor
temperature (°F) , xxx ASCII representation of the humidity sensor
relative humidity (%) , xxxx ASCII representation of the dew point reading
(°F) , xxxx ASCII representation of the lter time to ser-
vice (hours) , xxxx ASCII representation of the desiccant time to
service (hours) , xxxx ASCII representation of the valve time to
service (hours) , x ASCII representation of programming jump-
ers , 1 or 0 Is the unit alarmed? 1 = alarm , 1 or 0 Is service required? 1 = service , xx ASCII representation of the energy savings
(%) , x Reserved for future use, always 1 for now , ETX end of text character OxO3 CR carriage return LF line feed
Determining jumper positions:
Each jumper 8 bits weighted by position
JP Value 8 128
7 64 6 32 5 16 4 8 3 4 2 2 1 1
Example:
If jumper 8, 5, and 1 are installed, a value of 128+16+1 = 145 is returned
To decode, the algorithm:
· If (number >= 128) è jumper 8 = on
· number = number - 128
· If (number >= 64) è jumper 7 = on
· number = number - 64;
· etc.....
JUMPERS:
The programming jumpers are as follows (0=off, 1=on):
JP Bit 1 0 off = externally heated on = blower dryer 2 1 on = energy management sensor installed 3 2 on = dew point sensor installed 4 3 on = no cooling (blower purge only) 5 4 on = tower pressure switches installed 6 5 on = not used (fast cycle for development,
V3.5 and prior)
7 6 on = to download language text (factory
use)
8 7 on = to enable factory set-up screens
27
Page 30

7.0 Maintenance

WARNING - This equipment is a pressure-containing
device. Depressurize before servicing.
NOTE: The Dryer Controller is equipped with Service
Reminder functions for lters, desiccant and valves.
7.1 Desiccant Replacement
NOTE: The use of the correct replacement desiccant
is necessary for proper dryer operation. Never use hygroscopic salts of the type commonly used in
“deliquescent ” type dryers.
1. Frequency Of Desiccant Replacement
Desiccant should be replaced whenever the required
dew point cannot be maintained while the dryer is being operated within its design conditions and there are no mechanical malfunctions.
NOTE: Desiccant life is determined by the quality of
the inlet air. Proper ltering of the inlet air will extend
the life of the desiccant. Typically desiccant life is 2 years.
2. Procedure for Desiccant Charge Replacement
a. Depressurize and de-energize the dryer.
b. Remove the ll and drain plugs or anges (where
applicable) from the desiccant tower and drain the spent desiccant. Place a container at the base of the vessel to collect the desiccant. If necessary tap the sides of the vessels with a rubber mallet to loosen desiccant.
NOTE: Use extreme care when inserting rods or
other tools through the desiccant ll or drain ports to loosen packed desiccant. Internal ow diffusers
at the ends of the desiccant beds can be damaged or punctured by sharp instruments. These diffusers
are necessary to distribute the airow and keep the
desiccant beads within the tower. Desiccant beads in
exhaust mufers, afterlters, or the piping connected
to the desiccant towers may indicate a perforation of a diffuser.
c. Replace the drain plug using Teon tape or another
pipe thread sealant suitable for compressed air
service. Reinstall drain port ange cover (where
applicable) in each desiccant tower.
d. Refer to Table 1 (on page 5) for desiccant quan-
tity per tower.
When using Table 1 you will nd the desiccant
quantities listed in layers. Each layer will vary in depth due to the type, quantity and purpose of the
desiccant. Layer 1 must be installed rst at the
bottom of the vessel followed by layer number 2 etc., until the complete charge of desiccant has been installed.
e. Utilizing an appropriate sized funnel, ll each
desiccant tower as follows:
1) Install the required quantity of tabular support (model 4300 only) or activated alumina in layer 1 of each tower.
2) Level layer 1 and each subsequent layer of desiccant as added to each tower.
3) Finish lling each tower with desiccant until
all desiccant has been installed. LIGHT tap­ping on the tower sides with a soft-face mallet should yield additional free space to allow installation of all desiccant required. DO NOT TAMP OR RAM DESICCANT.
f. Clean the ll port closure. Replace the ll plug
using Teon tape or another pipe thread sealant suitable for compressed air service. Reinstall ll port ange cover (where applicable) in desiccant
tower.
3. Insuring Desiccant Dryness
Replacement desiccant is shipped in airtight
containers. Keep the covers on these containers tightly closed until use to avoid moisture contamination. If desiccant is exposed to air it can be heated in an oven at 400°F (204°C) for four hours before
use. Alternatively, if the dryer is not relled with
dry desiccant, it may be necessary to operate
the unit with an inlet ow rate of less than 50% of
maximum rated inlet capacity until the desiccant has regenerated fully.
7.2 Purge Mufers
Purge mufers should be checked regularly, changed annually. Mufer disseminator elements become clogged
with desiccant dust over time, creating back pressure
and restricted purge ow.
7.3 Valves
1. Process and pilot valves should be checked fre­quently for leaks and proper operation.
2. Purge pressure adjustment valve should be checked frequently for proper adjustment.
7.4 Pilot Air Filter Element Replacement
1. Frequency of replacement
The pilot air lter contains a lter element that should
be changed yearly. Replacement may be required sooner if pressure drop across cartridge prevents valves from actuating properly.
WARNING – The pilot air lter housing is a pressure- containing device, depressurize before servicing.
Slowly open manual drain valve on bottom of lter
bowl by turning clockwise to verify that the housing is depressurized before removing bowl.
28
Page 31
2. Procedure for element replacement
a. Isolate dryer from air supply
b. Depressurize dryer by running dryer and allowing
system pressure to purge to atmosphere. Loss of pilot pressure will eventually prevent purge/ repressurization valves from opening. Remaining pressure can be vented to atmosphere through
the manual drain on the pilot air lter. The system
must be fully depressurized before removing the bowl.
c. Remove the filter bowl by pushing up, turn-
ing counterclockwise and then pulling straight down.
d. Clean the lter bowl.
e. Replace the element.
f. Clean and lubricate o-ring at top of bowl and
reassemble in reverse order.
7.5 Dew Point Analyzer Filter (optional) Element Replacement
1. Frequency of replacement
The Dew Point Analyzer lter contains a lter element
that should be changed yearly. Replacement may be required sooner if pressure drop across cartridge prevents the Dew Point Analyzer from operating properly.
WARNING – The Dew Point Analyzer lter housing is a pressure-containing device, depressurize before servicing. Slowly open manual drain valve on bottom
of lter bowl by turning clockwise to verify that the
housing is depressurized before removing bowl.
2. Procedure for element replacement
a. Isolate dryer from air supply
b. Depressurize dryer by running dryer and allowing
system pressure to purge to atmosphere. Loss of pilot pressure will eventually prevent purge/ repressurization valves from opening. Remaining pressure can be vented to atmosphere through
the manual drain on the pilot air lter. The system
must be fully depressurized before removing the bowl.
c. Remove the filter bowl by pushing up, turn-
ing counterclockwise and then pulling straight down.
d. Clean the lter bowl.
e. Replace the element.
f. Clean and lubricate o-ring at top of bowl and
reassemble in reverse order.
29
Page 32

