KES Maintenance Sch edule............................................................ 22
KES Enviro Start-Up Report............................................................. 24
Filter Frequency Chart...................................................................... 26
KES OPERATIONS AND MAINTENANCE MANUAL
INTRODUCTION
The SPRING AIR SYSTEMS INC. kitchen Enviro system (KES), Exhaust Cleaning Assembly for Kitchen
Exhaust Duct, “Enviro Unit” is ULC and UL listed for use in a commercial kitchen exhaust system. KES
units are available in sizes ranging from 1,000 CFM to 40,000 CFM for indoor or outdoor applications.
The primary function of a KES Enviro unit is to filter the grease, lint and dust particles and remove the odor
from the exhaust air.
The Underwriters’ Laborato ries of Canada Limited (ULC) listing allows the use of non-NFPA-96 exhaust
ductwork after the exhaust air is discharged from the KES unit. In other words the discharge ductwork can
be treated similar to standard HVAC ducting. Also after the kitchen exhaust air has been treated with the
KES unit the exhaust can be discharged outdoors at low levels.
The Underwriters Laboratories Inc. (UL) listing allows the kitchen exhaust air to be discharge to atmosphere
at low levels.
Prior to any installation the installer must seek approval from the authorities having jurisdiction.
THE SYSTEM
The grease -laden air rises from the cooking equipment into a UL or ULC exhaust hood. The exhaust hood
removes some of the airborne grease particulate. Typically most micron and submicron particles escape
Exhaust to
atmophere at
low level
Discharge Ductwork
KESF Fan Box
Interconnecting Ductwork
KES-ISH Filter Box
Water Wash
Panel
Remote
RPW(D) Panel
NFPA-96 Ductwork
Listed Exhaust Hood
Appliance Line-up
into the exhaust ductwork. The exhaust ducting is connected from the hood to the inlet of the KES Enviro
unit. This exhaust ductwork must be supplied and installed in accordance with the NFPA -96 code.
KES System Schematic
Figure 1
Within the KES unit the exhaust air travels through three stages of particulate filters:
1Two (2) inches pleated - 30 percent ASHRAE 52-76 prefilters.
2Twenty-one (21) to twenty -two (22) inch bag - 90 percent ASHRAE 52-76 filters.
3Twelve (12) inches box - 95 percent DOP filters.
Enviro Maintenance Manual 2004
KES-ISH
KESF
Once through the particulate filter sections the exhaust air enters the optional odor removal section. The
odor section is only required when discharging cooking smells may be offensive. This section consists of
two optional odor removal systems.
1.Odor Cells filled with activated alumina impregnated with potassium permanganate. The odor is controlled
through a combination of sorption and the chemical modification of the gaseous contaminates. The
odor media is non-toxic and non-flammable.
1.Odor spray solution. The odor is control by spraying an odor reducer into the exhaust air stream
intermittently during the operation of the cooking systems.
EXHAUST OUTLET
TO THE OUTDOORS
Exhaust Fan
Odour Removal Section
EXHAUST OUTLET
TO THE KESF FAN
Fire Damper
Box Filter
Bag Filter
2 inch prefilter
Pressure switches
LV-10 Panel
2.
KES-ISH and KESF Enviro components
Figure 2
The exhaust air is discharged from the KES unit through a single width, single inlet (SWSI) or double width,
double inlet (DWDI) exhaust fan. The discharge ductwork transfers the exhaust air outdoors.
CONTROL SYSTEM
Water Wash Ventilator System: SB, SBA Panels
The KES unit off/on operation is controlled from the SB, or SBA water wash ventilator control panel. Power
is fed to the RPW10 panel through terminals 1 & 4. When the fan selector switch on the water wash control
panel closes a signal is sent through terminal 3 to the RPW10 panel to activate the KES unit.
INTERNAL WIRING BY SPRING AIR
FAN SWITCH
OFF/ON
L N
Mo 09:00
01. 20. 03
LOGO!
Q1
Q2
1 2
1 2 1 2Q31 2
H
I4I1 I2 I3 I5 I6 I7
ESC OK
HOT WATER SOLENOID
CURCUIT BREAKER
I8
Q4
B
DETERGENT
PUMP
WASH PILOT
C
FAN PILOT
OPTIONAL COLD
WATER SOLENOID
1
1
7
3
8
9
4
4
G
ALL REMOTE ELECTRIAL WIRING
SHALL CONFORM TO ALL LOCAL
AND NATIONAL CODE REQUIREMENTS
REMOTE WIRING BY TRADES
1
POWER SUPPLY TO THE SB10H/C PANEL
4
24 HOURS/DAY - 120V/1/60 - 15 AMPS
1
THREE (3) WIRES TO THE KES UNIT RPW10 CONTROL
3
PANEL - 120V/1/60 - 5 AMPS MAXIMUM.
