Spirax-Sarco Limited grants the legal user of this product (or device) the right to
use the Work(s) solely within the scope of the legitimate operation of the product
(or device). No other right is granted under this licence. In particular and without
prejudice to the generality of the foregoing, the Work(s) may not be used, sold,
licensed, transferred, copied or reproduced in whole or in part or in any manner
or form other than as expressly granted here without the prior written consent of
Spirax-Sarco Limited.
1. Safety information
Safe operation of this unit can only be guaranteed if it is properly installed,
commissioned and maintained by a qualified person (see Section 1.11) in compliance
with the operating instructions. General installation and safety instructions for
pipeline and plant construction, as well as the proper use of tools and safety
equipment must also be complied with.
The product is designed and constructed to withstand the forces encountered
during normal use.
Use of the product for any other purpose, or failure to install the product in
accordance with these Installation and Maintenance Instructions, could cause
damage to the product, will invalidate the marking, and may cause injury or
fatality to personnel.
IM-P192-02 MI Issue 22
EMC directive
The product complies with the Electromagnetic Compatibility Directive
2004 / 108 / EC. A technical file with a reference number of 'UK Supply TVA flowmeter'
supports the Spirax Sarco claim that the product complies with the requirements of
the Directive and the product can be used in Class A (heavy industrial) and Class B
(domest ic / commercial areas).
The following conditions should be avoided as they may create interference above
the heav y industrial limits if:
The product or its wiring is located near a radio transmitter.
-
Cellular telephones and mobile radios may cause interference if used within
-
approximately 1 metre (39") of the product or its wiring. The actual separation
distance necessary will vary according to the surroundings of the installation
and the power of the transmitter.
If this product is not used in the manner specified by this IMI, then the protection
provided may be impaired.
1.1 Intended use
Referring to the Installation and Maintenance Instructions, name-plate and Technical
Information Sheet, check that the product is suitable for the intended use / application.
The product listed complies with the requirements of the European Pressure
Equipm ent Direc tive 97 / 23 / EC, car ries the mark when so required.
The product falls within the following Pressure Equipment Directive categories:
Product
TVA flowmetering
system
i) The product has been specifically designed for use on saturated and superheated
steam only which is in Group 2 of the above mentioned Pressure Equipment
Directive.
ii) Check material suitability, pressure and temperature and their maximum and
minimum values. If the maximum operating limits of the product are lower than
those of the system in which it is being fitted, or if malfunction of the product
could result in a dangerous overpressure or overtemperature occurrence, ensure
a safety device is included in the system to prevent such over-limit situations.
iii) Determine the correct installation situation and direction of fluid flow.
iv) Spirax Sarco products are not intended to withstand external stresses that may
be induced by any system to which they are fitted. It is the responsibility of the
installer to consider these stresses and take adequate precautions to minimise
them.
v) Remove protection covers from all connections and protective film from all name-
plates, where appropriate, before installation on steam or other high temperature
applications.
IM-P192-02 MI Issue 23
DN50 to DN100-1--
Group 1
Gases
Group 2
Gases
Group 1
Liquids
Group 2
Liquids
1.2 Access
Ensure safe access and if necessary a safe working platform (suitably guarded)
before attempting to work on the product. Arrange suitable lifting gear if required.
1.3 Lighting
Ensure adequate lighting, particularly where detailed or intricate work is required.
1.4 Hazardous liquids or gases in the pipeline
Consider what is in the pipeline or what may have been in the pipeline at some
previous time. Consider: flammable materials, substances hazardous to health,
extremes of temperature.
1.5 Hazardous environment around the product
Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases,
extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive
noise, moving machinery.
1.6 The system
Consider the effect on the complete system of the work proposed. Will any proposed
action (e.g. closing isolation valves, electrical isolation) put any other part of the
system or any personnel at risk?
Dangers might include isolation of vents or protective devices or the rendering
ineffective of controls or alarms. Ensure isolation valves are turned on and off in a
gradual way to avoid system shocks.
1.7 Pressure systems
Ensure that any pressure is isolated and safely vented to atmospheric pressure.
Consider double isolation (double block and bleed) and the locking or labelling of
closed valves. Do not assume that the system has depressurised even when the
pressure gauge indicates zero.
1.8 Temperature
Allow time for temperature to normalise after isolation to avoid the danger of burns
and consider whether protective clothing (including safety glasses) is required.
1.9 Tools and consumables
Before starting work ensure that you have suitable tools and / or consumables
available. Use only genuine Spirax Sarco replacement parts.
1.10 Protective clothing
Consider whether you and /or others in the vicinity require any protective clothing to
protect against the hazards of, for example, chemicals, high / low temperature,
radiation, noise, falling objects, and dangers to eyes and face.
IM-P192-02 MI Issue 24
1.11 Permits to work
All work must be carried out or be supervised by a suitably competent person.
Installation and operating personnel should be trained in the correct use of the product
according to the Installation and Maintenance Instructions.
Where a formal 'permit to work' system is in force it must be complied with. Where
there is no such system, it is recommended that a responsible person should know
what work is going on and, where necessary, arrange to have an assistant whose
primary responsibility is safety.
Post 'warning notices' if necessary.
1.12 Handling
Manual handling of large and /or heavy products may present a risk of injury. Lifting,
pushing, pulling, carrying or supporting a load by bodily force can cause injury
particularly to the back. You are advised to assess the risks taking into account the
task, the individual, the load and the working environment and use the appropriate
handling method depending on the circumstances of the work being done.
1.13 Residual hazards
In normal use the external surface of the product may be very hot. If used at the
maximum permitted operating conditions the surface temperature of some products
may reach temperatures of 250 °C (482 °F).
Many products are not self-draining. Take due care when dismantling or removing the
product from an installation (refer to 'Maintenance instructions').
1.14 Freezing
Provision must be made to protect products which are not self-draining against frost
damage in environments where they may be exposed to temperatures below freezing
point.
1.15 Disposal
Unless otherwise stated in the Installation and Maintenance Instructions, this product
is recyclable and no ecological hazard is anticipated with its disposal providing due
care is taken.
1.16 Returning products
Customers and stockists are reminded that under EC Health, Safety and Environment
Law, when returning products to Spirax Sarco they must provide information on
any hazards and the precautions to be taken due to contamination residues or
mechanical damage which may present a health, safety or environmental risk. This
information must be provided in writing including Health and Safety data sheets
relating to any substances identified as hazardous or potentially hazardous.
IM-P192-02 MI Issue 25
2. General product information
T h i s ma n ua l ex pl a in s how to i n s t a l l , co m m i s s i on an d ma in t ai n the S p ir a x Sarc o T V A o w m e t e r
for use on saturated and superheated steam.
2.1 Product description
The Spirax Sarco T VA owmeter is designed to reduc e the cost of owmetering and is used
as an accurate means to measure steam owrates and record total ow.
For satur ated steam installati ons the T VA ow meter is a stand alone device and requires no
o t h er e qui p m en t, s u c h as d i f fe r e n t ial p res s u re t ra n s m it te r s , p res s u r e se n s o rs, e tc . to c al cu l a t e
mass owrates of saturated steam.
With superheated steam installations, the addition of the pressure sensing kit is required to
ena b le mas s owra t es to be me asu r ed whe r e the re l ati o n bet w e en pr e s sur e and tem p era t ure
has been lost (steam saturation curve).
2.2 Equipment delivery and handling
Factory shipment
Prior to shipment, the Spirax Sarco TVA owmeter is tested, calibrated and inspected to
ensure proper operation, including the wired communications.
Receipt of shipment
Each carton should be inspected at the time of delivery for possible external damage. Any
visible damage should be recorded immediately on the carrier’s copy of the delivery slip.
Each car ton should be unpacked carefully and its contents checked for damage.
I f i t is f oun d t h a t so me i te ms h a ve bee n d a m ag ed o r ar e m i s si n g , not i f y S p ir ax S ar co i mm ed i a t el y
and provide full details. In addition, damage must be reported to the carrier with a request
for their on-site inspection of the damaged item and its shipping carton.