8.0 Troubleshooting

WARNING - A POTENTIAL ELECTRICAL SHOCK HAZARD EXISTS. Some of the troubleshooting
checks may require gaining access to the dryer’s
electrical enclosure(s) while the power supply is
energized and should be performed by a qualied
electrical technician.
WARNING - Before performing any electrical or mechanical repairs or maintenance, or removing or disassembling any component, be sure to de­energize and depressurize the dryer.
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
Indicator lights not illuminated 1. No power to unit.
2. Loss of power supply to (or at) dryer’s electrical disconnect switch or breaker. (customer supplied)
3. Blown fuse.
4. Board malfunction.
Excessive pressure drop in dryer 1. Inlet/Outlet screens on desiccant tow-
Low Pressure Alarm
Left Tower or Right Tower Drying
ers are dirty
2. Excessive ow rate
1. Loss of dryer air supply.
2. Excessive air demand.
3. Faulty drying tower pressure switch
4. Drying tower Inlet Valve failed to open
5. Drying tower Purge Exhaust Valve failed to close.
6. Drying tower Depressurization Valve failed to close
7. Regenerating tower Outlet Check Valve failed to close
8. Drying tower Purge Check Valve leak­ing
1. Check voltage at terminal board.
2. Check disconnect switch or breaker closed. If tripped breaker or blown fuse is noted, investigate and Remedy cause.
3. Replace fuse.
4. Replace board.
1. Clean screens; follow desiccant removal instructions in the Maintenance section.
2. Check ow rate of inlet air. Reduce to design ow rate.
1. Check compressor supplying dryer.
2. Check equipment downstream of dryer.
3. Check pressure switch operation using tower pressure gauge for comparison. Replace switch if defective.
4a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air lter is fully closed, ensure pilot air lter
cartridge is not clogged, ensure pilot air shut-off valve is open
4b. Check for inlet pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
4c. Check for drying tower Inlet Valve failure - examine valve
and actuator for damage. Repair or replace as necessary.
5a. Check for air ow out of drying tower Purge Valve or ex-
haust piping indicating valve is not completely closed.
5b. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air lter is fully closed, ensure pilot air lter
cartridge is not clogged, ensure pilot air shut-off valve is open
5c. Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
5d. Check for drying tower Purge Exhaust Valve failure - exam-
ine valve and actuator for damage. Repair or replace as necessary.
6. Check for air ow out of drying tower Depressurization Mufer indicating valve is not completely closed. Repair or
replace as necessary.
7. Indicated by excessive ow out of regenerating tower
Purge Valve. Examine valve internals. Repair or replace as necessary.
8. Indicated by excessive ow out of regenerating tower Purge Valve or reverse air ow through heater and blower, i.e., out of the blower intake lter, examine valve internals. Repair
or replace as necessary.
CAUTION: Air owing backwards through heater and
blower may be very hot.
30
Page 33
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
High Pressure Alarm
Left Tower or Right Tower Re­generating
Low Pressure Alarm
Left Tower or Right Tower Re­generating
Temperature Under-Range or Temperature Over-Range Alarm
Left Tower or Right Tower
Dew Point Under-Range or Dew Point Over-Range Alarm
Left Tower or Right Tower Re­generating
1. Faulty regenerating tower pressure switch
2. Regenerating tower Depressurization
Mufer clogged.
3. Regenerating tower Depressurization Valve failed to open.
4. Regenerating tower purge exhaust pip­ing obstructed.
5. Regenerating tower Purge Exhaust Valve failed to open.
6. Repressurization valve (V11) failed to close.
1. Faulty left tower pressure switch.
2. Regenerating tower Purge Exhaust Valve failed to close.
3. Regenerating tower Depressurization Valve failed to close.
4. Repressurization valve (V11) failed to open.
5. Repressurization orices are blocked.
1. Tower temperature sensor failure.
Under-Range è Short circuit on sensor Over-Range è Open circuit on sensor
1. Energy Management temperature sen­sor (RTD4) failure.
1. Check pressure switch operation using tower pressure gauge for comparison. Replace switch if defective.
2. Examine inner core and clean or replace as necessary.
3. Check valve operation. Repair or replace as possible.
4. Ensure piping is free of obstructions.
5a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air lter is fully closed, ensure pilot air lter
cartridge is not clogged, ensure pilot air shut-off valve is open.
5b. Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
5c. Check for regenerating tower Purge Exhaust Valve failure -
examine valve and actuator for damage. Repair or replace as necessary.
6a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air lter is fully closed, ensure pilot air lter
cartridge is not clogged, ensure pilot air shut-off valve is open.
6b. Check for Repressurization Valve (V11) failure. Check valve
operation. Repair or replace as necessary.
1. Check pressure switch operation using tower pressure gauge for comparison. Replace switch if defective.
2a. Check for air ow out of regenerating tower Purge Valve or
exhaust piping indicating valve is not completely closed.
2b. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air lter is fully closed, ensure pilot air lter
cartridge is not clogged, ensure pilot air shut-off valve is open
2c. Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
2d. Check for regenerating tower Purge Exhaust Valve failure -
examine valve and actuator for damage. Repair or replace as necessary.
3. Check for air ow out of regenerating tower Depressur­ization Mufer indicating valve is not completely closed.
Repair or replace as necessary.
4a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air lter is fully closed, ensure pilot air lter
cartridge is not clogged, ensure pilot air shut-off valve is open.
4b. Examine repressurization valve (V11) for damage. Repair
or replace as necessary.
5. Check orices for obstruction and clean as necessary.
1. Check temperature circuit for continuity. Repair or replace as necessary.
1. Check temperature circuit for continuity. Repair or replace as necessary.
31
Page 34
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
Outlet Dew Point Alarm
Left Tower or Right Tower
High Humidity Alarm
Left Tower or Right Tower
Heater Over-Temperature Alarm
Heater Low-Temperature Alarm
Energy Management Under­Range Alarm or Energy Management Over­Range Alarm
Blower Motor Overload Alarm 1. Restricted or blocked purge air ow.
Heater High Inlet Temperature
(models 3200, 3600, & 4300 only)
1. Inlet air ow higher than the sizing
condition.
2. Liquids entering the dryer inlet.
3. Inlet air temperature higher than the sizing condition.
4. Desiccant dusting.
5. Contaminated desiccant (e.g. with oil).
6. Heater temperature set too low.
7. Heating malfunction due to heater failure or heater contactor failure.
1. Desiccant bed overloaded.
2. Dew point sensor or monitor damaged or defective.
3. Loss of desiccant drying capacity
1. Insufcient purge gas ow.
2. Temperature sensor failure.
1. Heating malfunction due to heater failure or heater contactor failure.
2. Temperature sensor failure.
1. Energy Management sensor failure. 1. Check circuit for continuity. Repair or replace as neces-
2. Line failure
1. On-line tower purge check valve is leaking.
2. Temperature sensor failure.
1. Reduce inlet ow to sizing condition.
2. Check the inlet air line for liquids. Inspect prelter and
drain valve. Clean, repair or replace automatic drain valve.
3. Check the compressor aftercooler and cooling system. Reduce inlet air temperature to sizing condition.
4. Check air pressure, airow and airow surges and correct
as necessary. Replace desiccant.
5. Check prelter and automatic drain valve. Replace prelter
element. Clean, repair or replace drain valve as necessary. Consult factory concerning need for desiccant replacement.
6. Adjust controller set point.
7. Replace heater or heater contactor.
1. Check inlet air ow rate, temperature and pressure. Higher than design ow, and temperature, and lower than design
pressure will result in overloading of the dryer.
2. Examine sensor for physical damage and check monitor/ sensor operation. Replace sensor or monitor as necessary.
3. Inlet air improperly ltered causing desiccant contamination
- examine lter elements and drains. Repair or replace as
necessary. Useful life of desiccant has been exceeded.
1. Check for purge blockage, temperature sensor failure, etc.
2. Repair and replace as required.
1. Replace heater or heater contactor.
2. Repair and replace as required.
sary.
1a. Dirty intake lter on blower - examine lter element and
clean or replace.
1b. Regenerating tower purge exhaust valve failed to open -
1) Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air lter is fully closed, ensure pilot air lter
cartridge is not clogged, ensure pilot air shut-off valve is open.
2) Check for purge pilot air solenoid valve failure. Check valve operation. Repair or replace as necessary.
3) Check for regenerating tower Purge Exhaust Valve failure ­examine valve and actuator for damage. Repair or replace as necessary.
1c. Purge exhaust piping obstructed - ensure piping is free of
obstructions.
1d. Regenerating tower purge check valve failed to open - ex-
amine valve internals. Repair or replace as necessary.
2. Check voltages and currents in the motor circuit.
1. Examine valve internals. Repair or replace as required.
2. Repair and replace as required.
32
Page 35