4
4
(OPTIONAL) POWER SUPPLY TO SUPPLY FAN
9
MOTOR STARTER - 120V/1/60 - 2 AMPS MAXIMUM
8
(OPTIONAL) THREE (3) WIRES TO SUPPLY AIR MOTORIZED
4
SHUTOFF DAMPER AND END SWITCH 120V/1/60
9
2 AMPS MAXIMUM.
NORMALLY OPEN
END SWITCH
1
WHITE
RED
7
NOTE 1:
TWO (2) WIRES TO THE
WET CHEMICAL CONTROL
HEAD 120V/1/60 - 1A.
EXHAUST INLET
FROM THE HOOD
Typical KES wiring to SB10C water wash panel
Figure 3
Enviro Maintenance Manual 2004
The “NORMAL” operation pilot energizes on the RPW10 remote kitchen annunciation panel. After 30
seconds the RPW10 control circuit is activated. The RPW10 is a stainless steel panel located remote from
the SB or SBA panel. See Figure 5 for RPW10 wiring and dimensions. The KES exhaust fan motor is
energized through the terminals 5 & 4 to the LV10 J-Box located on the KESF fan section. See figure 11 for
internal wiring of the LV10 J-box. See figure 3 or 5 for a SB water wash panel.
Mo 09:00
01. 20. 03
LOGO!
Typical KES wiring to SBA10C water wash panel
Figure 4
RPW10 ELECTRICAL DATA
OVERIDE SWITCH
I3I2NLI1
I4
Mo 09:00
01. 20. 03
LOGO!
1 2Q1211
15 AMP CURCUIT BREAKER
I7 I8I6I5
L
AUX!
OKESC
Q3
Q4Q2
2Q312
I4I3I1NI2
RUN/STOP
Q2Q1
21
21
Q4
21
21
WARNING
NORMAL
PREFILTER CLOGGED
BAG FILTER CLOGGED
BOX FILTER CLOGGED
FILTER REMOVED
FIRE
1
3
4
1
4
5
12
13
14
15
16
17
18
4
9
R6
8
1
7R6
THREE (WIRES) TO THE WATER WASH CONTROL
PANEL - 120V/1/60 - 10 AMPS
TO KES UNIT LV10 PANEL ON FILTER
BOX - TEN (10) WIRES
120V/1/60 - 10 AMPS.
(OPTIONAL) POWER SUPPLY TO SUPPLY FAN
MOTOR STARTER, 120V/1/60 - 2 AMPS
(OPTIONAL) THREE (3) WIRES TO
MOTORIZED INLET DAMPER AND END
SWITCH, 120V/1/60 - 1 AMP
TWO (2) WIRES TO THE WET CHEMICAL
CONTROL HEAD, 120V/1/60 - 1AMP
NORMALLY OPEN
END SWITCH
1
WHITE
7
RED
NORMALLY OPEN
END SWITCH
WHITE
RED
DRY CONTACT FOR BUILDING FIRE ALARM
FIRE ANUNCIATION, 5 AMPS MAXIMUM, N/O
RPW10 Wiring Schematic
Figure 5
POWER WIRING BY GENERAL CONTRACTOR
CONTROL WIRING BY MECHANICAL CONTACTOR
FACTORY WIRING BY SPRING AIR SYSTEMS
TERMINALDESCRIPTION
1&4
5
12
13
14
15
16
17
18
20&21
LEGEND
POWER SUPPLY FROM BREAKER PANEL
KES FAN/NORMAL OPERATION
PREFILTER CLOGGED
BAG FILTER CLOGGED
BOX FILTER CLOGGED
FILTER OUT/LOW AIR
FIRESTAT - HIGH LIMIT
0DOR SPRAY UNIT
LV10 RESET
BMS START/STOP
Enviro Maintenance Manual 2004
PANEL MOUNTING
HOLES LOCATED
IN PANEL BACK.
8.0"
5.0"
FILTER
OVERIDE
NORMAL
PREFILTER
CLOGGED
BAG FILTER
CLOGGED
WARNING
FIRE
BOX FILTER
CLOGGED
FILTER
REMOVED
14.0"
Remote RPW10 Panel Dimensions
Figure 6
Water Wash Ventilator System: AP, MP Panels
The KES unit off/on operation is controlled from the MP or AP water wash ventilator control panel. The fan
selector switch on the water wash control panel closes and sends power through terminals 3 & 4 to the
RPW10 remote panel to energize the exhaust fan through terminals 5 & 4 in the LV -10 J-Box. (The LV10 JBox is mounted on the KES-ISH filter section).
The “NORMAL” operation pilot energizes on the RPW10. After 30 seconds the KES control circuit within the
RPW10 remote panel is activated. See Figure 5 for RPW10 internal wiring. The exhaust fan motor is
energized through the terminals 9 & 4 to the motor starter located on the KESF fan section. See figure 11
for internal wiring of LV10 J-Box with RPW10 remote panel.
Mo 09:00
01. 20. 03
LOGO!
Typical KES wiring to AP20C water wash panel
AUX!