Storage
If a o wme ter is to be stor ed pr ior to ins t al lat ion , the envi ron menta l sto r ag e cond iti ons shou ld
be at a temperature between 0°C and 55°C (32°F and 131 °F), and between 10% and 90 %
relative humidity (non- condensing).
2.3 Sizes and pipe connections
DN50, DN80 and DN100
The TVA owmeter is of a wafer design, suitable for tting between the following anges:
EN 1092 PN16, PN25 and PN40
BS 10 Table H
ASME B 16.5 Class 150 and 300
Korean Standard KS 20.
IM-P192-02 MI Issue 26
* Sensor cable
* 'U' syphon assembly
* Pressure sensor
Earth
cable
¼"
NPSM
boss
Earth
cable
TVA owmeter body
F
l
o
w
Flowmeter stem
* Items required for superheat operation
Fig. 1 TVA flowmeter
IM-P192-02 MI Issue 27
Electronics housing
2.4 Pressure / temperature limits
Pressure psi g
Steam
saturation
curve
Temperature °C
Pressure bar g
The product should not be used in this region due to the limitations of the software.
Temperature °F
Maximum allowable
PMA
pressure @ 239 °C (462 °F)
TMA Maximum allowable temperature 239 °C(462 °F)
Minimum allowable temperature0 °C (non-freezing) (32 °F non-freezing)
Maximum
operating
PMO
pressure for
saturated
steam service
Minimum operating pressure0.6 bar g(8.7 psi g)
TMO Maximum operating temperature239 °C(462 °F)
Minimum operating temperature 0 °C (non-freezing) (32 °F non-freezing)
Maximum electronics ambient temperature55 °C(131 °F)
Maximum electronics humidity level90% RH (non-condensing)
Maximum
differential
PMX
pressure
Cold hydraulic test pressure of:52 bar g(754 psi g)
Horizontal
ow
Vertical
ow
The pressure drop across the TVA owmeter at the maximum
rated ow is nominally 750 m bar (300 inches wg) for the DN50,
and 500 m bar (200 inches wg) for the DN80 and DN100
Saturated steam 32 bar g (464 psi g) otherwise as
Superheated
steam
Saturated
steam
Saturated
steam only
23 bar g @ 239 °C (333 psi g @ 462 °F)
32 bar g @ 239 °C (464 psi g @ 462 °F)
7 bar g @ 170°C (101 psi g @ 338 °F)
the specied ange rating
*
IM-P192-02 MI Issue 28
High pressure syphon tube assembly
Maximum design pressure80 bar g(1 160 psi g)
Maximum design temperature450 °C(842 °F)
Maximum working conditions60 bar g @ 450 °C (870 bar g @ 842 °F)
Pressure sensing kit
Maximum operating temperature125 °C(257 °F)
Minimum operating temperature0 °C (non-freezing) (32 °F non-freezing)
Maximum operating pressure50 bar g(725 psi g)
Maximum ambient temperature
(cable+connector)
Important note
*
CAUTION:
If the electronic housing is mounted at
an angle of more than 45° from the
vertically downward position the PMO
(maximum operating pressure) must
be limited to 7 bar g (101 psi g) and
saturated steam applications only.
70°C(158°F)
Limited to
7 bar g (101 psi g)
and
saturated steam
applications
only
The electronic housing must be
mounted vertically downward for all
superheated applications.
Fig. 2 Installation limiting conditions
IM-P192-02 MI Issue 29
For saturated steam
applications
over 7 bar g (101 psi g)
to 32 bar g (464 psi g) and all
superheated applications up to
23 bar g (333.5 psi g).
2.5 Technical data
IP ratingIP65 with correct cable glands.
Power supply Loop powered nominal 24 Vdc
4-20 mA (proportional to mass ow)
Outputs
Communication port
Performance
System uncertainty to ISO 17025
(95% condence to 2 STD)
Pulsed output V
R
10 kW, Von 0.7 V
min
EIA 232C 15 m limit - See Section 4.12
RS485 for longer distances
(conversion from RS232)
±2% of reading over the range of 10%
to 100% of maximum rated ow
Note: Dimension 'X' is a recommended minimum distance between the pressure tapping
and the flowmeter. However it can be installed at any distance provided the cable allows
(Standard cable length is 1 m).
X
kit
A
D
'U'
syphon
Any free hanging cable must be
Caution:
secured to prevent contact with the
Fig. 3
steam pipe.
F
G
C
E
IM-P192-02 MI Issue 211
3. Installation
Note: Before actioning any installation observe the 'Safety information' in Section 1.
To meet its specified accuracy and performance it is essential that the following installation
guidelines are followed carefully. For steam applications sound steam engineering practices
should be followed, including the use of separators. The installation must conform to all
relevant construction and electrical codes.
Limited to
7 bar g (101 psi g)
and
saturated steam
applications
only
CAUTION:
If the electronic housing is mounted
at an angle of more than 45° from the
vertically downward position the PMO
(maximum operating pressure) must
be limited to 7 bar g (101 psi g) and
saturated steam applications only.
The electronic housing must be
mounted vertically downward for all
superheated applications.
Fig. 4 Installation limiting conditions
For saturated steam
applications
over 7 bar g (101 psi g)
to 32 bar g (464 psi g) and all
superheated applications up to
23 bar g (333.5 psi g).
A by pa ss line wil l enabl e sa fe removal of the TVA o wm eter for ma in te nance or calib ra tion.
Closing valves V1 and V2 and opening va lve V3 wil l al low the TVA owmete r to be is ol ated
for re-zeroing (temperature to be <20°C).
V3
Strainer
Steam
Separator
Tra p se t
Fig. 5 Typical installation
V1
TVA
owmeter with
Superheat kit
tted
V2
Spool
piece
IM-P192-02 MI Issue 212
3.1 Environmental conditions
The owmeter should be located in an environment that minimises the effects of heat,
vibration, shock and electrical interference. (Pressure / temperature limits are detailed in
Section 2.4).
CAUTION: Do not lag (insulate) the TVA flowmeter or mating flanges as this may result
in excessive temperatures in the electronics. Exceeding specified temperature limits
will invalidate the warranty, adversely effect the performance and may damagethe TVA
flowmeter, see Figure 6.
Do not
insulate the anges of the TVA owmeter
Flow
Fig. 6 Pipeline insulation
Other considerations
Be sure to allow sufcient clearance for:
-
Installation of conduit / wiring.
Removal of the electronics enclosure cover.
-
Viewing of the display. Note electronics housing and display can be rotated.
-
Do not allow the earth cable to touch the steam pipe or damage to the sheath will occur.
-
Tie up any loose (excess) cable.
Warning: Do not install the flowmeter outdoors where it can be subjected to adverse
weather conditions like driving rain or where it can freeze.
IM-P192-02 MI Issue 213
3.2 Mechanical installation
Warning: Do not alter the adjustment nut at the back of the TVA flowmeter shaft, as
this will affect the flowmeters calibration.
Orientation
The TVA owmeter can be installed in any orientation when used on saturated steam
applications and when the pressure is below 7 bar g (101 psi g), see Figures 7, 8 and 9.
When the pressure is above 7 bar g (101 psi g) or used on a superheated steam application
the T VA owmeter must be installed in a hor izontal pipe, with the electronics housing below
the body, see Figure 9.
Note: The TVA owmeter operates with ow in one direction only. It is not intended for use
with bi-directional ow. The TVA owmeter is clearly marked with a direction of ow arrow.
Fig. 7
Vertical flow limited
to 7 bar g (101 psi g)
and saturated steam
applications only
Caution: If the electronic housing is
mounted at an angle of 45° (or more) from
the vertically downward position the PMO
(maximum operating pressure) must be
limited to 7 bar g (101 psi g) and saturated
steam applications only.
The electronic housing must be mounted
vertically downward for all superheated
applications.
Flow
Flow
Flow
Horizontal flow limited to 7 bar g (101 psi g)
and saturated steam applications only
Fig. 8
IM-P192-02 MI Issue 214
Note: The 'U' syphon and pressure sensor
must be used for superheated steam
applications.