Electrical Schematic – 460VAC, 3 phase

(Contact factory to request certied drawings)
DETAIL A (2-WIRE DEWPOINT TRANSMITTER)
20
21
72
21
249 OHM
1/8W
+12VDC
20
21
21
EXTERNALLY LOCATED
RED
BLACK
DEWPOINT
3
TRANSMITTER
+ 4-20MA OUT
1
CUSTOMER PROVIDED
460VAC, 3 PHASE
(FOR FUSING AND WIRE
SIZING SEE TABLE 1)
{
LOW TENSION ENCLOSURE
L
L
TB5
N
N
PE
PE
+12VDC
DC COM
RTD1+
RTD1-
ANLG1+
ANLG1-
ANLG2+
ANLG2-
+5VDC
DC COM
RTD2+
RTD2-
RTD3+
RTD3-
RTD4+
RTD4-
RTD5+
RTD5-
IN1
LPS
LPS
RPS
RPS
IN2
IN3
L PURGE
L PURGE
R PURGE
R PURGE
L DRY
L DRY
R DRY
R DRY
OUT1
OUT2
ALARM
CONTACTS
20
21
80
81
70
249 OHM
1/8W
72
21
10
11
84
85
86
87
88
89
32
33
34
35
36
37
38
39
50
+
51
­52
+
53
­54
+
55
­56
+
57
-
25
21
59
20
NO
NC
C
3-WIRE DEWPOINT TRANSMITTER (FOR 2-WIRE, SEE DETAIL A)
+12VDC
RED
20
BLACK
21
GREEN
BROWN
BLACK
GREEN
21
RED
ORANGE
+ -
20 21
+12VDC
EXTERNALLY LOCATED
DEWPOINT
3
TRANSMITTER
G
+ 4-20MA OUT
1
OPTION
HEATER OVERTEMPERATURE
RTD3
RTD
RIGHT CHAMBER
RTD2
RTD
LEFT CHAMBER
RTD1
RTD
54
SOLENOID "B"
56
SOLENOID "A"
25
SOLENOID "E"
EXTERNALLY LOCATED
ENERGY MGMT
SENSOR
RTD4
+
1-5VDC OUT
+ 5VDC
YELLOW
G
-
OPTION
55
57
+12VDC
20
21
L1
L2
L3
L4
L5
L6
101
101
101
4CR1
101 107
5CR1
101
101
+12VDC DC COM
20
20
32
33
SET @ 45PSIG
1PS
35
34
SET @ 45PSIG
2PS
OL-AUX
36
1TS
+ -
50
+ -
52
+ -
59
L2
L1
20
1PSB
1CR1
104
104
104
2CR1
3CR1
37
2CR
53
3CR
1CR
MC1
MC2
MC3
2FU
1FU
3FU
+12VDC
+V -V
L N
G
MC-AUX
105
105
OL-AUX
26
28
LEFT CHAMBER PRESSURE SWITCH
RIGHT CHAMBER PRESSURE SWITCH
USED ON MODELS 3200, 3600 & 4300
51
21
HEAT ENABLE
401
OL1
402
OL2
403
OL3
404
HC1
405
HC2
406
HC3
0.5 AMP
407
0.5 AMP
H1 H3
408
1.25 AMP
101A
21
K TYPE
1TC
+ -
L1 N
106
C NO
1TR (OFF-DELAY, SE T @ 180S)
101
A1B1A2
1TR1
114
15 18
SOLENOID "F"
3PS
26
27
5PSIG
SOLENOID "G"
4PS
28
29
5PSIG
460VAC
X1 X2
115VAC
102
108
SOLENOID "C"
SOLENOID "D"
HIGH TENSION ENCLOSURE
H2 H4
1T
102
102
102
102
HC
102
102
MC
21
21
4CR
21
21
21
5CR
21
MOTOR1M
1HTR
21
NOTE: SET 1TR ON MODE "D". (SIGNAL OFF-DELAY)
LEFT CHAMBER DEPRESS
LEFT CHAMBER PURGE EXHAUST
RIGHT CHAMBER DEPRESS
RIGHT CHAMBER PURGE EXHAUST
33
Page 36

Electrical Schematic – 575VAC, 3 phase

(Contact factory to request certied drawings)
DETAIL A (2-WIRE DEWPOINT TRANSMITTER)
+12VDC
20
21
249 OHM
72
21
20
21
1/8W
21
LOW TENSION ENCLOSURE
L
L
N
N
PE
TB5
PE
+12VDC
DC COM
RTD1+
RTD1-
ANLG1+
ANLG1-
ANLG2+
ANLG2-
+5VDC
DC COM
RTD2+
RTD2-
RTD3+
RTD3-
RTD4+
RTD4-
RTD5+
RTD5-
IN1
LPS
LPS
RPS
RPS
IN2
IN3
L PURGE
L PURGE
R PURGE
R PURGE
L DRY
L DRY
R DRY
R DRY
OUT1
OUT2
ALARM
CONTACTS
20
21
80
81
70
249 OHM
1/8W
72
21
10
11
84
85
86
87
88
89
32
33
34
35
36
37
38
39
50
+
51
­52
+
53
­54
+
55
­56
+
57
-
25
21
59
20
NO
NC
C
EXTERNALLY LOCATED
RED
BLACK
+12VDC
20
RED
ORANGE
DEWPOINT
3
TRANSMITTER
+ 4-20MA OUT
1
3-WIRE DEWPOINT TRANSMITTER (FOR 2-WIRE, SEE DETAIL A)
RED
BLACK
21
GREEN
BROWN
BLACK
GREEN
21
+ -
20 21
+12VDC
CUSTOMER PROVIDED
575VAC, 3 PHASE
(FOR FUSING AND WIRE
SIZING SEE TABLE 1)
EXTERNALLY LOCATED
DEWPOINT
3
TRANSMITTER
G
+ 4-20MA OUT
1
HEATER OVERTEMPERATURE
RTD3
RTD
RIGHT CHAMBER
RTD2
RTD
LEFT CHAMBER
RTD1
RTD
54
SOLENOID "B"
56
SOLENOID "A"
25
SOLENOID "E"
OPTION
L1
L2
{
EXTERNALLY LOCATED ENERGY MGMT
SENSOR
RTD4
+
1-5VDC OUT
+ 5VDC
YELLOW
G
-
OPTION
55
57
+12VDC
20
21
L3
L4
L5
L6
101
101
101
4CR1
101 107
5CR1
101
101
+12VDC DC COM
20
20
32
33
SET @ 45PSIG
1PS
35
34
SET @ 45PSIG
2PS
OL-AUX
36
1TS
+ -
50
+ -
52
+ -
59
L2
L1
+12VDC
20
1PSB
1CR1
104
104
104
2CR1
3CR1
37
2CR
53
3CR
21
1CR
MC1
MC2
MC3
2FU
1FU
3FU
+V -V
L N
G
MC-AUX
105
105
OL-AUX
26
28
LEFT CHAMBER PRESSURE SWITCH
RIGHT CHAMBER PRESSURE SWITCH
USED ON MODELS 3200, 3600 & 4300
51
HEAT ENABLE
401
OL1
402
OL2
403
OL3
404
HC1
405
HC2
406
HC3
0.5 AMP
407
0.5 AMP
H1 H3
408
1.25 AMP
101A
21
K TYPE
1TC
+ -
L1 N
106
C NO
1TR (OFF-DELAY, SE T @ 180S)
101
A1B1A2
1TR1
114
15 18
SOLENOID "F"
3PS
26
27
5PSIG
SOLENOID "G"
4PS
28
29
5PSIG
575VAC
H2 H4
X1 X2
115VAC
1HC
102
108
MC
4CR
SOLENOID "C"
5CR
SOLENOID "D"
MOTOR1M
1HTR
1T
102
21
102
102
102
102
102
21
21
21
21
21
21
NOTE: SET 1TR ON MODE "D". (SIGNAL OFF-DELAY)
LEFT CHAMBER DEPRESS
LEFT CHAMBER PURGE EXHAUST
RIGHT CHAMBER DEPRESS
RIGHT CHAMBER PURGE EXHAUST
HIGH TENSION ENCLOSURE
34
Page 37

