Spring Air Systems REV-LOW DN-B-F User Manual

Page 1
REV-LOW Hood
Dry Extractor
Box Canopy
DN-B-F
The REV-LOW hood is used on all single row cooking equipment lineups, wall mounted. The unit is ceiling hung with a recommended mounting height of 6'-6" (1981 mm) from the lower edge of the canopy to the floor. The ventilator is installed with the core extractor section over the cook’s head. The hood is finished with a number 4 finish on exposed sides. The REV-LOW hood is available with fluorescent or incandescent lights wired to a J-box.
Efficiency
The REV-LOW hood is a revolutionary idea in commercial kitchen ventilator design. The REV-LOW allows the exhaust flow to be field adjusted from 90cfm/ft to 450cfm/ft over each appliance without affecting the overall efficiency of the ventilator. Your kitchen will exhaust the lowest minimum required anywhere to ventilate the appliances located under the hood. After your kitchen is complete, appliances can be Relocated, Added, or Removed from under the hood! It’s a simple adjustment to fine-tune your
Dead Weight Fire Damper
Model DN-B-F
Patent No.
5,540,214
ventilator to provide excellent smoke capture with maximum grease extraction.
Exhaust and Supply
The REV-LOW hood exhaust calculations are outlined in the REV-LOW Engineering Manual. The complete kitchen ventilation system must be balanced, such that a minimum of 80% continuous heated makeup air is provided through dedicated makeup air systems or the kitchen A/C units. It is good engineering practice to provide this heated fresh air into the kitchen space. The heated fresh air should not exceed 90 percent of the total exhaust volume.
Page 2
REV LOW Exhaust Volume Vs Exhaust Duct Size
Exhaust
Volume
CFM l/s W x L
450 212 10 x 4 254 x 102 3500 1652 10 x 33.5 254 x 851 500 236 10 x 4.5 254 x 114 3625 1711 10 x 34.5 254 x 876 625 295 10 x 6.0 254 x 152 3750 1770 10 x 36.0 254 x 914 750 354 10 x 7.0 254 x 178 3875 1829 10 x 37.0 254 x 940 875 413 10 x 8.0 254 x 203 4000 1888 14 x 27.0 356 x 686 1000 472 10 x 9.5 254 x 241 4125 1947 14 x 28.0 356 x 711 1125 531 10 x 10.5 254 x 267 4250 2006 14 x 29.0 356 x 737 1250 590 10 x 12.0 254 x 305 4375 2065 14 x 30.0 356 x 762 1375 649 10 x 13.0 254 x 330 4500 2124 14 x 30.5 356 x 775 1500 708 10 x 14.0 254 x 356 4625 2183 14 x 31.5 356 x 800 1625 767 10 x 15.5 254 x 394 4750 2242 14 x 32.5 356 x 826 1750 826 10 x 16.5 254 x 419 4875 2301 14 x 33.0 356 x 838 1875 885 10 x 18.0 254 x 457 5000 2360 14 x 34.0 356 x 864 2000 944 10 x 19.0 254 x 483 5125 2419 14 x 35.0 356 x 889 2125 1003 10 x 20. 254 x 508 5250 2475 14 x 36.0 356 x 914 2250 1062 10 x 21.5 254 x 546 5375 2537 14 x 36.5 356 x 927 2375 1121 10 x 22.5 254 x 572 5500 2596 14 x 37.5 356 x 953 2500 1180 10 x 24.0 254 x 610 5625 2655 14 x 38.5 356 x 978 2625 1239 10 x 25.0 254 x 635 5750 2714 14 x 39.0 356 x 991 2750 1298 10 x 26.0 254 x 660 5875 2773 14 x 40.0 356 x 1016 2875 1357 10 x 27.5 254 x 699 6000 2832 14 x 41.0 356 x1041 3000 1416 10 x 28.5 254 x 724 6125 2891 14 x 42.0 356 x 1067 3125 1475 10 x 30.0 254 x 762 6250 2950 14 x 42.5 356 x1080 3250 1534 10 x 31.0 254 x 787 6375 3008 16 x 38.0 406 x 965 3375 1593 10 x 32.0 254 x 813 6500 3067 16 x 39.0 406 x 991
1. If exact exhaust volume is not indicated use duct size closest to required exhaust.
2. Model B water wash hoods and dry extractors have 1.5” W.C. (0.38kPa) for exhaust flow rates from 90 to 450 CFM/ft (140 to 700 l/s/m)
3. Refer to the REV-LOW Engineering Manual for detailed exhaust air volume calculations.
Spring Air Systems Model No. DN-B-F Hood Specification
The REV-LOW hood dry extractor shall be a Spring Air Systems model no. DN-B-F, box canopy, high efficiency, hood, ULC listed, and built in accordance with the NFPA-96.
The unit casing shall be a minimum 18 GA. stainless steel on all exposed surfaces. The ventilator shall have a full-length inlet slot, a centrifugal vortex chamber, a vortex and a VARIFLOW baffle. The vortex chamber shall provide a full 270-degree centrifugal spin around the vortex baffle. The VARIFLOW baffles are field adjustable without special tools to provide the minimum exhaust volume. Both chambers, the VARIFLOW baffles, the fire suppression nozzles shall be fully accessible through removable front grease inserts. The grease inserts shall
Duct Collar Size Exhaust
W x L
in x in
mm x mm
Duct Collar Size
Volume
CFM l/s W x L
in x in
W x L mm x mm
also be removable without special tools. The grease trough and cup shall be constructed of
stainless steel. The fire damper shall be activated by a fusible link and dead weight arrangement. The hood shall have ______ incandescent/fluorescent lights evenly spaced along the length of the hood.
Engineering Data
Item Number: ___________________ Model Number: __________________ Number of Sections: __________________ Hood Length: __________________ Hood Width: __________________ Lights: __________________ Exhaust Volume: __________________ No. of Duct Collars: __________________ Size of Duct Collar __________________ Static Pressure: __________________
dnbf
Spring Air Systems Inc. Phone: 905-338-2999, Fax: 905-338-0179,e-mail: info@springairsystems.com