Rotating the electronics enclosure
The electronics housing can be rotated 270° to
enable sufcient clearance for installation. To
rotate the electronic s housing, loosen the 6 mm
grub scr ew located on the re ar of the electro nics
housing (see Figure 10). The electronics housing
can now be rotated to the required position.
When the el ectronics h ousing has been loc ated
into the co rrect positi on retighten the gr ub screw
to a torque of 1.3 N m (11.5 lbf in).
Flow
Fig. 9
Horizontal flow up to
32 bar g (464 psi g)
for saturated steam applications
and
23 bar g
(333.5 psi g)
for superheated steam applications
Warning: Do not loosen / remove the stem
from the main body of the unit.
Warning: Do not loosen /
remove the stem from the
main body of the unit.
6 mm grub screw
Earth
Fig. 10
IM-P192-02 MI Issue 215
cable
Rotating the electronics front panel
To rotate the electronics front panel loosen the four retaining screws and rotate the front
panel to the orientation, required.
Note: Take care not to damage or strain any of the wiring.
Retaining screwsRetaining screws
ABCD
For applications with
st ea m ab ov e 7 ba r g
and all superheated
applications.
Note:
Fitting the TVA
in this orientation
when the RS485
board is fitted
ensures that the
display can be read
easily.
For vertical flow applications.For saturated steam
applications below
7 bar g.
Upstrea m / downstream p ipework
Th e T VA ow me te r shoul d be inst al le d in pi pe wo rk ma nu fa ctured to BS 16 0 0, ASME B 36.10
Schedule 40 or EN 10216-2 / EN 10216-5 equivalent, which corresponds to the following
pipeline internal diameters:
For dif ferent pipe standards / schedules,
if th e ow meter is bei ng op erate d at th e
extreme of its published maximum
range, and maximum accuracy is
required, downstream spool pieces
manufactured from pipe to the above
standard should be used.
It is impor tant that the internal upstream and downstream diameters of pipe are smooth.
Ideally seamless pipes should be used and there should be no intrusive weld beads on the
int ernal diameter. It is recommende d that slip -on a nges be used to avoid any intr usive weld
beads on the internal diameter of the pipe.
Note: See Figures 11 to 14 for other considerations which need to be noted before
determining the correct installation location.
Nominal diameter Nominal internal diameter
50 mm52 mm
80 mm77 mm
100 mm102 mm
IM-P192-02 MI Issue 216
The TVA flowmeter normally
onl y req uir es a mini mum of 6
pipe diameters upstream and
3 downstre am of clear straig ht
pipe. These dimensions
assume a measurement
from a single 90° bend (see
Figure 11).
6D Minimum
6D Minimum
3D Minimum
3D Minimum
Flow
Fig. 11
If any of the following congurations are present upstream of the TVA owmeter:
Two right angled bends in two planes.
-
Pressure reducing valve.
-
Partly open valve.
-
Then it is recommended that the minimum upstream clear pipework is doub led to 12 diameters
(See Figure 12).
12D Minimum
3D Minimum
Note: The 'U' syphon
and pressure sensor
must be used for
superheated steam
applications.
Note: The 'U' syphon and
Flow
Fig. 12
IM-P192-02 MI Issue 217
pressure sensor must be used for
superheated steam applications.
Avoid installing the TVA owmeter downstream of an actuated valve as rapid cycling of
the valve could give rise to inaccurate results or damage the flowmeter. See Figure 13. In
configurations where there is more than one rapid acting pressure reducing valve close
coupled, the TVA owmeter should be installed with a minimum of 25 upstream and 3
downstream pipe diameters away from the valves.
Safety valves should also be as far away as possible from the flowmeter - at least 25D.
25D
Minimum
3D
Minimum
Flow
Fig. 13
Note: The 'U' syphon and
pressure sensor must be
used for superheated steam
applications.
IM-P192-02 MI Issue 218
To install the TVA owmeter pipeline unit into existing pipework and for aiding possible
flowmeter removal, a spool piece can be fabricated locally to the dimensions given below
(see Figure 14).
SizeDN50DN80DN100
Flow
Fig. 14
Dimension A
180 mm240 mm300 mm
7.1 in9.5 in11. 8 i n
A
Spool piece
Note: The 'U' syphon and
pressure sensor must be
used for superheated steam
applications.
IM-P192-02 MI Issue 219
Location in pipework
Bolt ring gaskets having the same internal diameter of the pipework are recommended.
This will prevent possible inaccuracies being created by the gasket protruding into the pipe.
It is import ant that the TVA ow meter is located centrally in the pipework as any eccentricity
may ca use in ac cur at e re adings. The TVA owmeter has int eg ral cen te ring webs, wh ic h loc ate
on the internal diameter of the pipework (see Figure 15).
Integral centering webs
Integral centering webs
Earth cable
Fig. 15 Integral centering webs
Note: The 'U' syphon and
pressure sensor must
be used for superheated
steam applications.
Fig. 16 Gaskets fitted correctly
IM-P192-02 MI Issue 220
Fig. 17 Gaskets fitted incorrectly
Fig. 18 Gaskets and pipe offline, fitting incorrectly
IM-P192-02 MI Issue 221
3.3 Fitting the pressure sensor for superheated steam applications
To operate the TVA flowmeter on superheated steam the pressure sensor must be installed
upstream of the actual flowmeter. This is to give full density compensation and allow the
amount of superheat to be calculated.
A ¼" NPS M boss wi ll be re qu ired on the pip e fo r th e conne ct ion of the 'U ' sy ph on and pres su re
sensor. It should be sited as close to the upstream flange as practicably possible (see Figure
19, and take into account dimension 'X' in Section 2.8).
Note: The TVA must only be used for superheated steam application, when the pipe is in a
horizontal plane.
* Sensor cable
* 'U' syphon assembly
* Pressure sensor
Earth
cable
¼"
NPSM
boss
Earth
cable
TVA owmeter body
F
l
o
w
Flowmeter stem
* Items required for superheat operation
Fig. 19 TVA flowmeter
Electronics housing
IM-P192-02 MI Issue 222
3.4 Electrical installation
The TVA owmeter is a loop powered device. Thi s Sec tion describes loop wiring and shows
typical conductor terminations (The EIA 232C (RS 232) wiring is discussed in Section 4.11,
page 41). It also considers the effect of connecting additional equipment (e.g. recorder, loop
powered display) to the loop, plus the pressure sensor connection.
Wiring the TVA flowmeter
The wiring terminals can be accessed by removing the end cap of the enclosure. A typical
loop wiring diagram is shown in Figure 20.
If an M75 0 display unit is purchased from Spir ax Sarco for use with the TVA ow meter, the
M750 must be congured to the ow of the T VA owmeter @ 20 mA. If the T VA owmeter
4 - 20 mA output is rescaled (see Section 4.6.1), it is important that the 20 mA input valve
on the M750 is also rescaled.
Recommendations:
Ensure the provided EMC gland is used to connect the wiring to the electronics housing.
-
When using the RS232/485 port, PVC covered steel conduit should be used.
-
All cables that run through conduit should be screened. The screens must be earthed at
-
the far end of the installation and not at the owmeter.
If using the loop and switch pulse ports:
-
- Either combine both por t outputs to one screened four core cable which is terminated
with an EMC gland.
-or, use exible conduit as described above.
Notes:
The flowmeter must be earthed. The TVA is supplied with a 350 mm earthing lead
attached to a 4 mm threaded hole at the rear of the enclosure close to the 20 mm
conduit holes.
Remove the silica gel from the enclosure after commissioning.
When connecting the superheat kit to the TVA, the cable from the pressure sensor
must be threaded through the 20 mm conduit hole on the rear of the electronics housing.
Plug the connector on to the pin header (as indicted in Figure 20) making sure that the
blanking pin is aligned correctly with the missing pin on the plug.
Refit the end cap ensuring that no wires are crushed and tighten the cable gland
to 13 N m (9.58 lbf ft) to ensure an IP65 seal.