Electrical Data – Fusing & Wire Sizing

Electrical Service: 460VAC, 3 phase
MODEL COMPONENT RATING
HEATER 10 KW 12.6 20 AMPS #12 AWG
500
MOTOR 2.5 HP 4.1 7.5 AMPS #14 AWG
HEATER 12 KW 15.1 20 AMPS #12 AWG
600
MOTOR 4 HP 6.2 10 AMPS #14 AWG
HEATER 14 KW 17.6 25 AMPS #12 AWG
750
MOTOR 4 HP 6.2 10 AMPS #14 AWG
HEATER 17 KW 21.3 30 AMPS #10 AWG
900
MOTOR 4 HP 6.2 10 AMPS #14 AWG
1050
1300
1500
1800
2200
2600
3200
3600
4300
HEATER 19 KW 23.8 30 AMPS #10 AWG
MOTOR 5 HP 7.6 12 AMPS #14 AWG
HEATER 23 KW 28.9 40 AMPS #8 AWG
MOTOR 7.5 HP 11 17.5 AMPS #14 AWG
HEATER 28 KW 35.1 45 AMPS #8 AWG
MOTOR 10 HP 14 20 AMPS #14 AWG
HEATER 33 KW 41.4 60 AMPS #6 AWG
MOTOR 10 HP 14 20 AMPS #14 AWG
HEATER 40 KW 50.2 70 AMPS #4 AWG
MOTOR 10 HP 14 20 AMPS #14 AWG
HEATER 45 KW 56.5 80 AMPS #4 AWG
MOTOR 15 HP 21 30 AMPS #10 AWG
HEATER 54 KW 67.8 90 AMPS #2 AWG
MOTOR 5 HP 7.6 12 AMPS #14 AWG
HEATER 60 KW 75.3 100 AMPS #2 AWG
MOTOR 7.5 HP 9.0 12 AMPS #14 AWG
HEATER 70 KW 87.9 110 AMPS #2 AWG
MOTOR 7.5 HP 11 17.5 AMPS #14 AWG
F.L.A.
@460VAC
SUGGESTED
FUSING
WIRE SIZE
Electrical Service: 575VAC, 3 phase
MODEL COMPONENT RATING
HEATER 10 KW 10.0 15 AMPS #12 AWG
500
MOTOR 2.5 HP 3.3 6 AMPS #14 AWG HEATER 12 KW 12.0 20 AMPS #12 AWG
600
MOTOR 4 HP 5.0 9 AMPS #14 AWG HEATER 14 KW 14.1 20 AMPS #12 AWG
750
MOTOR 4 HP 5.0 9 AMPS #14 AWG HEATER 17 KW 17.1 25 AMPS #12 AWG
900
MOTOR 4 HP 5.0 9 AMPS #14 AWG
1050
1300
1500
1800
2200
2600
3200
3600
4300
HEATER 19 KW 19.1 25 AMPS #12 AWG MOTOR 5 HP 6.1 9 AMPS #14 AWG HEATER 23 KW 23.1 30 AMPS #8 AWG MOTOR 7.5 HP 9.0 15 AMPS #14 AWG HEATER 28 KW 28.1 40 AMPS #8 AWG MOTOR 10 HP 11.0 17.5 AMPS #14 AWG HEATER 33 KW 33.1 50 AMPS #8 AWG MOTOR 10 HP 11.0 17.5 AMPS #14 AWG HEATER 40 KW 40.2 60 AMPS #6 AWG MOTOR 10 HP 11.0 17.5 AMPS #14 AWG HEATER 45 KW 45.2 60 AMPS #6 AWG MOTOR 15 HP 17.0 25 AMPS #10 AWG HEATER 54 KW 54.2 70 AMPS #4 AWG MOTOR 5 HP 6.1 9 AMPS #14 AWG HEATER 60 KW 60.2 80 AMPS #4 AWG MOTOR 7.5 HP 6.1 9 AMPS #14 AWG HEATER 70 KW 70.3 90 AMPS #2 AWG MOTOR 7.5 HP 9.0 15 AMPS #14 AWG
F.L.A.
@575VAC
SUGGESTED
FUSING
WIRE SIZE
35
Page 38

P&ID Schematic - Models 500 through 600

(Contact factory to request certied drawings)
DRY GAS
OUTLET
4 26
27
28
25
19
20
24
23
6
13
43
42
16
29
21
LEFT
SET @ 176°F
RTD 1
M
SET @
45 PSIG
1PS
SET @
5 PSIG
3PS
EXH.
(RTD4/HS1)
ENERGY MGMT OPTION
SOL 'F'
SET @ 165 PSIG
V7 V8
2
SOL 'C'
V12 V13
3
1
V11
1TC
SET @ 370°F
RTD 3
SET @ 650°F
SOL 'D'
SOL 'E'
10
DPA
DEWPOINTER OPTION
V6V5
SET AT 100 PSIG
RIGHT
CHAMBERCHAMBER
REGENDRYING
SOL 'G'
SET @
45 PSIG
SET @
5 PSIG
2PS
4PS
SET @ 176°F
RTD 2
13
14
44A
44
22
3
15
7
8
11
12
9
18
54
WET GAS
INLET
36
19
5
17
2
1
EXH.
V9
V3
V4
V1 V2
NOTES SYMBOLS ARE PER ANSI Y32.10 "GRAPHIC SYMBOLS FOR FLUID POWER DIAGRAMS."
1. AS SHOWN FLOW DIRECTION IS:
2.
SOLENOID VALVES 'B', 'D', & 'G' ARE SHOWN ENERGIZED,
3. SOLENOID VALVES 'A', 'C', 'E', & 'F' ARE SHOWN DE-ENERGIZED.
4.
V10
INDICATES OPTION
EXH.
LEFT CHAMBER DRYING RIGHT CHAMBER REGEN PILOT GAS LINE
SOL 'A'
SOL 'B'
Page 39
LEGEND
1. INLET VALVE (V1 LEFT, V2 RIGHT)
2. PURGE EXHAUST VALVE (V3 LEFT, V4 RIGHT)
3. PURGE CHECK VALVE (V5 LEFT, V6 RIGHT)
4. OUTLET CHECK VALVE (V7 LEFT, V8 RIGHT)
5. DEPRESS VALVE (V9 LEFT, V10 RIGHT)
6. PURGE HEATER WITH INSULATION
7. HEATER TEMPERATURE THERMOCOUPLE
8. HEATER OVERTEMPERATURE RTD
9. CHAMBER RTD (LEFT & RIGHT)
10. RELIEF VALVE
11. CHAMBER PRESSURE GAUGES (LEFT & RIGHT)
12. CHAMBER PRESSURE SWITCH (LEFT & RIGHT)
13. SERVICE VALVE
14. PILOT AIR FILTER
15. PRESSURE REGULATOR & GAUGE
16. SOLENOID VALVE
17. MUFFLER
18. DESICCANT CHAMBER
19. DESICCANT RETAINING SCREEN (TOP & BOTTOM)
20. DESICCANT FILL PORT
21. DESICCANT DRAIN PORT
22. HOT PIPE INSULATION
23. PURGE PRESSURE GAUGE
24. PURGE BLOWER AND MOTOR
25. PURGE SUCTION FILTER SILENCER
26. REPRESS/SWEEP VALVE (V11)
27. REPRESS/SWEEP CHECK VALVE (V12 LEFT, V13 RIGHT)
28. REPRESS/SWEEP ORIFICE
29. CHAMBER BLOW-DOWN VALVE
ENERGY MANAGEMENT OPTION
42. ENERGY MANAGEMENT PILOT OPERATED VALVE
43. ENERGY MANAGEMENT SENSOR (RTD4/HS1)
DEWPOINTER OPTION
44. DEWPOINT ANALYZER 44A. DEWPOINT ANALYZER FILTER
INSULATION OPTION
54. CHAMBER INSULATION
FIXED CYCLE TIMING
(TIME IN MINUTES)
ELECTRICAL COMPONENT
ENERGIZED
SOLENOID VALVE 'A' 3 WAY
SOLENOID VALVE 'B' 3 WAY
SOLENOID VALVE 'C' 3 WAY
SOLENOID VALVE 'D' 3 WAY
SOLENOID VALVE 'E' N.C.
SOLENOID VALVE 'F' N.C.
SOLENOID VALVE 'G' N.C.
HEATER
BLOWER MOTOR
LEFT CHAMBER DRYING (RIGHT CHAMBER REGEN)
2
176
PROCESS COMPONENT
PROCESS COMPONENT
DEPRESSURIZATION
STATUS
CLOSED
YES
V1
OPEN
NO
CLOSED
YES
V2
OPEN
NO
OPEN
YES
V3
NO
CLOSED
YES
OPEN
V4
NO
CLOSED
CLOSED
NO
V11
OPEN
YES
YES OPEN
V9
NO
CLOSED
YES
OPEN
V10
NO
CLOSED
ON
YES
OFF
NO
YES
ON
OFF
NO
3 1762
55
4 4
2ND STAGE REGENERATION
(JUMPER SELECTABLE)
HEATER COOL DOWN
HEATING
RIGHT CHAMBER DRYING (LEFT CHAMBER REGEN)
REPRESSURIZATION
DEPRESSURIZATION
HOLD
HEATING
55
2ND STAGE REGENERATION
(JUMPER SELECTABLE)
HEATER COOL DOWN
3
REPRESSURIZATION
HOLD
Sequence of Operation
(Models 500 through 600)
37
Page 40