Figure 7
Enviro Maintenance Manual 2004
KESF
EXHAUST DISCHARGE
DUCTWORKDUCTWORK AS REQUIRED
POWER SUPPLY
TO KESF FAN UNIT
FIELD INTERCONNECTING
INTERLOCK BETWEEN KES-ISH LV10 AND KESF MOTOR STARTER
THREE (3) WIRES TO
RPW10 PANEL FROM
WATER WASH PANEL
POWER SUPPLY
TO SB10 WASH PANEL
120V/1/60
KES-ISH
POWER SUPPLY
TO RPD10 REMOTE
WATER WASH
PANEL MODEL
SB10C OR SB10H
TEN (10) WIRES FROM
THE RPW10 CONTROLLER
FROM THE KES-ISH LV10
J-BOX - 120V/1/60
CONTROLLER
EXHAUST INLET
RPW10
DUCTWORK
Remote wiring of KES Enviro units with Water Wash Hood and Panel
Figure 8
Filter Hood or Dry Grease Extractor: RPD10 Remote Panel
The KES unit off/on operation is controlled from RPD10 remote annunciation panel. The fan selector switch
on the RPD10 remote panel closes and sends power through terminals 5 & 4 to the LV10 J-Box to energize
the exhaust fan circuit. (The LV10 J-Box is mounted on the KES-ISH filter section). The “NORMAL”
operation pilot on the RPD10 remote kitchen annunciation panel energizes and after 30 seconds the KES
control circuit within the RPD10 remote panel is activated. The exhaust fan motor is energized through the
terminals 5 & 4 to the motor starter. See fi gure 8 for the RPD10 remote panel wiring and figure 9 for
dimensions.
RPD10A ELECTRICAL DATA
FAN SWITCH
OFF/ON
OVERIDE SWITCH
I4I2L N I1 I3
I5 I6 I7 I8 L N
Mo 09:00
01. 20. 03
LOGO!
Q3Q1
1 2Q21 2 1 2Q41 2
15 AMP CURCUIT BREAKER
AUX!
ESC OK
I1 I2 I3 I4
RUN/STOP
Q1
2
1
Q3
2
1
POWER SUPPLY TO THE KES UNIT
RPD10 CONTROL PANEL - 120V/1/60 - 15 AMPS
OPTIONAL BMS START/STOP - 120V/1/60
CLOSE CONTACT ACROSS 20&21 TO START UNIT
OPEN CONTACT ACROSS 20&21 TO STOP UNIT
JUMPER MUST BE IN PLACE AS NOTED TO OPERATE FROM BMS
TO KES UNIT LV10 PANEL ON FILTER
BOX - TEN (10) WIRES
120V/1/60 - 10 AMPS.
(OPTIONAL) POWER SUPPLY TO SUPPLY FAN
MOTOR STARTER, 120V/1/60 - 2 AMPS
(OPTIONAL) THREE (3) WIRES TO
MOTORIZED INLET DAMPER AND END
Q2
1 2
Q4
1 2
SWITCH, 120V/1/60 - 1 AMP
TWO (2) WIRES TO THE WET CHEMICAL
CONTROL HEAD, 120V/1/60 - 1AMP
DRY CONTACT FOR BUILDING FIRE ALARM
FIRE ANUNCIATION, 5 AMPS MAXIMUM, N/O
OVERIDE
POWER WIRING BY GENERAL CONTRACTOR
CONTROL WIRING BY MECHANICAL CONTACTOR
FACTORY WIRING BY SPRING AIR SYSTEMS
TERMINAL
POWER SUPPLY FROM BREAKER PANEL
1&4
KES FAN/NORMAL OPERATION
5
PREFILTER CLOGGED
12
BAG FILTER CLOGGED
13
14BOX FILTER CLOGGED
FILTER OUT/LOW AIR
15
FIRESTAT - HIGH LIMIT
16
0DOR SPRAY UNIT
17
18
LV10 RESET
BMS START/STOP
20&21
PANEL MOUNTING
HOLES LOCATED
IN PANEL BACK.
KES
OFF/ON
FILTER
NORMAL
PREFILTER
CLOGGED
BAG FILTER
CLOGGED
8.0"
RPD10 DIMENSIONAL DATA
LEGEND
DESCRIPTION
WARNING
FIRE
BOX FILTER
CLOGGED
FILTER
REMOVED
5"
14.0"
RPD10 Wiring Schematic
Figure 9
Enviro Maintenance Manual 2004
RPD10 Internal Wiring
Figure 10
PANEL MOUNTING
HOLES LOCATED
IN PANEL BACK.
5"
KES
OFF/ON
FILTER
OVERIDE
NORMAL
PREFILTER
CLOGGED
BAG FILTER
CLOGGED
8.0"
RPD10 Remote Panel Dimensions
Figure 11
Enviro Maintenance Manual 2004
WARNING
FIRE
BOX FILTER
CLOGGED
FILTER
REMOVED
14.0"
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.