IM-P192-02 MI Issue 223
EIA 232 (RS 232)
Communication port
(RJ11 socket)
Superheat pressure sensor
pin header connection
M750 display unit
with 4-20 mA active
input (supplying
current loop)
1
2
N
-
3
L
4
+
5
Remote NPN input
(maximum 28 V)
Power
R
0 Volts
PulseLoop
+-+-
Or R 10 k W
Power
+
R
0 Volts
Remote PNP input
(maximum 28 V)
Fig. 20 TVA with EIA 232 (RS232) Communications and 4-20mA wiring diagram.
9 - 28 Vdc
-
Loop powered
4-20 mA
display unit or
chart recorder
230 V
50 Hz
Fuse 1A
IM-P192-02 MI Issue 224
Note: Do not reconnect loop
power supply to these terminals
when RS485 board fitted.
-
Power supply 24 Vdc (19 - 28v) 50 mA maximum
+
GND data
B - data
A + data
Fig. 21 TVA with EIA 485 (RS485) Communications wiring diagram
IM-P192-02 MI Issue 225
Power supply requirements
A no minal 24 Vdc is nee de d to power th e flo wm et er. However, th e T VA owme te r wi ll oper at e
correctly as long as the power supply is in the range shown in Figure 20. A single, stand-
al one, supply may be capab le of powerin g se ve ra l trans mi tters . It can be mou nt ed in a con trol
room or in the fie ld, but cannot be on the same loop. Follow the power supply manuacturer’s
recommendations with regard to mounting and environmental considerations.
The graph (Figure 22) shows the range of power supply voltages and loop resistances over
which the TVA owmeter is cap able of operati ng. The loop resistan ce inc lu des all the wiring.
TVA owmeter
operating range
V = 0.022R + 6
9 V V 28 V
R (ohms)
Fig. 22
V (volts)
Cable length
Generally the maximum cable length between the TVA owmeter and the power supply is
300 m (984 ft).
However the actual cable length is governed by the number of network devices, the total
resistance of the network and the cable capacitance.
Suggested cable type: for both loop and pulse should be shielded twisted pairs, each core,
seven stranded wire with cross sectional area of 0.5 mm².
EMC cable glands suitable for M20 x 1.5 to EN 50262 / IP68 are recommended.
The cable gland / body torque setting is 13 N m (9.58 lbf ft).
The gland nut torque setting (with cable fitted) is 12 N m (8.85 lbf ft).
IM-P192-02 MI Issue 226
4. Commissioning
total
power
After all mechanical and electrical work
has been completed, the following
commissioning instructions should be
followed.
The TVA flowmeter should
be commissioned with the
flow through the unit
isolated.
Note: The TVA owmeter is
factory set to display data in
metric units. To commission
the TVA to diplay imperial
units see Section 4.4.2.
Mounting screws
Fig. 23 TVA flowmeter display unit
All commissioning is carried out through the display unit installed behind the front end
cap of the T VA flowmeter enclosure. The display unit consists of a small LCD display and
a 5 button key pad.
As all the co mmissio ni ng sett in gs are stor ed in a non -v ol at ile mem or y, it is poss ib le to con ne ct
a 9 V PP3 battery to the TVA owmeter's 4 - 20 mA loop power supply and commission the
unit uninstalled. However, if using a T VA for a superheat application (with pressure sensor),
the sensor must be connected before powering up the flowmeter. Otherwise the pressure
channel calibration will be affected. The TVA owmeter should still be zeroed in-line (see
Section 4.5.3) and its operation checked. An M750 display unit can be used to provide a
remote display function if required, utilising the linear output.
Rotating the display
The display can be rotated through 180° to enable ease of commissioning. To rotate the
display disconnect the power supply, remove the mounting screws on the display unit,
carefully remove the display unit and rotate. Carefully replace the display unit and replace
mounting screws. Do not force the display unit into position. Reconnect the power supply.
Note 1 - Electrostatic discharge (ESD) procedures should be followed while rotating the
display.
Note 2 - DO NOT remove the 10 way connector from the display.
LCD
display
5 button
keypad
4.1 Run mode
Normally, the TVA owmeter will operate in the run mode, displaying the total flow, flow,
power, pressure or temperature of the fluid passing through the pipeline.
After initial power up, the TVA owmeter will automatically enter the run mode and all
commissioning menus can be accessed from this mode. (See Section 4.2, Commissioning
mode, for details on how to commission). In the run mode the fluid data is displayed on
several screens which can be accessed by pressing the up or down keys.
The display shows a numeric value and an arrow
indicating the reading type, i.e. total flow, flow, power,
pressure or temperature. All units (except °C) are
implied with imperial or metric units being indicated
by another arrow. The value of total flow is shown in
two parts. The first five digits of the total flow will be
displayed and after 10 seconds the following five
digits will be displayed. To access the first five digits
of total flow again it will be necessary to scroll up or
down and return to the total flow display.
IM-P192-02 MI Issue 227
Arrow
temp
flow
imp
pres
Fig. 24
total
power
total
power
4.1.1 Run mode data sequence
Total High
kg or lb
Total Low
kg or lb
Flow
POWER
Pressure
Temp. °C
Power kW or kBtu/h.
Pressure bar g or psi g, depending if
metric or imperial units are selected.
Temperature °C or ° F.
The following chart indicates the run mode data display sequence.
Depending on the configuration, the flow units will be:
UnitsSteam
Metrickg, kg / h, kW, bar g, °C
Imperiallb, lb / h, kBtu / h, psi g, °F
The TVA owmeter is fac tory set to display steam data in metri c units and pressing the up or
down keys will scroll through the following data.
pres
pres
flow
flow
Total flow
temp
temp
total
imp
imp
flow
power
pres
total
flow
power
pres
Flow
Temperature
Fig. 25
Power
temp
total
total
temp
temp
imp
flow
flow
imp
imp
power
power
pres
pres
temp
total
temp
imp
flow
imp
power
pres
Pressure
IM-P192-02 MI Issue 228
4.1.2 Error display messages
Any errors that occur will be displayed in the run mode. The errors will alternate with the
normal run mode display and will be prioritised. The errors will be latched and can only be
cancelled by pressing the 'OK' button. Once the error message has been cancelled the display
will show the next (if any) error.
Any continuous error will reinstate itself 2 seconds after it has been cancelled, and will be
indicated by a flashing exclamation mark (!).
Certain errors will also cause the 4-20 mA alarm signal to be initiated.
The error messages are displayed over two screens and are:
= Power interrupted.
= No signal from sensor.
(This can also activate the 4-20 mA alarm).
= Signal from sensor constant.
(This can also activate the 4-20 mA alarm).
= Flow above the maximum.
= Line conditions have changed from
superheat to saturation (only when pressure
POWER
OUt
NO
SIGNL
SENSR
CONSt
HIGH
FLOW
SUb
SAt
sensor enabled).
IM-P192-02 MI Issue 229
4.2 Commissioning mode
The commissioning mode is used to zero the flowmeter, re-range, enable the pressure sensor
(for superheat applications), set and test the outputs and change the pass code.
All data entr y is performed via a menu and sub menu configuration with the key pad but tons
used for navigation, i.e. to go deeper into the menu the right hand key is pressed, to scroll
up and down the menu the up and down keys are pressed and to exit from a sub-menu the
le ft key is pre ss ed. Any dat a is entered us in g the OK bu tton. The previous ly ent er ed sele ct ion
will flash. Af ter a period of five minutes without any keys being pressed the TVA owmeter
will automatically default to the run mode.
For a full commissioning f low chart see Section 4.3.
To enter the commissioning mode press and hold down the 'OK' key for 3 seconds. The
display then shows:
Followed by:
The leading digit will flash indicating that this is the position of the cursor.
The default factory set pass code is 7452. (This can be changed from within the commissioning
mode). The pass code can be entered by using the up and down keys to increment the flashing
value and the left and right keys to move the cursor. Pressing 'OK' will enter the pass code.
If an incorrect pass code is used the display will automatically return to the run mode.