P&ID Schematic - Models 750 through 4300

(Contact factory to request certied drawings)
SET @ 165 PSIG
26
4
27
28
25
19
20
24
23
30
6
13
43
42
16
29
21
LEFT
SET @ 176°F
RTD 1
DRY GAS
OUTLET
M
SET @
45 PSIG
1PS
SET @
5 PSIG
3PS
EXH.
(RTD4/HS1)
ENERGY MGMT OPTION
SOL 'F'
V7 V8
1TS
(225°F)
2
SOL 'C'
V12 V13
3
1
V11
1TC
SET @ 370°F
RTD 3
SET @ 650°F
SOL 'D'
SOL 'E'
V6V5
SET @
45 PSIG
SET @ 5 PSIG
SOL 'G'
10
DPA
DEWPOINTER OPTION
SET AT 100 PSIG
2PS
4PS
SET @ 176°F
RTD 2
CHAMBERCHAMBER
RIGHT
REGENDRYING
13
14
44A
44
22
3
15
7
8
11
12
9
18
54
38
19
5
17
2
OPEN 5 TURNS
FROM FULL CLOSED
& LOCK IN PLACE
1
MODEL 750 ONLY
(SEE DETAIL 'A'
FOR 900-4300)
1A
EXH.
V9
WET GAS
INLET
V10
V3
V4
V2
V1
NOTES SYMBOLS ARE PER ANSI Y32.10 "GRAPHIC SYMBOLS FOR FLUID POWER DIAGRAMS."
1. AS SHOWN FLOW DIRECTION IS:
2.
SOLENOID VALVES 'B', 'D', & 'G' ARE SHOWN ENERGIZED,
3. SOLENOID VALVES 'A', 'C', 'E', & 'F' ARE SHOWN DE-ENERGIZED.
4.
EXH.
INDICATES OPTION
SOL 'A'
SOL 'B'
LEFT CHAMBER DRYING RIGHT CHAMBER REGEN PILOT GAS LINE
Page 41
LEGEND
DETAIL 'A' (MODELS 900-4300)
V4
SOL 'C'
V3
2
3
4
1
5
2
3
SOL 'D'
4
1
5
1. INLET VALVE (V1 LEFT, V2 RIGHT) 1A. FLOW CONTROL VALVE
2. PURGE EXHAUST VALVE (V3 LEFT, V4 RIGHT)
3. PURGE CHECK VALVE (V5 LEFT, V6 RIGHT) (NO SPRING)
4. OUTLET CHECK VALVE (V7 LEFT, V8 RIGHT)
5. DEPRESS VALVE (V9 LEFT, V10 RIGHT)
6. PURGE HEATER WITH INSULATION
7. HEATER TEMPERATURE THERMOCOUPLE
8. HEATER OVERTEMPERATURE RTD
9. CHAMBER RTD (LEFT & RIGHT)
10. RELIEF VALVE
11. CHAMBER PRESSURE GAUGES (LEFT & RIGHT)
12. CHAMBER PRESSURE SWITCH (LEFT & RIGHT)
13. SERVICE VALVE
14. PILOT AIR FILTER
15. PRESSURE REGULATOR & GAUGE
16. SOLENOID VALVE
17. MUFFLER
18. DESICCANT CHAMBER
19. DESICCANT RETAINING SCREEN (TOP & BOTTOM)
20. DESICCANT FILL PORT
21. DESICCANT DRAIN PORT
22. HOT PIPE INSULATION
23. PURGE PRESSURE GAUGE
24. PURGE BLOWER AND MOTOR
25. PURGE SUCTION FILTER SILENCER
26. REPRESS/SWEEP VALVE (V11)
27. REPRESS/SWEEP CHECK VALVE (V12 LEFT, V13 RIGHT)
28. REPRESS/SWEEP ORIFICE
29. CHAMBER BLOW-DOWN VALVE
30. TEMPERATURE SWITCH (MODELS 3200 - 4300 ONLY)
ENERGY MANAGEMENT OPTION
42. ENERGY MANAGEMENT PILOT OPERATED VALVE
43. ENERGY MANAGEMENT SENSOR (RTD4/HS1)
DEWPOINTER OPTION
44. DEWPOINT ANALYZER 44A. DEWPOINT ANALYZER FILTER
INSULATION OPTION
54. CHAMBER INSULATION
FIXED CYCLE TIMING
(TIME IN MINUTES)
ELECTRICAL COMPONENT
PROCESS COMPONENT
ENERGIZED
SOLENOID VALVE 'A' 3 WAY
SOLENOID VALVE 'B' 3 WAY
SOLENOID VALVE 'C' 3 WAY
SOLENOID VALVE 'D' 3 WAY
SOLENOID VALVE 'E' N.C.
SOLENOID VALVE 'F' N.C.
SOLENOID VALVE 'G' N.C.
HEATER
BLOWER MOTOR
LEFT CHAMBER DRYING (RIGHT CHAMBER REGEN)
2
176
PROCESS COMPONENT
DEPRESSURIZATION
CLOSED
OPEN
CLOSED
OPEN
OPEN
CLOSED
OPEN
CLOSED
CLOSED
OPEN
CLOSED
OPEN
CLOSED
ON OFF
ON OFF
HEATING
STATUS
YES
V1
NO
YES
V2
NO
YES
V3
NO
YES
V4
NO
NO
V11
YES
YES OPEN
V9
NO
YES
V10
NO
YES
NO
YES
NO
(Model 750 through 4300)
3 1762
55
4 4
2ND STAGE REGENERATION
(JUMPER SELECTABLE)
HEATER COOL DOWN
= FAILS IN POSITION
*
RIGHT CHAMBER DRYING (LEFT CHAMBER REGEN)
REPRESSURIZATION
DEPRESSURIZATION
HOLD
Sequence of Operation
HEATING
55
2ND STAGE REGENERATION
(JUMPER SELECTABLE)
HEATER COOL DOWN
3
REPRESSURIZATION
HOLD
LOSS OF POWER
* *
* *
39
Page 42
Replacement Parts – Models 500 through 600
7
8
42
43
9
6
25
24
11
1514
1
REAR VIEW
10
3
AIR
OUT
26
4
23
LEFT CHAMBER RIGHT CHAMBER
11
CONTROL ENCLOSURE
HIGH TENSION ENCLOSURE
40
44
AIR
2
5
29
FRONT VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
Phone: 1+ 352-873-5793 FAX: +1 352-873-5770 Email: ppc.americas.am@spx.com Web: www.spx.com/pneumatic-products
SIDE VIEW
IN
Page 43
MODEL
500 600
MAINTENANCE KITS
Year 2 Maintenance Kit Elements*, Mufer, Drain, Desiccant Evaluation Kit IBPMK2-04-A IBPMK2-06-A
Year 3 Maintenance Kit
Year 4 Maintenance Kit Elements*, Mufer, Drain, Desiccant Evaluation Kit IBPMK4-04-A IBPMK4-06-A
Year 5 Maintenance Kit
Desiccant Kit IBPDES-04 IBPDES-06
*NOTE: Replacement Prelter and Afterlter elements are included in Standard Kits.
All the contents of the 2 Year Kit, Pressure
Switches, Valve Repair Kits, Blower Hose
All the contents of the 4 Year Kit, Pressure
Switches, Valve Repair Kits, Blower Hose
IBPMK3-04-A IBPMK3-06-A
IBPMK5-04-A IBPMK5-06-A
REPLACEMENT PARTS
ID# DESCRIPTION
1 Inlet Valve Assembly (V1 & V2) * Solenoid Valve (Sol “A”, “B”) 3203652 3203652 1 2 2 Purge Exhaust Valve Assembly (V3 & V4) 3152701 3152701 1 2 * Solenoid Valve (Sol “C”, “D”) 3203652 3203652 1 2 3 Purge Check Valve (V5 & V6) 3160401 3160401 1 2 4 Outlet Check Valve (V7 & V8) 3160401 3160401 1 2 5 Depress Valve (V9, V10) 4010085 4010085 1 2 * Depress Solenoid Valve (Sol “F”, “G”) 3203652 3203652 1 2 6 Purge Heater 3152742 3152741 1 7 Heater Temperature Thermocouple (1TC) 3153971 3153971 1 8 Heater Overtemperature RTD (RTD3) 3153224 3153224 1 9 Chamber RTD (RTD1, RTD2) 3153224 3153224 1 2
10 Pressure Relief Valve 7400684 7400684 1
11 Chamber Pressure Gauge 4011096 4011096 1 2
12 Chamber Pressure Switch (1PS, 2PS) 3149016 3149016 1 2
* Chamber Depressurization Pressure Switch (3PS, 4PS) 3152525 3152525 1 2 14 Pilot Air Filter Element 3158592 3158592 1 1 15 Pilot Air Pressure Regulator 3154237 17 Depress Mufer 3133635 3133635 2
* Depress Mufer Replacement Core 3075949 3075949 2 2 23 Purge Pressure Gauge 3158833 3158833 1 24 Blower (460V) 3157894 3158197 1
* Blower Hose 3251999 3242540 1 25 Silencer Assembly 3152461 3152461 1
* Blower Inlet Silencer Element 1270769 1270769 1 26 Repress/Sweep Valve (V11) 4010085 4010085 1 1
* Repress/Sweep Solenoid Valve (Sol “E”) 3203652 3203652 1 1 27 Repress/Sweep Check Valve (V12 & V13) 3151005 3151005 1 2 29 Chamber Blowdown Valve 4009894 4009894 2 42 Energy Management Pilot Operated Valve 1274209 1274209 1 43 Energy Management Sensor (RTD4/HS1) 3144864 3144864 1
* Energy Management Vent Needle Valve 3158747 3158747 1 44 Dew-point Sensor - Ceramic 3154859 3154859 1
* Dryer Controller 7417845 7417845 1
* Heater Contactor 3153829 3153829 1
* Blower Motor Contactor 3158056 3158056 1
* Relay, Overload, 3Pole, 600V Max, 3.2-16Amp 3158551 3158551 1
* Relay, SPDT 12VDC Coil, 120VAC, 10A (1CR, 2CR, 3CR, 4CR, 5CR) 3154359 3154359 1 5
* Fuse 1.25A 600V (3FU) 1240671 1240671 1 1
* Fuse .5A 600V (1FU, 2FU) 1241118 1241118 1 2
* Temperature Controller 7416897 7416897 1
* Timer, SPDT, 0.1S-120HR 3203083 3203083 1
Desiccant Evaluation Kit 3150628 3150628 Pre-Filter Assembly PCS15001G24
Auto-Drain 3044466 3044466
Afterlter Assembly PCS15001G24 PCS16001G32
NOTES:
1. Parts and Maintenance Kits are for standard builds only. Please contact the factory with your dryer serial number for assistance on identifying spare parts and maintenance kits for your specic unit.
2. All quantities for one dryer.
3. ID# correspond to P&ID legend (* Not pictured in diagrams.)
3151877 3151877 1 2
3154237 1
PCS16001G32
SAFETY
STOCK
DRYER
QTY.
Phone: 1+ 352-873-5793 FAX: +1 352-873-5770 Email: ppc.americas.am@spx.com Web: www.spx.com/pneumatic-products
41
Page 44