After the correct pass code is entered the display shows:
ENtER
PASS
7452
bASIC
dAtA
IM-P192-02 MI Issue 230
To exit from the commissioning mode at any stage, continually pressing the left key will return
to the run mode.
Pressing the up and down buttons scrolls through the various first level menus.
Pressing the right arrow button enters a particular sub-menu.
ENtER
PASS
8888
bASIC
dAtA
MEtER
OUt
PUts
PRES
SENSR
tESt
ALARM
SWVER
SEt
PASS
IM-P192-02 MI Issue 231
4.3 TVA flowmeter commissioning flow chart
Software
version number
(test
display)
Power on sequence; turn
on all segments, then
show the software version
no.
VER x.x
Normal run mode
display sequence
Total
high
Total
low
ENtER
PASS
kg or lb
(kWh or kBtu)
Default = 8888
but user settable.
8888
Conguration
sub-menus
bASIC
dAtA
Flow
Power
Pressure
Temp. °C
Error Messages
These alternate with the normal run mode display.
They will be prioritised and will be latched when
they occur.
Pressing the 'OK' button will cancel the displayed
alarm and allow the next one to be viewed.
A continuous alarm will re-occur on the display
2 seconds after it has been cancelled.
Power
from
sensor
sensor
Flow
above
POWER
OUt
NO
SIGNL
SENSR
CONST
HIGH
FLOW
SUb
SAt
The 4- 20 mA
alarm can also
be activated
The 4- 20 mA
alarm can also
be activated
Shows when
ow exceeds
maximum
Line temperature
drops below
steam saturation
temperature
interrupted
No signal
Signal from
constant
maximum
Temp below
saturation
kg /h or lb / h
kW or kBtu /h
bARG or PSIG, depending if metric or
imperial units are selected.
°C or °F
HIGH
LOW
OFF
ON
OFF
ON
OFF
xxxx
O/P
ALARM
POWER
ALARM
CONSt
ALARM
SEt
PASS
SWVERxxxx
ALARM
MEtER
OUt
PUtS
PRES
SENSR
dELAyXX
yES
NO
SAt
ALARM
tESt
IM-P192-02 MI Issue 232
dRy
xxx%
CLEAR tOtAL
ZERO MEtER
4- 20 mA
PULSE
COMMSbAUD
yES
NO
dIR
S/N
SORCE
NUM /
PULSE
PULSE
WIDTH
xxxxx
UNItS
tOtAL
AtMOS
PRES
tOtAL
ENRGy
xxxxx
in kg or lbs,
MJ or kBtu.
xxxmS
Must not
exceed 4 pulses
per second.
1200
MASS
ENERGy
xxx.xx
HORIZdOWN
SORCE
SEt4 mA
SEt20 mA
CHECK
4 mA
CHECK
20 mA
MEt
IMP
UP
FLOW
POWER
xxxxx
in kg /h or lb /h,
kW or kBtu /h.
xxxxx
OP = 4 mA
Connect a DVM
and use the up
and down keys to
set 4 or 20 mA.
OP = 20 mA
yES
NO
tyPE
0CAL
25CAL
SH MARGN
PRES
ALARM
ASCII
MOdbuS
Press OK to select
XXXXX
XXXXX
yESNOLIMIt
ON
OFF
9600
Add
XXX
ALARM
dELAyXXX
OFF
ON
XXX
dISP
4-20 mA
OUt
PULSE
OUt
CANCL
Display
test
xxx.xxmA
ON
OFF
IM-P192-02 MI Issue 233
4.4 bASIC DAtA Sub menu
bASIC
dAtA
dRy
UNItS
tOtAL
AtMOS
PRES
xxx%
xxx.xx
MASS
ENERGy
MEt
IMP
4.4.1 dRy
Pressing the right key will display the dryness fraction. This is the dryness fraction of the
saturated steam being measured. This can then be edited to suit the application. Press the
'OK' button to confirm the selection.
After the dryness fraction is entered the display will automatically step to the next sub menu
and show 'UNItS'
4.4.2 UNItS
The units displayed and transmitted can be selected between metric (MEt), and
imperial (IMP).
A summary of the units is detailed in the Table below.
UnitsSteam
Metrickg, kg / h, kW, bar g, °C
Imperiallb, lb / h, kBtu / h, psi g, °F
Select either 'MEt' or 'IMP' and press the 'OK' button to confirm.
4.4.3 CLEAR tOtAL
This function is used to clear the total by pressing and holding the 'OK' key for 3 seconds.
Note: The total is backed-up every 8 minutes in the TVA flowmeter's non-volatile memor y.
If power is lost the TVA owmeter could lose up to 8 minutes worth of totalised steam.
4.4.4 AtMOS PRES
This value compensates the flowrates for atmospheric pressure. It should be used if a high
degree of accuracy is required or when the T VA owmeter is installed high above sea level.
Note: Values up to two decimal places can be entered.
If metric units are selected pressure units are bar absolute, for imperial units psi absolute.
IM-P192-02 MI Issue 234
4.5 MEtER Sub-menu
MEtER
This sub-menu contains information about
the flowmeter and is used to zero the
flowmeter and clear the total.
dIR
S/N
ZErO MEtER
CLEAR tOtAL
xxxxx
HORIZ
DOWN
UP
4.5.1 dIR
dIR is the orientation that the TVA owmeter is installed in. The TVA owmeter can be installed
with horizontal flow up to a pressure of 32 bar g (464 psi g). For installations that require
vertical flow either up or down the maximum pressure must not exceed 7 bar g (101 psi g).
By selecting down or up the effect of gravity on the cone is taken into account.
Note: Upon entering the dIR sub-menu, HORIZ is always shown rst. The actual direction
selected is the one which is ashing.
4.5.2 S/N
This is the factory set serial number of the TVA owmeter and is displayed by pressing the
ri ght key.
4.5.3 ZErO MEtER
Th is functi on is used to ze ro the TVA owm et er manually to co mp ensate for any elec tronic dr if t .
The procedure for zeroing the flowmeter is as follows:
-Isolate the pipeline where the flowmeter is installed and ensure that there is no flow. The
line temperatures should be above 5 ° C (41 °F) and below 30 °C (86 °F).
-Press and hold the 'OK' button for three seconds.
On completion the display will step back to S/N.
If 'ZErO ErrOr' is displayed, check to ensure that the line is isolated with no flow.
If 'tEMP ErrOr' is displayed the line temperature is below 5°C (41 °F). Allow the temperature
to move above 5 °C (41 °F) and re-zero. Note: The flowmeter should ideally be zeroed
annually after 12 months service.
4.5.4 CLEAR tOtAL
This function is used to clear the total by pressing and holding the OK key for 3 seconds.
Note: The total is backed-up every 8 minutes in the TVA owmeter's non-volatile memory.
If power is lost the TVA owmeter could lose up to 8 minutes worth of totalised steam.
IM-P192-02 MI Issue 235
4.6 OutPutS Sub-menu
This sub-menu allows both the 4-20 mA and pulsed
outputs of the flowmeter to be configured.
4.6.1 4-20 mA Output sub-menu
OUt
PUtS
4-20mA
PULSE
OUt
PUtS
The 4-20 mA sub-menu allows
re-ranging and re-calibrating of
the 4-20 mA output.
4-20 mAFLOW
SORCE
SEt4 mA
SEt20 mA
CHECK
4 mA
CHECK
20 mA
POWER
XXXX
XXXX
OP = 4mA
OP = 20 mA
4.6.2 SORCE
This changes the source data for the 4-20 mA between flow and power.
4.6.3 SEt4 mA
This sets the value for the flowrate or power, which is equivalent to 4 mA. The minimum
value that can be set as 4 mA is 0 and the maximum is the 20 mA equivalent value less one.
4.6.4 SEt20 mA
This sets the value for the flowrate or power, which is equivalent to 20 mA. The minimum
value that can be set as 20 mA is the 4 mA equivalent value plus one and the maximum is
the meters rated maximum at 32 bar g. The 20 mA value must always be a minimum of one
greater than the 4 mA value.