Replacement Parts – Models 750 through 1800
25
24
7
8
42
3
43
2
9
MODEL 750
6
1
1A
REAR VIEW
10
11
1514
44
4
LEFT CHAMBER RIGHT CHAMBER
2
23
11
CONTROL ENCLOSURE
HIGH TENSION ENCLOSURE
5
FRONT VIEW
26
AIR
OUT
29
SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
AIR
IN
42
Phone: 1+ 352-873-5793 FAX: +1 352-873-5770 Email: ppc.americas.am@spx.com Web: www.spx.com/pneumatic-products
Page 45
MODEL
750 900 1050 1300 1500 1800
MAINTENANCE KITS
Year 2 Maintenance Kit Elements*, Mufer, Drain, Desiccant Evaluation Kit IBPMK2-08-A IBPMK2-10-A IBPMK2-12-A IBPMK2-14-A IBPMK2-16-A IBPMK2-18-A
Year 3 Maintenance Kit
Year 4 Maintenance Kit Elements*, Mufer, Drain, Desiccant Evaluation Kit IBPMK4-08-A IBPMK4-10-A IBPMK4-12-A IBPMK4-14-A IBPMK4-16-A IBPMK4-18-A
Year 5 Maintenance Kit
Desiccant Kit IBPDES-08 IBPDES-10 IBPDES-12 IBPDES-14 IBPDES-16 IBPDES-18
*NOTE: Replacement Prelter and Afterlter elements are included in Standard Kits.
All the contents of the 2 Year Kit, Pressure
Switches, Valve Repair Kits, Blower Hose
All the contents of the 4 Year Kit, Pressure
Switches, Valve Repair Kits, Blower Hose
IBPMK3-08-A IBPMK3-10-A IBPMK3-12-A IBPMK3-14-A IBPMK3-16-A IBPMK3-18-A
IBPMK5-08-A IBPMK5-10-A IBPMK5-12-A IBPMK5-14-A IBPMK5-16-A IBPMK5-18-A
REPLACEMENT PARTS
ID# DESCRIPTION
1 Inlet Valve Assembly (V1 & V2)
* Solenoid Valve (Sol “A”, “B”) 3203652 3203652 3203652 3203652 3203652 3203652 1 2 1A Inlet Pilot Operated Valve 3155189 3155189 3155189 3155189 3155189 3155189 1 2
2 Purge Exhaust Valve Assembly (V3 & V4) 3152701 3152394 3152394 3152394 3152394 3152394 1 2
* Solenoid Valve (Sol “C”, “D”) 3203652 4009880 4009880 4009880 4009880 4009880 1 2
3 Purge Check Valve (V5 & V6) 7405310
4 Outlet Check Valve (V7 & V8) 3160059 3160059 3160059 3160059 3160059 3160059 1 2
5 Depress Valve (V9, V10) 4010085 4010085 4010085 4010085 4010086 4010086 1 2
* Depress Solenoid Valve (Sol "F", "G") 3203652 3203652 3203652 3203652 3203652 3203652 1 2
6 Purge Heater 1200773 3152734 3152735 1171782 3152736 3152738 1
7 Heater Temperature Thermocouple (1TC) 3153971 3153971 3153971 3153971 3153971 3153971 1
8 Heater Overtemperature RTD (RTD3) 3153224 3153224 3153224 3153224 3153224 3153224 1
9 Chamber RTD (RTD1, RTD2) 3153224 3153224 3153224 3153224 3153224 3153224 1 2 10 Pressure Relief Valve 7400684 7400684 7400684 7400684 3100938 3100938 1 11 Chamber Pressure Gauge 4011096 4011096 4011096 4011096 4011096 4011096 1 2 12 Chamber Pressure Switch (1PS, 2PS) 3149016 3149016 3149016 3149016 3149016 3149016 1 2
* Chamber Depressurization Pressure Switch (3PS, 4PS) 3152525 3152525 3152525 3152525 3152525 3152525 1 2 14 Pilot Air Filter Element 3158592 3158592 3158592 3158592 3158592 3158592 1 15 Pilot Air Pressure Regulator 3154237 3154237 3154237 3154237 3154237 3154237 1 17 Depress Mufer 3133635
* Depress Mufer Replacement Core 3075949 3075949 3107791 3107791 3107791 3107791 2 2 23 Purge Pressure Gauge 3158833 3158833 3158833 3158833 3158833 3158833 1 24 Blower (460V) 3158197 3158197 3158198 3158199 3158200 3158200 1
* Blower Hose 3242540 3242540 3242540 3251998 3242539 3242539 1 25 Purge Suction Filter Silencer Assembly 3152728 3152728 3152728 3152729 3152729 3158021 1
* Blower Inlet Silencer Element 1270769 1270769 1270769 3153683 3153683 3159138 1 1 26 Repress/Sweep Valve (V11) 7010085 4010085 4010085 4010085 4010085 4010085 1 1
* Repress/Sweep Solenoid Valve (Sol ‘E’) 3203652 3203652 3203652 3203652 3203652 3203652 1 1 27 Repress/Sweep Check Valve (V12 & V13) 3151005 3151005 3151005 3151005 3151005 3151005 1 2 29 Chamber Blowdown Valve 4009894 4009894 4009894 4009894 4009900 4009900 2 42 Energy Management Pilot Operated Valve 1274209 1274209 1274209 1274209 1274209 1274209 1 43 Energy Management Sensor (RTD4/HS1) 3144864 3144864 3144864 3144864 3144864 3144864 1
* Energy Management Vent Needle Valve 3158747 3158747 3158747 3158747 3158747 3158747 1 44 Dew-point Sensor - Ceramic 3154859 3154859 3154859 3154859
* Dryer Controller 7417845 7417845 7417845 7417845 7417845 7417845 1
* Heater Contactor 3153829 3153829 3153829 3147965 3147965 3151845 1 1
* Blower Motor Contactor 3158056 3158056 3158056 3158653 3147640 3147640 1
* Relay, Overload, 3Pole, 600V Max, 3.2-16Amp 3158551 3158551 3158551 3158551 N/A N/A 1
* Relay, Overload, 3Pole, 600V Max, 5.4-27Amp N/A N/A N/A N/A 3158481 3158481 1
* Relay, SPDT 12VDC Coil, 120VAC, 10A (1CR, 2CR, 3CR, 4CR, 5CR) 3154359 3154359 3154359 3154359 3154359 3154359 1 5
* Fuse 1.25A 600V (3FU) 1240671 1240671 1240671 1240671 1240671 1240671 1 1
* Fuse .5A 600V (1FU, 2FU) 1241118 1241118 1241118 1241118 1241118 1241118 1 2
* Temperature Controller 7416897 7416897 7416897 7416897 7416897 7416897 2
* Timer, SPDT, 0.1S-120HR 3203083 3203083 3203083 3203083 3203083 3203083 1
Desiccant Evaluation Kit 3150628 3150628 3150628 3150628 3150628 3150628 Pre-Filter Assembly PCS18001G32 PCS19501G49 PCS112001G49C PCC114003G49 PCC118003G65 PCC118003G65
Auto-Drain 3044466 3044466 3044466 3044466 3044466 3044466
Afterlter Assembly PCS18001G32 PCS19501G49 PCS112001G49C PCC114003G49 PCC118003G65 PCC118003G65
NOTES:
1. Parts and Maintenance Kits are for standard builds only. Please contact the factory with your dryer serial number for assistance on identifying spare parts and maintenance kits for your specic unit.
2. All quantities for one dryer.
3. ID# correspond to P&ID legend (* Not pictured in diagrams.)
4. N/A - Not Applicable to this Model Size
3152393 3152393 3152393 3152393 3152393 3152393 1 2
7405310 7405310 7405310 7405310 7405310 1 2
3133635 3071392 3071392 3071392 3071392 2
3154859 3154859 1
SAFETY
STOCK
DRYER
QTY.
Phone: 1+ 352-873-5793 FAX: +1 352-873-5770 Email: ppc.americas.am@spx.com Web: www.spx.com/pneumatic-products
43
Page 46
Replacement Parts – Models 2200 through 2600
7
3
8
?
6
25
24
42
9
1 1A
43
REAR VIEW
4
26
23
LEFT CHAMBER
RIGHT CHAMBER
11
10
AIR
OUT
44
CONTROL ENCLOSURE
11
1514
44
2
FRONT VIEW
HIGH TENSION ENCLOSURE
5
29
SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
AIR
IN
Phone: 1+ 352-873-5793 FAX: +1 352-873-5770 Email: ppc.americas.am@spx.com Web: www.spx.com/pneumatic-products
Page 47
MODEL
2200 2600
MAINTENANCE KITS
Year 2 Maintenance Kit Elements*, Mufer, Drain, Desiccant Evaluation Kit IBPMK2-20-A IBPMK2-22-A
Year 3 Maintenance Kit
Year 4 Maintenance Kit Elements*, Mufer, Drain, Desiccant Evaluation Kit IBPMK4-20-A IBPMK4-22-A
Year 5 Maintenance Kit
Desiccant Kit IBPDES-20 IBPDES-22
*NOTE: Replacement Prelter and Afterlter elements are included in Standard Kits.
All the contents of the 2 Year Kit, Pressure
Switches, Valve Repair Kits, Blower Hose
All the contents of the 4 Year Kit, Pressure
Switches, Valve Repair Kits, Blower Hose
IBPMK3-20-A IBPMK3-22-A
IBPMK5-20-A IBPMK5-22-A
REPLACEMENT PARTS
ID# DESCRIPTION
1 Inlet Valve Assembly (V1 & V2)
* Solenoid Valve (Sol “A”, “B”) 3203652 3203652 1 2 1A Inlet Pilot Operated Valve 3155189 3155189 1 2
2 Purge Exhaust Valve Assembly (V3 & V4) 3152394 3152394 1 2
* Solenoid Valve (Sol “C”, “D”) 4009880 4009880 1 2
3 Purge Check Valve (V5 & V6) 3160063 3160063 1 2
4 Outlet Check Valve (V7 & V8) 3160060 3160060 1 2
5 Depress Valve (V9, V10) 4010086 4010086 1 2
* Depress Solenoid Valve (Sol "F", "G") 3154249 3154249 1 2
6 Purge Heater 1217919 1205010 1
7 Heater Temperature Thermocouple (1TC) 3153971 3153971 1
8 Heater Overtemperature RTD (RTD3) 3153224 3153224 1
9 Chamber RTD (RTD1, RTD2) 3153224 3153224 1 2 10 Pressure Relief Valve 3100938 3100938 1 11 Chamber Pressure Gauge 4011096 4011096 1 2 12 Chamber Pressure Switch (1PS, 2PS) 3149016 3149016 2
* Chamber Depressurization Pressure Switch (3PS, 4PS) 3152525 3152525 2 14 Pilot Air Filter Element 3158592 3158592 1 15 Pilot Air Pressure Regulator 3154237 3154237 1 17 Depress Mufer 3204478 3204478 2
* Depress Mufer Replacement Core 3126761 3126761 1 2 23 Purge Pressure Gauge 3158833 3158833 1 24 Blower (460V) 3158200 3158201 1
* Blower Hose 3242539 3242539 1 25 Purge Suction Filter Silencer Assembly 3158021 3158021 1
* Blower Inlet Silencer Element 3159138 3159138 1 1 26 Repress/Sweep Valve (V11) 4010086 4010086 1 1
* Repress/Sweep Solenoid Valve (Sol ‘E’) 3154249 3154249 1 1 27 Repress/Sweep Check Valve (V12 & V13) 3152094 3152094 1 2 29 Chamber Blowdown Valve 4009900 4009900 2 42 Energy Management Pilot Operated Valve 1274209 1274209 1 43 Energy Management Sensor (RTD4/HS1) 3144864 3144864 1
* Energy Management Vent Needle Valve 3158747 3158747 1 44 Dew-point Sensor - Ceramic 3154859 3154859 1
* Dryer Controller 7417845 7417845 1
* Heater Contactor 3158650 3158650 1
* Blower Motor Contactor 3149521 3149521 1
* Relay, Overload, 3Pole, 600V Max, 5.4-27Amp 3158481 3158481 1
* Relay, SPDT 12VDC Coil, 120VAC, 10A (1CR, 2CR, 3CR, 4CR, 5CR) 3154359 3154359 1 5
* Fuse 1.25A 600V (3FU) 1240671 1240671 1 1
* Fuse .5A 600V (1FU, 2FU) 1241118 1241118 1 2
* Temperature Controller 7416897 7416897 1
* Timer, SPDT, 0.1S-120HR 3203083 3203083 1
Desiccant Evaluation Kit Pre-Filter Assembly PCC124004G65 PCC136003G97
Auto-Drain 3044466 3044466
Afterlter Assembly PCC124004G65 PCC136003G97
NOTES:
1. Parts and Maintenance Kits are for standard builds only. Please contact the factory with your dryer serial number for assistance on identifying spare parts and maintenance kits for your specic unit.
2. All quantities for one dryer.
3. ID# correspond to P&ID legend (* Not pictured in diagrams.)
3152117 3152117 1 2
3150628 3150628
SAFETY
STOCK
DRYER
QTY.
Phone: 1+ 352-873-5793 FAX: +1 352-873-5770 Email: ppc.americas.am@spx.com Web: www.spx.com/pneumatic-products
45
Page 48
Replacement Parts – Models 3200 through 4300
26
3
7
8
6
25
24
42 43
9
1 1A
REAR VIEW
10 4
AIR
OUT
23
LEFT CHAMBER
11
1514
RIGHT CHAMBER
11
CONTROL ENCLOSURE
HIGH TENSION ENCLOSURE
30
46
44
2
5
29
FRONT VIEW SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
AIR
IN
Phone: 1+ 352-873-5793 FAX: +1 352-873-5770 Email: ppc.americas.am@spx.com Web: www.spx.com/pneumatic-products
Page 49
MODEL
3200 3600 4300
MAINTENANCE KITS
Year 2 Maintenance Kit Elements*, Mufer, Drain, Desiccant Evaluation Kit IBPMK2-24-A IBPMK2-26-A IBPMK2-28-A
Year 3 Maintenance Kit
Year 4 Maintenance Kit Elements*, Mufer, Drain, Desiccant Evaluation Kit IBPMK4-24-A IBPMK4-26-A IBPMK4-28-A
Year 5 Maintenance Kit
Desiccant Kit IBPDES-24 IBPDES-26 IBPDES-28
*NOTE: Replacement Prelter and Afterlter elements are included in Standard Kits.
All the contents of the 2 Year Kit, Pressure
Switches, Valve Repair Kits, Blower Hose
All the contents of the 4 Year Kit, Pressure
Switches, Valve Repair Kits, Blower Hose
IBPMK3-24-A IBPMK3-26-A IBPMK3-28-A
IBPMK5-24-A IBPMK5-26-A IBPMK5-28-A
REPLACEMENT PARTS
ID# DESCRIPTION
1 Inlet Valve Assembly (V1 & V2)
* Solenoid Valve (Sol “A”, “B”) 3203652 3203652 3203652 1 2 1A Inlet Pilot Operated Valve 3155189 3155189 3155189 1 2
2 Purge Exhaust Valve Assembly (V3 & V4) 3152093 3152093 3152093 1 2
* Solenoid Valve (Sol “C”, “D”) 4009880 4009880 4009880 1 2
3 Purge Check Valve (V5 & V6) 3160064 3160064 3160064 1 2
4 Outlet Check Valve (V7 & V8) 3160061 3160061 3160061 1 2
5 Depress Valve (V9, V10) 4010086 4010086 4010087 1 2
* Depress Solenoid Valve (Sol "F", "G") 3203652 3203652 3158444 1 2
6 Purge Heater 1181451 1185499 1276268 1
7 Heater Temperature Thermocouple (1TC) 3153971 3153971 3153971 1
8 Heater Overtemperature RTD (RTD3) 3153224 3153224 3153224 1
9 Chamber RTD (RTD1, RTD2) 3153224 3153224 3153224 1 2 10 Pressure Relief Valve 3100938 3100938 3119442 1
Chamber Pressure Gauge 4011096 4011096 4011096 2
11 12 Chamber Pressure Switch (1PS, 2PS) 3149016 3149016 3149016 1 2
* Chamber Depressurization Pressure Switch (3PS, 4PS) 3152525 3152525 3152525 1 2 14 Pilot Air Filter Element 3158592 3158592 3158592 1 1 15 Pilot Air Pressure Regulator 3154237 3154237 3154237 1 17 Depress Mufer 3130773 3130773 3130773 2
* Depress Mufer Replacement Core 3121200 3121200 3121200 1 2 23 Purge Pressure Gauge 3158833 3158833 3158833 1 24 Blower (460V) 3158474 3158475 3158475 1
* Purge Blower Throttling Valve 1170918 1170918 1170918 1
* Expansion Joint 1206327 1206327 1206327 1 25 Purge Suction Filter Silencer Assembly 3032795 3032795 3032795 1
* Blower Inlet Silencer Element 3504482 3504482 3504482 1 1 26 Repress/Sweep Valve (V11) 4010086 4010087 4010087 1 1
* Repress/Sweep Solenoid Valve (Sol ‘E’) 3203652 3203652 3158444 1 1 27 Repress/Sweep Check Valve (V12 & V13) 3152094 3152095 3152095 1 2 29 Chamber Blowdown Valve 4009900 4009900 4009900 2 30 Heater High Inlet Temperature Switch (1TS) 3159879 3159879 3159879 1 42 Energy Management Pilot Operated Valve 1274209 1274209 1274209 1 43 Energy Management Sensor (RTD4/HS1) 3144864 3144864 3144864 1
* Energy Management Vent Needle Valve 3158747 3158747 3158747 1
Dew-point Sensor - Ceramic 3154859 3154859 3154859 1
44
* Dryer Controller 7417845 7417845 7417845 1
* Heater Contactor 3158326 3158326 3158326 1
* Blower Motor Contactor 3158653 3158653 3158653 1
* Relay, Overload, 3Pole, 600V Max, 3.2-16Amp 3158551 3158551 3158551 1
* Relay, SPDT 12VDC Coil, 120VAC, 10A (1CR, 2CR, 3CR, 4CR, 5CR) 3154359 3154359 3154359 1 5
* Fuse 1.25A 600V (3FU) 1240671 1240671 1240671 1 1
* Fuse .5A 600V (1FU, 2FU) 1241118 1241118 1241118 1 2
* Timer, SPDT, 0.1S-120HR 3203083 3203083 3203083 1
* Temperature Controller 7416897 7416897 7416897 1
Desiccant Evaluation Kit 3150628 3150628 3150628 Pre-Filter Assembly PCC136003G97 PCC136003G97 PCC148004G97
Auto-Drain 3044466 3044466 3044466
Afterlter Assembly PCC136003G97 PCC136003G97 PCC148004G97
NOTES:
1. Parts and Maintenance Kits are for standard builds only. Please contact the factory with your dryer serial number for assistance on identifying spare parts and maintenance kits for your specic unit.
2. All quantities for one dryer.
3. ID# correspond to P&ID legend (* Not pictured in diagrams.)
3152117 3152798 3152798 1 2
SAFETY
STOCK
DRYER
QTY.
Phone: 1+ 352-873-5793 FAX: +1 352-873-5770 Email: ppc.americas.am@spx.com Web: www.spx.com/pneumatic-products
47
Page 50
Page 51