4.6.5 CHECK 4 mA
This allows the 4 mA value to be re-calibrated. A digital volt meter / multimeter should be
connected in series with the 4-20 mA output. Pressing the right arrow button will display OP
= 4 mA and the TVA owmeter will output a steady 4 mA. If the multimeter does not read 4
mA the up and down arrow buttons can be pressed to alter this current until 4 mA exactly is
indicated. Pressing the 'OK' button confirms the setting.
4.6.6 CHECK 20 mA
This allows the 20 mA value to be re-calibrated. A digital volt meter/multimeter should be
connected in series with the 4-20 mA output. Pressing the right arrow button will display OP
= 20 mA and the TVA owmeter will output a steady 20 mA. If the multimeter does not read
20 mA the up and down arrow buttons can be pressed to alter this current until 20 mA exactly
is indicated. Pressing the 'OK' button confirms the setting.
IM-P192-02 MI Issue 236
4.6.7 Pulse Output
This sub-menu allows the pulsed output to be configured.
PULSE
NO
4.6.8 PULSE
This selects whether the pulsed output is to be used or
disabled.
SORCEyES
NUM/
PULSE
PULSE
WIDTH
tOtAL
ENRGy
xxxxx
xxxmS
4.6.9 SORCE
This selects the source data for the pulsed output.
The source data can be either unit mass per pulse (tOtAL) or unit energy per pulse (ENRGy).
4.6.10 NUM / PULSE
This allows the total mass, or energy, which is equivalent to one pulse to be configured.
Units are dependent on the UNIt setting. Metric units will be kg for total or MJ for energy,
imperial units will be lb for total or kBtu for energy.
4.6.11 PULSE WIDTH
This allows the width of the pulse to be set. The width can be set in 0.01 second increments
from 0.02 seconds to a maximum of 0.2 seconds.
4.6 .12 C OMMS
This allows the connection to other communications protocols.
COMMSbAUD
1200
tyPE
ASCII
MOdbuS
Press OK to select
9600
Add
xxx
4.6.13 bAUD
This allows the communication speed to be set to either 1200 or 9 600. This must match the
rate set within the device it is communicating to.
4.6 .14 t y PE
This gives the choice to select either ASCII or Modbus protocols.
4.6 .15 A dd
If you have selected Modbus communications you must add an address. This is a three digit
number between 001 - 255. Again this must match the address that the device that you are
communcating to is set to.
IM-P192-02 MI Issue 237
4.7 PRES SENSR sub-menu
PRES
SENSR
yES
NO
0CAL
25CAL
SH MARGN
PRES
ALARM
XXXXX
XXXXX
ON
OFF
yESNOLIMIt
ALARM
dELAyXXX
XXX
OFF
ON
Selecting 'YES' at the PRES SENSR menu will enable the pressure sensor option.
4.7.1 0 C AL
When the pressure sensor has been enabled, the 0CAL menu will be displayed. Pressing the
right arrow key (>) will display the 0CAL bits values.
The calibration certificate supplied with every pressure sensor kit lists the 0CAL and
25CAL bits values that are required to be entered.
4.7. 2 25 C A L
Pr es sing th e do wn ar ro w key (v) will displ ay the 25CA L bi ts values. Th e calib ra ti on ce rti fic at e
supplied with every pressure sensor kit lists the 25CAL bits values that are required to be
entered into this menu.
When the bits values for the 25CAL have been entered press the OK but ton to confirm. This
will automatically display the SH MARGN menu.
4.7.3 SH MARGN
The SH MARG N menu enabl es the conf iguration of the super heat alarm, the superheat limit
(in degrees C) and delay before the alarm is triggered.
LIMItNumber of degrees of superheat have dropped before alarm is triggered.
ALARMCan be set to ON or OFF.
dELAyThe alarm in seconds before the alarm is triggered.
4.7.4 PRES ALARM
In the event the alarm is triggered 'LOWS-HT' will be displayed. The PRES ALARM is
activated in the event that the pressure has exceeded 30 bar g. In this event 'OVER PRES'
will be displayed.
4.7. 5 WAIT
On exiting the 'PRES SENSR' menu the wait command will be displayed. At this point the
software is zeroing the pressure channel. This will return to normal after approximately
5 seconds.
IM-P192-02 MI Issue 238
4.8 tESt sub-menu
The tESt sub-menu allows access to the TVA owmeter's diagnostic tools. From here the
display, 4-20 mA and pulse outputs can be tested.
tEStdISP
4-20mA
OUt
PULSE
OUt
CANCL
xxx.xxmA
ON
OFF
4.8.1 dISP
This allows the display to be tested. Pressing the right button will cause all the segments on
the display to be turned on. Pressing the left button cancels the test and steps to the next
stage.
4.8.2 4-20 mA Out
Th is allows the 4-20 mA ou tput to be te st ed . By edit in g the va lu e and pre ss ing the 'OK' but ton
the output can be set to the selected output. This current will continue to be transmitted for
five minutes unless the cancel option is chosen.
4.8.3 PULSE OUt
This allows the pulsed output to be tested. By selecting 'ON' or 'OFF' the desired test state
of the pulsed output can be selected. Once the 'OK' button is pressed the pulsed output will
remain in the selected state for five minutes or until the cancel option is chosen.
4.8.4 CANCEL
This al lows th e 4-20 mA output and pulsed output test si gnal se lecte d above to be cancel led
before the five minutes duration has expired.
IM-P192-02 MI Issue 239
4.9 ALARM sub-menu
Th is sub- menu gi ve s ac ces s to sett in g the act io n that is req ui re d on th e 4-20 mA output whe n
an error is det ected by th e T VA owme te r el ect ro ni cs. It al so gives ac cess to the power al ar m
function.
dELAyXX
4.9.1 O / P AL ARM
If the self-diagnostic electronics determine that the sensor output has been
HIGH
LOW
constant for a period of time, or is not giving out a signal, it will set the 4-20 mA
output to 22 mA.
If the self-diagnostic electronics determine that the sensor output has been
constant for a period of time, or is not giving out a signal, it will set the 4-20 mA
output to 3.8 mA.
HIGH
LOW
OFF
ON
OFF
yES
NO
O/P
ALARM
POWER
ALARM
CONSt
ALARM
SAt
ALARM
ALARM
ON
OFF
OFF
This disables the 4-20 mA alarm function.
4.9.2 POWER ALARM
OFF
ON
This disables the power alarm function.
This enables the power alarm function.
IM-P192-02 MI Issue 240
4.9.3 CONSt ALARM
This allows the constant f low alarm to be turned off.
The constant alarm is switched to on by the default factory setting. It detects if the flow has
been constant for long periods when at pressure, which may indicate a stuck cone due to
debris. If the system that the T VA is fitted to, has long periods where there is zero flow, but
the line is kept at a constant pressure, it is advisable to turn the alarm off to avoid unwanted
alarm messages.
ON
OFF
dELAy
This enables the saturated steam alarm.
This disables the saturated steam alarm.
This enables the time duration before alarm is displayed.
4.9.4 SAt ALARM
yES
NO
dELAy
This allows the Sub Saturation Alarm to be enabled or disabled.
The Sub Saturation alarm is switched off by default. If set it will alarm if the steam temperature
drops 2 °C below saturation temperature.
4.10 S W VER
This allows the soft ware version to be viewed.
4.11 SEt PASS
This allows the default pass code to be changed
to a user defined value.
It is impor tant that if the default pass code is
ch anged tha t th e ne w va lu e is not ed and kep t safe.
The new pass code can be recorded on the Table
in Section 9, page 50.
Enables the Sub Saturation Alarm.
Disables the Sub Saturation Alarm.
This sets the time duration before alarm is displayed. Can be zero.
SWVER
SEt
PASS
xxxx
xxxx
IM-P192-02 MI Issue 241
4.12 TVA communications
4.12.1 TVA UART set-up
The TVA flowmeter has an EIA 232C compatible communications link and supports two
protocols: a simple Line Feed [LF] terminated ASCII protocol and a subset of Modbus/RTU.