WARRANTY

The manufacturer warrants the product manufactured by it, when properly installed, operated, applied, and maintained in accordance with the procedures and recommendations outlined in the manufacturer’s instruction manuals, to be free from defects in material or workmanship for a period of one (1) year from the date of shipment from the manufacturer or the manufacturer’s authorized distributor, or eighteen months from the date of shipment from the factory, whichever occurs rst, provided such defect is discovered and brought to the manufacturer’s attention the aforesaid warranty period. The manufacturer will repair or replace any product or part determined to be defective by the manufacturer within the warranty period, provided such defect occurred in normal service and not as the result of misuse,
abuse, neglect, or accident.
The warranty covers parts and labor for the warranty period. Repair or replacement shall be made at the factory or the installation site, at the sole option of the manufacturer. The manufacturer must rst authorize any service performed on the product by anyone other than the manufacturer. Normal maintenance items requiring routine replacement are not warranted. Unauthorized service voids the warranty and any resulting charge or subsequent claim will not be paid.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WRITTEN, ORAL, OR STATUTORY, AND IS EXPRESSED IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN, MANUFACTURE, OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER, REPORT, REPAIR, OR MODIFY LATENT DEFECTS INHERENT THEREIN. THE MANUFACTURER, HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE PRODUCT OR OTHER INCIDENTAL OR CONSEQUENTIAL COSTS, EXPENSES, OR DAMAGES INCURRED BY THE BUYER, WHETHER ARISING FROM BREACH OF WARRANTY, NEGLIGENCE OR STRICT LIABILITY IN TORT.
The manufacturer does not warranty any product, part, material, component, or accessory manufactured by others and sold or supplied in connection with the sale of the manufacturer’s products.
AUTHORIZATION FROM THE SERVICE DEPARTMENT IS NECESSARY BEFORE
MATERIAL IS RETURNED TO THE FACTORY OR IN-WARRANTY REPAIRS ARE MADE.
SERVICE DEPARTMENT: (352) 873-5793
Page 52
IBP SERIES
Blower Purge Desiccant Compressed Air Dryer
SPX
4647 S.W. 40th Avenue
Ocala, Florida 34474-5788 U.S.A.
P: (352) 873-5793
F: (352) 873-5770
E: ppc.americas@spx.com
www.spx.com/pneumatic-products
Improvements and research are continuous at SPX.
Specifications may change without notice.
ISSUED 07/2014 Form No.: 3158144 Revision: I
COPYRIGHT ©2014 SPX Corporation
Loading...