This enables users to easily interrogate the TVA flowmeter for steam data using either a dumb
terminal or a P.C. loaded with a simple terminal emulation program or a standard Modbus
Master / Client application. The connection length is limited to 15 metres and must be in the
same building / area as the TVA flowmeter.
The TVA’s communication set up should be as follows:
TVA ASCII set-upTVA Modbus set-up
Baud rate
Data bits
Stop bits
Parity
Echo
Response time:
The TVA will start responding within 500 msec. The actual time to fully receive a response
from the T VA is baud rate dependent, for example a Modbus poll of 12 registers @1200 baud
rate could take ((5 + 24) bytes x ~10 ms / byte) + 500 ms ≈ 800 ms to complete.
The polling frequency can be faster if the polling algorithm is set to poll immediately after
receiving a valid response to a poll.
4.12.2 Using the EIA 232C communications
It is assumed that:
The elec trical wiring f or the EIA 232C commu nications has been c arried out in ac cordance
-
with the EIA 232C standard. Please note the TVA EIA 232C connection requires a
c o nnector RJ11 li n k e d to a 9 wa y D-type ada p t o r. Fig ur e 2 5 i l l u s t r a tes the T VA owm et e r ' s
RJ11 socket from the front.
1200 or 9600
7
one
none
off
Baud rate1200 or 9600
Data bits8
Stop bitsone
Paritynone
Echooff
The table below lists the RJ11 socket's pin connections.
The signals are named from the PC (or data terminal) end.
RJ11 pin9-way D-typeSignal
1Not used
24DTR
35GND
42RX
53TX
68CTS
6 5 4 3 2 1
Pin numbers
Fig. 26 RJ11 socket
IM-P192-02 MI Issue 242
The commu n i c a t i ons prot o c o l ha s been set up on th e co m m u nicati n g de v i c e a s de s c r i b ed
-
earlier in this Section. The following is a Table of operating codes in ASCII characters:-
ASCII communications
Please note that all the following commands are case sensitive…
User transmits TVA responds (metric)TVA responds (imperial)
AB[LF]Pressure in bar g [LF]Pressure in psi g
AC[LF]Line Temperature in °C [LF]Line temperature in °F
AH[LF]Energy total in kWh [LF]Energy total in kBtu
AP[LF]Power in kW [LF]Power in kBtu / h
AR[LF]Flow rate in kg / h [LF]Flow rate in lb / h
AT[ LF]Total in kg [LF]Total in lb
4.12.3 Using RS485 Communications
The TVA is available with RS485 communications. This is achieved by converting the
communication from RS232 by an additional PCB. The PCB is fitted at the factor y when the
TVA is ordered with RS485 communications.
However, the RS485 communications board is available if ordered with a replacement
electronics front panel.
Note: RS232/4-20mA outputs are not available if the RS485 board is fitted.
The TVA is a RS485 slave device and must be powered by connecting 24VDC to terminals
4 and 5.
The data terminals are 1-3 and all must be connected for the communication to work correctly.
TerminalSignal
1Data +
2Data -
3Data GND
4Power +
5Power -
4.13
After installation or maintenance ensure that the system is fully functioning.
Carry out tests on any alarms or protective devices.
IM-P192-02 MI Issue 243
4.14 Modbus communications
The TVA flowmeter has Modbus communications, in addition to the ASCII Modbus comms
that are avai la ble th rough the TVA RS232 port . An RS48 5 to RS2 32 converter is re quired, or
alternatively, an Ethernet to RS232 converter, both of which are widely available.
Modbus comms protocol
Format: Request frame
Address1 by te
Function code1 byte
Start address2 bytes
Quantity of registers2 bytes
Error check (CRC)2 bytes
Tot al8 bytes
Format: Response frame (normal)
Address1 by te
Function code1 byte
Byte count1 byte
Register data2 x Quantity of registers, MSB first, low register address first
Error check (CRC)2 bytes
Tot al5+ (2 x Quantity of registers) bytes
Format: Response frame (error)
Address1 by te
Error code1 byte (error code = function code plus 0x80)
Exception code1 byte (01 or 02 see below)
Error check (CRC)2 bytes
Tot al5 bytes
Note: Only ‘Read holding registers’ (function code ‘03’) is currently supported
4.14.1 ModBus request frame structure example.
Byte 1Byte 2Byte 3Byte 4Byte 5Byte 6Byte 7Byte 8
Device
address
The above frame will poll all Modbus registers from Total low 16-bits up to and including
Software Version.
Function
code
x
(3)
Register
start
address
(MSB)
(0)
Register
start
address
(LS B)
(0)
Register
quantity
(MSB)
(0)
Register
quantity
(LS B)
(12)
IM-P192-02 MI Issue 244
CRC
(LS B)
x
CRC
(MSB)
x
Register
number
400010Total low 16 bitsx1Kg
400021Total high 16 bitsx1Kg
400032Flow x1Kg/h
400043Pressurex10 0BarG
400054Temperature x10 °C
400065
400076Powerx1kW
400087
400098
400109Alarm status-(bit-fields) Look table below
4001110SxS device ID--T VA = 0
4001211Software version--
4002120Total low 16 bitsx1Lbs
4002221Total high 16 bitsx1Lbs
4002322Flow x1Lbs/h
4002423Pressurex100PSIg
4002524Temperaturex10 °F
4002625
4002726Powerx1KBTU/h
4002827
4002928
Note Modbus protocol requires that Modbus addresses star t at offset 0, not 1. Register
addresses start from 1 in description but 0 in binar y. Most parameters are 16 bits and few
pa ra meters ar e 32 bits. Mo db us regi st er s are 16 bits, i.e. 1 dev ic e pa rameter nee ds 1x an d 2x
Modbus register(s) respectively. As a general note on Modbus, register types and reference
register number ranges are implemented as follows:
0x = Coil = 00001 - 09999
1x = Discrete input = 10001 - 19999
3x = Input register = 30001 - 39999
4x = Holding register = 40001 - 49999
Modbus
address
ParameterReceived
Water equivalent
flowrate
Energy low
16 bits
Energy high
16 bits
Water equivalent
flowrate
Energy low
16 bits
Energy high
16 bits
data
scale
x10L/hour
x1kWh
x1kWh
x10Lbs/hour
x1kBTU
x1kBTU
UnitsNotes
M ultiply by the invers e 'Rece iv ed Dat a
*
Scale' to extract data in relevant units,
i.e. divide polled 'Temperature' by 10
to get the value in °C… Tip: use real
(float) type to retain 2-decimal-point
accuracy.
Total = (Total high x
65536) + Total low
Energy = (Energy high x
65536) + Energy low
200 is sw ver 2.00, 201
is sw ver 2.01 etc
Total = (Total high x
65536) + Total low
Energy = (Energy high x
65536) + Energy low
*
*
*
*
IM-P192-02 MI Issue 245
4.14.2 Alarm status register bit-fields:
Bit 1Bit 0StateAlarm code
00Superheat0x0000
01Not applicableNot applicable
10Saturated0x0002
11Sub-saturated0x0003
BitSet (1)Cleared (0)
Bit 2 (0x0004)
Bit 3 (0x0008)Superheat margin activeSuperheat margin idle
Bit 4 (0x0010)Hi flow alarm is activeHi flow alarm is idle
Bit 5 (0x0020)Sensor constant alarm is activeSensor constant alarm is idle
Bit 6 (0x0040)
Bit 7 (0x0080)
Bit 8 (0x0100)Hi flow alarm has latched-
Bit 9 (0x0200)Sensor constant alarm has latched-
Bit 10 (0x0400)
Bit 11 (0x0800)Power failed alarm has latchednothing
Bit 12 (0x1000)Low superheat (Low S- HT) alarm-
Bit 13 (0x2000)Over pressure alarm (OVEr PRES)-
Bit 14 (0x4000)--
Bit 15 (0x8000)--
A maximum of 12 Modbus registers can be polled together at the same frame. It has to be
noted that only a poll with a valid start address and quantity that falls within the supported
register range will produce a normal frame response. If you ask for a frame with start address
outside this range or a frame that the start address + quantity falls outside this range, the
TVA will reply with an 'illegal data address' error message. If the function code is incorrect,
it will reply with an 'illegal function' error message.
If a message is received with the wrong CRC, it will be ignored. The TVA response time is
not instant (look below) so wait for it to reply before asking for more data, other wise it will
ignore new requests.
Pressure alarm is active
(too high or too low)
No signal from sensor alarm is
active
Power failed (has been turned off
and on) alarm is active
No signal from sensor alarm is
latched
Pressure alarm is idle
No signal from sensor alarm is
idle
Power failed alarm is idle
-
IM-P192-02 MI Issue 246
Important note: T he TVA is a lo op powere d de vi ce. It requires the CTS and DTR ter minal s
to be wired and enab led to power the commu nicat ions interface. Failure to do so wil l prevent
the communications working.
4.14.3 Response time:
The TVA will start responding within 500 msec. The actual time to fully receive a response
from the T VA is baud rate dependent, for example a Modbus poll of 12 registers @1200 baud
rate could take ((5 + 24) bytes x ~10 ms / byte) + 500 ms ≈ 800 ms to complete.
The polling frequency can be faster if the polling algorithm is set to poll immediately af ter
receiving a valid response to a poll.
5. Maintenance
The T VA owmeter should be zeroed using the zero meter sub-menu at least once a year.
This will remove any electronic long term drift that may occur. Frequency of re-calibration
depends upon the service conditions experienced by the meter and the application.
Re-calibration frequency can be typically between 2 and 5 years.
5.1 Replacement of the TVA flowmeter display electronics
To replace the electronics:
Disconnect the power supply.
-
Remove the front housing.
-
Remove the mounting screws on the display unit and carefully remove the electronics.
-
Carefully unplug the ribbon cable.
-
Reconnect the ribbon cable to the new electronics and carefully replace.
-
Replace the mounting screws and reconnect the power supply.
-
Note: Electrostatic discharge (ESD) procedures should be followed while installing the new
electronics.
Do not force the electronics/display unit into position.
IM-P192-02 MI Issue 247
6. Spare parts
1. Spare electronics for the T VA owmeter are available from Spirax Sarco and consist of:
TVA owmeter replacement display and electronics with front housing. State if
-
RS485 board is fitted.
It is impor t an t th at the se rial numb er of the TVA owmeter is gi ve n at the ti me of ord er ing.
Example: 1 of f Spirax Sarc o display and el ectro nics panel for a DN100 T VA owm eter
having the following Serial number D_ ____ _ . This can be found on the product label
on the stem.
2. Superheated steam conversion kit. This comprises of a new electronics front panel,
co mplete wi th pressu re sen sor and syp ho n. Please not e: the ser ial num be r of the exis ti ng
TVA must be provided at the time of order placement.
IM-P192-02 MI Issue 248
7. Fault finding
Many faults which occur on commissioning are found to be due to incorrect wiring or setting up,
therefore it is recommended that a thorough check is carried out should there be a problem.
The TVA owmeter display has in-built diagnostic features and will indicate a number of
errors on the display and via the 4-20 mA output.
The errors will alternate with the normal run mode display and will be shown according to
priority. The errors will be latched and can only be cancelled by pressing the 'OK' button.
Once the error message has been cancelled the display will show the next (if any) error.
Any continuous error will re-instate itself 2 seconds after it has been cancelled, and will be
indicated by a flashing exclamation mark (!).
SymptomPossible causeAction
Display is blankdc voltage is not within
Display shows:
NO SIGNL
Display shows:
POWER Out
Display shows:
SENSR CONST
the range of 9-28 Vdc.
Supply connected with
reverse polarity.
Electronics faulty.
Insufficient supply
voltage.
Current loop resistance
is greater than Rmax.
Electronics faulty.
Power supply
interrupted.
Cone jammed.
Electronics Faulty.
Check power supply/current
connections. See Section 3.3.
Change polarity.
Refer to: Spirax-Sarco Limited
Check supply voltage is between 9 and
28 Vdc.
Check current loop resistance and
reduce if necessary.
Check current output electronics (refer
to Sections 4.6, 4.7 and 4.8).
Refer to: Spirax-Sarco Limited
Ensure power supply is secure and
cancel error using the OK key.
Totals transmitted may not be valid.
Remove unit from pipeline and check
cone movement.
Check current output electronics (refer
to Sections 4.6, 4.7 and 4.8).
Refer to: Spirax-Sarco Limited
Display shows:
HIGH FLOW
IM-P192-02 MI Issue 249
Meter undersized.Check sizing and replace
if necessary.
SymptomPossible causeAction
Constant 3.8 mAError signal set to Low.Check display for errors
Constant 22 mAError signal set to High. Check display for errors
Flow indicated
responds to
changes in actual
flow but value
indicated does
not correspond to
actual flowrate
Flowmeter not properly
centred in the pipeline.
Gaskets at the
flowmeter protrude into
the pipe bore.
Irregularities on the
surface of the pipe bore.
Signal falsified due to
bi-phase medium.
Insufficient upstream/
downstream pipe
lengths.
Flow direction reversed.
and rectify as above.
Check current output electronics (refer
to Sections 4.6, 4.7 and 4.8).
and rectify as above.
Check current output electronics
(refer to Sections 4.6, 4.7 and 4.8).
The axis of the flowmeter bore should
be aligned with that of the pipe.
See Section 3, Figures 16, 17 and 18
for proper installation of gaskets.
Pipe bore should be free of
irregularities.
Bi-phase media are not permitted.
Use a separator for wet steam droplets
from the steam.
See Section 3 for correct lengths of
upstream and downstream pipes.
Check flow direction arrow
on primary.
Pulse output is
incorrect
Pulse output incorrectly
set.
Pulse width incorrectly
set.
Pulse output is
overloaded.
Pulse output electronics
faulty.
Check programming of pulse output,
Section 4.6.7.
Check maximum pulse width of
counter electronics.
Check load ratings.
Test pulse output.
If faulty replace unit.
IM-P192-02 MI Issue 250
SymptomPossible causeAction
TVA produces
large amount of
noise (banging and
clattering)
Non zero flow
indicated when no
actual flow is in the
pipe.
RS232/Modbus
communications
not working
Additional fault finding for versions with RS485 conversion board fitted.
SymptomPossible causeAction
No power and no
diodes lit up.
Upstream/downstream
installation lengths
incorrect.
Unit not zeroed at
commissioning.
4 mA output not
calibrated.
4 mA retransmission set
to a value higher than
zero.
Interference.
CTR/DTS not
connected/powered.
No power to terminals
4 and 5
Power to terminals 4
and 5 wrong way round.
Re-install following the installation
guidelines (Section 3).
Zero unit.
Calibrate 4 mA output (Section 4.6.5).
Reset 4 mA.
Check earthing.
Connect CTR/DTS terminals
Check power supply.
Connect to terminals 4 and 5 correct
way round.
No communication,
Green diode lit
only.
No communication,
Green diode lit,
Yellow diode
flashing, blue
diode off.
IM-P192-02 MI Issue 251
No query received from
computer system.
A and B wires
connected wrong way
round.
Baud rate set wrong.Change baud rate.
ASCII / Modbus
selected wrong.
Check communication cable
connection.
Wrong configuration of computer
system (wrong port, etc.)
Connect A and B wires correct way
round.
Change ASCII to Modbus or Modbus to
ASCII.
8. Settings table
This Table shows all changeable options, and enables records to be made of any changes
made to the pass code or other settings. It provides a convenient reference should future
changes be required.
Sub-menu
Basic data
Outputs
ErrorHigh
Pass code745 2
Changeable
settings
Dryness fraction1.0
UnitsMetric
Nominal pressure
Atmospheric pressure1.01 bar a
4-20 mA
Source dataFlow
4 mA setting0
20 mA setting
PulseON
Source dataTota l
Number of pulses1 per kg
Pulse width50 mS
Factory
settings
Flowmeter
maximum
@ 32 bar g
Customer
settings
Further
changes
IM-P192-02 MI Issue 252
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.